background image

 

Doc

 

No.

 

FM0589

 

issue

 

A

 

Page

 

10

 

 

5.

 

LOCK

 

RELEASE

 

 

The

 

choice

 

of

 

electric

 

lock

 

release

 

lock

 

is

 

left

 

to

 

the

 

installer

 

so

 

the

 

most

 

appropriate

 

type

 

and

 

mounting

 

kit

 

can

 

be

 

obtained

 

for

 

each

 

installation.

 

 

The

 

lock

 

chosen

 

should

 

operate

 

from

 

12V

 

DC

 

for

 

direct

 

connection

 

to

 

the

 

Entel

 

i2

 

door

 

panel,

 

if

 

an

 

AC

 

lock

 

or

 

higher

 

voltage

 

DC

 

lock

 

is

 

used

 

then

 

a

 

separate

 

PSU

 

will

 

be

 

required.

 

 

5.01

 

12V

 

DC

 

LOCK

 

CONNECTION

 

 

The

 

lock

 

release

 

is

 

connected

 

directly

 

across

 

the

 

door

 

panel

 

Lock

 

Supply

 

(

LKSP

)

 

and

 

Lock

 

Return

 

(

LKRT

)

 

terminals

 

using

 

1.0mm

 

cable.

 

 

The

 

LKSP

 

terminal

 

is

 

a

 

+12V

 

DC

 

supply

 

fused

 

at

 

1A.

 

The

 

LKRT

 

terminal

 

is

 

a

 

switched

 

0V.

  

 
 

  

LKRT

  

                 

DC

 

LOCK

 

ONLY

 

 

         

LKSP

 

 
 
 

 

IMPORTANT

 

 

A

 

reverse

 

bias

 

diode

 

or

 

a

 

varistor/MOV

 

must

 

be

 

fitted

 

directly

 

across

 

all

 

DC

 

lock

 

terminals

 

to

 

prevent

 

back

 

emf

 

from

 

the

 

lock

 

coil

 

causing

 

malfunction

 

and

 

possible

 

long

 

term

 

damage

 

to

 

the

 

Entel

 

i2

 

door

 

panel.

 

 

 

Diode

 

Type:

 

1N4001

   

or

   

MOV

 

Type:

 

GNR07D330K

 

 

5.02

 

LOCK

 

TYPE

 

LINK

 

SETTING

 

 

A

 

link

 

setting

 

is

 

provided

 

on

 

the

 

door

 

panel

 

board

 

to

 

choose

 

a

 

standard

 

(fail

 

secure)

 

or

 

fail

 

safe

 

lock

 

type.

  

With

 

LK1

 

in

 

position

 

A

 

0V

 

is

 

applied

 

during

 

the

 

lock

 

release

 

period.

 

With

 

LK1

 

in

 

position

 

B

 

0V

 

is

 

removed

 

during

 

the

 

lock

 

release

 

period.

 

 

 

LINK

 

No.

 

LINK

 

POSITION

 

'A

'

 

LINK

 

POSITION

 

'B'

 

 

 

 

LK1

 

standard

 

lock

 

fail

 

safe

 

lock

 

 

A

 

standard

 

lock

 

requires

 

power

 

to

 

unlock

 

(fail

 

secure).

 

A

 

fail

 

safe

 

lock

 

requires

 

power

 

to

 

lock

 

(fail

 

open).

 

 

5.03

 

LOCK

 

RELEASE

 

DURATION

 

 

The

 

time

 

the

 

lock

 

release

 

remains

 

open

 

is

 

programmable

 

from

 

1

 

to

 

99

 

seconds,

 

see

 

section

 

7.09.

  

 

5.04

 

PRESS

 

TO

 

EXIT

 

(PTE)

 

CONNECTION

 

 

A

 

N/O

 

press

 

to

 

exit

 

button

 

can

 

be

 

connected

 

across

 

the

 

0V

 

and

 

EXLK

 

terminals

 

in

 

the

 

door

 

panel

 

to

 

override

 

the

 

lock

 

release

 

and

 

allow

 

egress

 

from

 

the

 

building.

 

For

 

added

 

safety

 

it

 

is

 

recommended

 

that

 

the

 

PTE

 

button

 

N/C

 

contacts

 

are

 

also

 

connected

 

in

 

series

 

with

 

the

 

lock

 

supply

 

wiring

 

on

 

fail

 

safe

 

locks.

