This section provides a brief introduction to some of the options available for our ELI
system.
11.1
Emergency Stop Switch
This switch is used to immediately remove power from the load in the event of an
emergency condition e.g. electrical shock, burning of the load or water located
around the ELI. When the emergency stop button is pushed, the inverter will stop
running immediately and the static switch does not activate. There will be no AC
supply at the output.
This shutdown condition is latched until a manual reset has been performed.
Manual reset is performed by pressing the inverter off switch (
O
) and the inverter
control switch (WX) simultaneously. Once the system is reset follow the Start-up
procedure discussed earlier to turn the system back on.
11.2
Remote Display Panel
The remote panel is a display module with LCD and LED’s that can monitor 1 –
99 ELI’s via a DB9 connected in series from distance < 1000m. It allows for
remote monitoring of the ELI status and alarms.
11.3
12 Pulse Rectifier
Located inside the ELI system cabinet. The 12-pulse rectifier is an optional
feature for 8KW to 48KW systems. The 12-pulse rectifier is designed to reduce
the input harmonic distortion to less than 2%.
11.4
External Wrap Around Bypass
A separate cabinet that allows for complete removal of the ELI system from the
load, while still supplying the load with conditioned power. Systems can include
isolation transformer for different voltage configurations, distribution panels and
Kirk-Key interlock protection to ensure proper operation.
11.5
Normally Off Function
All Normally Off loads shall not exceed 50% of the ELI rating per phase.
45
Warning!
Similar products from other manufacturers will not fit into our ELI systems.
The installation of any option requires professional settings and should only be
performed by the factory or factory trained representatives.