TYM 1000/2000 Slide Gate Operator Installation Guide
- 14 -
Rev 9 02/14
Advanced Controller
Programming
Entering Advanced Programming Mode
To access and program the Advanced Programming
functions, for each programming session, Advanced
Programming must be enabled.
After exiting programming, the Advanced Programming
functions will be available on the programming display during
the next programming session unless the operator has run
50 or more cycles. After that, Advanced Programming must
be enabled again.
Maximum Run Time
The factory default for the Maximum Run Time (MRT) is
99 seconds. When the operator starts, a timer will begin
counting. If an open or close limit is not reached or an
obstacle or reversing input is not received before the timer
expires, the operator will stop, the unit locks out and the
alarm sounds. The timer can be set for 10 to 99 seconds.
See p. 27 for reset
Single Button Input Setup
This function is used for selecting the operation for single
button controls and radio receivers.
The factory default sets the SINGLE input terminal so
successive inputs will cycle the operator in OPEN-STOP-
CLOSE-STOP order.
Alternately, the SINGLE input can be set to cause the gate
to OPEN unless the gate is fully open. If the gate is fully
open, the input will cause the gate to CLOSE.
Stagger Mode
(Rarely used in slide gate installations)
This function is used in dual gate installations only. The
factory default sets the Stagger Mode to OFF. In dual gate
installations the two operators communicate through the
3-wire COMM LINK interface. When using the Stagger
Mode, set one operator for delayed opening and the other
operator for delayed closing. The Stagger Delay Time
programming function (see below) sets the length of the
delay.
3
NOTE: This function will only be displayed if dual gate
operation is selected.
FUNCTION
ADVANCED PROGRAMMING FUNCTIONS
WILL NOT BE DISPLAYED
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
ADVANCED
PROGRAMMING
"AD"
ADVANCED PROGRAMMING OPTIONS
WILL BE DISPLAYED
NOTE: ADVANCED PROGRAMMING
WILL STAY ENABLED AFTER
EXITING PROGRAMMING UNTIL
THE GATE CYCLES 50 TIMES
FUNCTION
SINGLE INPUT WILL OPEN OPERATOR,
IF OPERATOR IS ALREADY OPEN, SINGLE
INPUT WILL CLOSE OPERATOR
SINGLE INPUT WILL CYCLE OPERATOR
IN ORDER OF OPEN-STOP-CLOSE-STOP
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
SINGLE BUTTON
INPUT SETUP
"SB"
FUNCTION
SETS THIS OPERATOR FOR
DELAYED OPEN
DISABLES STAGGER FUNCTION
SETS THIS OPERATOR FOR
DELAYED CLOSE
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
STAGGER
MODE
"SM"
DUAL GATES
ONLY
FUNCTION
PRESS ENTER FOR 1 SECOND
WHILE DISPLAY IS FLASHING, PRESS
UP OR DOWN TO CHANGE THE
MAXIMUM RUN TIME (10-99 SECONDS)
OPTIONS
MAXIMUM RUN
TIMER
DISPLAY SHOWS CURRENT
MAXIMUM RUN TIME SETTING
ENTER
ENTER
PRESS ENTER TO STORE THE VALUE
"RT"