INSTALLATION PROCEDURES
Carpentry Procedures
Case Pull-Up Locations
All the N7DNL and NHD models have four
pull-ups at each end of the case. Pull-ups A,
B, C and D are located as shown and should
be installed and tightened starting with A and
finishing with D.
NOTE
If extra pull-up bolts are needed, use the
bolts from the side shipping supports.
See “General-UL/NSF I&S Manual” for
line-up assembly instructions.
Electrical Procedures
Electrical Considerations
CAUTION
Make sure all electrical connections at
components and terminal blocks are tight.
This will prevent burning of electrical
terminals and/or premature component
failure.
NOTE
Raceway covers will be shipped loose.
See the “General-UL/NSF I&S Manual” for
raceway cover installation and removal
instructions.
Case Fan Circuit
This circuit is to be supplied by an uninter-
rupted, protected 120V circuit. The case fan
circuit is not cycled, except when equipped
for gas defrost (NHD models only). On gas
defrost cases the fans circuit is controlled by
a klixon.
Fluorescent Lamp Circuit
The standard lighting for N7DNL and NHD
cases is 2 rows of T-8 canopy lights. Optional
T-8 Nose Light is available on all models,
while T-8 shelf lighting is only available on
the NHD models.
Defrost Information
See “General-UL/NSF I&S Manual” for
operational descriptions for each type of
defrost control.
Defrost Control Charts
N7DNL Models
Defrost
Defrost
Defrosts Duration
Term.
Type
Per Day
(Min)
Temp.
Off Time
6
19
------
The N7DNL cases do not have any klixons.
NHD Models
Defrost
Defrost
Defrosts Duration
Term.
Type
Per Day
(Min)
Temp.
Off Time
4
24
------
Electric
4
24
41°F
Gas
4
15
55°F
Most klixons are located on the right end of
the evaporator coil.
NOTE
The Gas Defrost Termination klixon is
located at the by-pass check valve.
CAUTION
If electronic sensors are used in place of
the klixons, the sensors must be located in
the same location as the klixons for that
defrost type. Any other locations will
effect the refrigeration efficiency of the
case.
June, 2007
Page 8
Summary of Contents for N7DNL
Page 5: ...April 2008 Page 5 ...
Page 6: ...Page 6 April 2008 NHD L M Extended Height Multi Shelf Medium Temp Merchandisers ...
Page 7: ...April 2008 Page 7 ...
Page 10: ...June 2007 Page 10 N7DNL Domestic Export 50 Hz Case Circuits 12 Cases ...
Page 11: ...June 2007 Page 11 NHD L M Domestic Export 50 Hz Case Circuits 6 8 Cases ...
Page 12: ...Page 12 June 2007 ...
Page 13: ...June 2007 Page 13 NHD L M Domestic Export 50 Hz Case Circuits 12 Cases ...
Page 14: ...Page 14 June 2007 ...
Page 25: ...Installation Service Manual N7DNL NHD June 2007 Page 25 NHDM ILLUSTRATED ...