 

 

5.05

 

TAILGATE

 

CONNECTION

 

 

A

 

N/C

 

door

 

contact

 

should

 

be

 

connected

 

across

 

the

 

0V

 

and

 

T/G

 

terminals

 

in

 

the

 

door

 

panel

 

to

 

detect

 

when

 

the

 

door

 

is

 

opened.

 

This

 

will

 

automatically

 

terminate

 

the

 

lock

 

timer

 

2

 

seconds

 

after

 

the

 

door

 

re

closes

 

and

 

reduce

 

the

 

likelihood

 

of

 

other

 

visitors

 

entering

 

during

 

the

 

same

 

lock

 

release

 

period.

  

 

The

 

contact

 

is

 

also

 

used

 

to

 

illuminate

 

the

 

telephone

 

LED’s

 

green

 

to

 

indicate

 

“door

 

open”.

 

If

 

a

 

door

 

contact

 

is

 

not

 

fitted

 

then

 

T/G

 

must

 

be

 

linked

 

to

 

0V

 

and

 

the

 

telephone

 

door

 

open

 

LED’s

 

will

 

not

 

function.

  

 

Summary of Contents for ENTEL i2

Page 1: ...product improvement and reserves the right to modify the specification of its products If any variation to the details in this document are suspected please contact Tynetec s Technical Support on 01670 352371 Tynetec a business unit of Legrand Electric Ltd Unit 10 Cowley Road Blyth Riverside Business Park Blyth Northumberland NE24 5TF Tel 01670 352 371 Fax 01670 362 807 Email sales tynetec co uk W...

Page 2: ...oc No FM0589 issue A Page 2 CONTENTS Section Topic Page 1 Overview 3 2 Controller 4 3 Door Panels 5 4 Telephones 8 5 Lock Release 10 6 Easikey Option 11 7 Programming 12 8 Test Mode 16 9 Commissioning 18 ...

Page 3: ...anel and the controller 1 x 4 pair 0 5mm CW1308 BT spec Line Power Connection 1 x 2 5mm Earth If a Oneprox reader is fitted in the door panel then an additional 6 core 7 0 2 cable will be required to the PAC Easikey controller Note door panel backboxes and fascias must be bonded to the spare Mains Earth terminal in the controller using a 2 5 mm2 cable Cable length to a door panel should not exceed...

Page 4: ...e IP65 rating of the enclosure 2 02 EARTH BONDING All door entry metalwork eg controller cabinet door panel backbox fascia fireman s switches etc must be bonded to Earth via the Mains Earth terminal using a minimum of 2 5 mm2 cable 2 03 MAINS SUPPLY The 240V AC mains connection should be taken from the landlords supply and terminated in the fused screw terminal block provided in the controller Rep...

Page 5: ...N All door panels have a 40mm square cut out and 4 off M3 x 20mm studs for a PAC 20049 Oneprox panel mount reader ordered separately If the reader is not supplied then a Tynetec Logo blanking plate is fitted Door panels with a PAC reader fitted will require an additional 6 core 7 0 2mm cable connected to the PAC Easikey controller see section 6 3 03 TRADE TIMES The door panel has an integral real ...

Page 6: ... components or keypad Cable entry into the backbox should be through the side or rear 20mm knockouts provided Important the backbox and fascia must be bonded to the spare Earth terminal in the controller using 2 5 mm2 cable The height above finished floor level at which the backbox is mounted should be clarified with the Supervising Officer The backbox should be cut into the brick work or door scr...

Page 7: ...RING FROM CONTROLLER The 4 pair cable must be looped once through the ferrite core before being connected to the door panel board The ferrite core suppresses Electro Static Discharge ESD transients which could otherwise travel down the wiring and cause damage to components in the door panel 3 08 DOOR PANEL CONNECTION Two separate cables should be installed from the controller to the door panel a 4...

Page 8: ... FUNCTION When the telephone has been called and the handset is lifted the pushbutton is used to release the door lock The lock release duration is programmable from 1 to 99 seconds see section 7 09 4 03 DOOR OPEN INDICATION The LED indicator will illuminate green on all telephones when the entrance door is open provided a N C door contact is connected across the door panel T G 0V terminals Note t...

Page 9: ...phone ID s must run sequentially starting from 1 through to 15 For ease of programming set telephone ID 1 in the lowest flat number in the building TEL ID DIL SWITCH NUMBER 1 2 3 4 1 ON OFF OFF OFF 2 OFF ON OFF OFF 3 ON ON OFF OFF 4 OFF OFF ON OFF 5 ON OFF ON OFF 6 OFF ON ON OFF 7 ON ON ON OFF 8 OFF OFF OFF ON 9 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF...

Page 10: ...pplied during the lock release period With LK1 in position B 0V is removed during the lock release period LINK No LINK POSITION A LINK POSITION B LK1 standard lock fail safe lock A standard lock requires power to unlock fail secure A fail safe lock requires power to lock fail open 5 03 LOCK RELEASE DURATION The time the lock release remains open is programmable from 1 to 99 seconds see section 7 0...

Page 11: ...resistant stainless steel readers can be surface mounted separately The Easikey 250 controller is available in its own metal box complete with power supply or unboxed with an inner door mounting kit for fitting inside the Entel i2 controller A maximum of 250 Oneprox tokens can be used with the Easikey 250 system Up to 3 of these tokens must be retained as Editors which are needed when adding delet...

Page 12: ...to 99 Secs 10 Secs 10 Set Telephone Privacy Time 0 on off or 1 to 99 Mins 10 Mins 11 Set Door Panel Audio Level 1 to 5 3 12 Set Telephone Audio Level 1 to 5 3 13 Set Number of Ring Cycles 1 to 10 5 14 Set Trade Start Time 1 00 00 15 Set Trade Stop Time 1 00 00 16 Set Trade Start Time 2 00 00 17 Set Trade Stop Time 2 00 00 18 Set Trade Start Time 3 00 00 19 Set Trade Stop Time 3 00 00 20 Enable Dis...

Page 13: ...de Note the day and year is not cleared if defaults are loaded 7 05 ASSIGN ENTRANCE KEYS TO TELEPHONES This allows the door panel buttons to be set to call the correct telephones Press 5 and a message will announce Assign Entrance Keys Press the door panel buttons in order from lowest to highest flat number See Note After each door panel key press a message will announce Handset 1 Handset 2 etc If...

Page 14: ... for which a telephone can be turned off by the user 1 to 99 minutes If set to 0 the telephone can be switched on off manually without a timed automatic reset Press 10 and a message will announce Privacy Time 10 Minutes e g current setting Enter a new privacy time MM 1 to 99 minutes followed by enter 0 for on off A message will announce the new privacy time setting Privacy Time MM Minutes Ready 7 ...

Page 15: ...t Time 2 Press 17 for Trade Stop Time 2 Press 18 for Trade Start Time 3 Press 19 for Trade Stop Time 3 7 17 ENABLE DISABLE TRADE OPERATION If enabled the door panel TRADE button will release the door lock or the lock will be released for the entire Trade period if no Trade button is enabled If disabled the Trade periods set above will be ignored they are retained in memory if they need to be re en...

Page 16: ...nce Test Mode Disabled When a test option is selected you have 15 minutes to perform the test 8 01 TEST 1 HANDSET TEST Press ENTER and the door panel will announce Handset Test Please Wait After a short delay the door panel should announce Zero Faults followed by Test 1 Handset Test If faults exist the telephone ID s with faults will be announced Check the wiring ID settings in these telephones Pr...

Page 17: ...ift the handset and press the lock button You will hear a message recorded in TEST 3 playback in the earpiece Press again to repeat the message Return to the door panel and press EXIT The door panel will announce the current test mode Press UP to select the next test 8 06 TEST 6 HANDSET RING LEVEL Press ENTER and the door panel will announce Handset Ring Level Press Lock Key to Start Go to a telep...

Page 18: ...ime period the door panel TRADE button should not function Enter program mode and reset the system time to within a trade time period Exit program mode Press the door panel TRADE button a message should announce Door Open Please Enter and the door lock will release Return to the program mode and reset the correct time 9 02 TYPICAL FAULTS FAULT POSSIBLE CAUSE Door panel dead 12V Supply LED not lit ...

Page 19: ...ume Default 3 Level ___ Press to Exit Button Fitted Yes No Telephone Volume Default 3 Level ___ Door Lock Type Fail Safe Fail Secure Flat No Speech Enabled Disabled Firmware Version V _____ Controller Part No ZE200I Other ___________ Serial No ________________ Trade Times Trade Option Enabled Disabled Trade Period 1 Start ___ ___ Stop ___ ___ Auto BST Enabled Disabled Trade Period 2 Start ___ ___ ...

Page 20: ...A Page 20 Tynetec a business unit of Legrand Electric Ltd Unit 10 Cowley Road Blyth Riverside Business Park Blyth Northumberland NE24 5TF Tel 01670 352 371 Fax 01670 362 807 Email sales tynetec co uk Web www tynetec co uk ...

Reviews: