background image

 

Doc

 

No.

 

FM0589

 

issue

 

A

 

Page

 

13

 

 

7.

 

PROGRAMMING

 

 

7.01

 

LOAD

 

SYSTEM

 

DEFAULTS

 

 

This

 

will

 

clear

 

all

 

programming

 

back

 

to

 

the

 

factory

 

defaults

 

listed

 

in

 

the

 

table

 

on

 

the

 

previous

 

page.

 

 

Press

 

1

 

 

and

 

a

 

message

 

will

 

announce

 

Load

 

Defaults

 

Press

 

 

and

 

a

 

message

 

will

 

announce

 

Defaults

 

Loaded

 

 

Ready

 

If

 

you

 

don’t

 

want

 

to

 

load

 

defaults

 

press

 

#

 

to

 

exit

 

the

 

mode

 

 

7.02

 

SET

 

TIME

 

 

Press

 

2

 

 

and

 

a

 

message

 

will

 

announce

 

Time

 

15

 

50

 

(e.g.

 

current

 

time

 

3:50

 

PM)

 

Enter

 

the

 

correct

 

time

 

HHMM

 

(24

 

hour

 

format)

 

followed

 

by

 

  

A

 

message

 

will

 

announce

 

the

 

new

 

time

 

setting

 

Time

 

HHMM

 

 

Ready

 

If

 

you

 

don’t

 

want

 

to

 

change

 

the

 

time

 

setting

 

press

 

#

 

to

 

exit

 

the

 

mode

 

Note:

 

the

 

time

 

is

 

not

 

cleared

 

if

 

defaults

 

are

 

loaded.

 

 

7.03

 

SET

 

DATE

 

 

Press

 

3

 

 

and

 

a

 

message

 

will

 

announce

 

Date

 

09

 

04

 

(e.g.

 

current

 

date

 

9

th

 

April)

 

Enter

 

the

 

correct

 

date

 

DDMM

 

(date

 

&

 

month)

 

followed

 

by

 

  

A

 

message

 

will

 

announce

 

the

 

new

 

date

 

setting

 

Date

 

DDMM

 

 

Ready

 

If

 

you

 

don’t

 

want

 

to

 

change

 

the

 

date

 

setting

 

press

 

#

 

to

 

exit

 

the

 

mode

 

Note:

 

the

 

date

 

&

 

month

 

is

 

not

 

cleared

 

if

 

defaults

 

are

 

loaded.

 

 

7.04

 

SET

 

DAY

 

AND

 

YEAR

 

 

Press

 

4

 

 

and

 

a

 

message

 

will

 

announce

 

Day

 

and

 

Year

 

05

 

10

 

(e.g.

 

Friday

 

2010)

  

01

 

=

 

Monday

 

Enter

 

the

 

correct

 

day

 

and

 

year

 

DDYY

 

 

followed

 

by

 

  

A

 

message

 

will

 

announce

 

the

 

new

 

day

 

and

 

year

 

setting

 

Day

 

and

 

Year

 

DDYY

 

 

Ready

 

If

 

you

 

don’t

 

want

 

to

 

change

 

the

 

day

 

and

 

year

 

setting

 

press

 

#

 

to

 

exit

 

the

 

mode

 

Note:

 

the

 

day

 

and

 

year

 

is

 

not

 

cleared

 

if

 

defaults

 

are

 

loaded.

 

 

7.05

 

ASSIGN

 

ENTRANCE

 

KEYS

 

TO

 

TELEPHONES

 

 

This

 

allows

 

the

 

door

 

panel

 

buttons

 

to

 

be

 

set

 

to

 

call

 

the

 

correct

 

telephones.

 

 

Press

 

5

 

 

and

 

a

 

message

 

will

 

announce

 

Assign

 

Entrance

 

Keys

  

Press

 

the

 

door

 

panel

 

buttons

 

in

 

order

 

from

 

lowest

 

to

 

highest

 

flat

 

number

 

 

See

 

Note

 

After

 

each

 

door

 

panel

 

key

 

press

 

a

 

message

 

will

 

announce

 

“Handset

 

1”

 

 

“Handset

 

2”

 

…etc

 

If

 

the

 

door

 

panel

 

has

 

a

 

TRADE

 

button

 

press

 

this

 

twice

 

after

 

the

 

last

 

flat

 

number

 

A

 

message

 

will

 

announce

 

“Trade”

 

Press

 

 

and

 

a

 

message

 

will

 

announce

 

Entrance

 

Keys

 

Saved

 

 

Ready

 

 

 

this

 

assumes

 

the

 

telephone

 

ID’s

 

have

 

been

 

set

 

starting

 

with

 

ID

 

1

 

in

 

the

 

lowest

 

flat

 

number

 

and

 

running

 

sequentially.

 

If

 

this

 

is

 

not

 

the

 

case

 

press

 

the

 

flat

 

numbers

 

in

 

order

 

of

 

the

 

telephone

 

ID’s.

 

 

7.06

 

ASSIGN

 

FLAT

 

NUMBERS

 

TO

 

TELEPHONES

 

 

This

 

allows

 

the

 

actual

 

flat

 

number

 

to

 

be

 

announced

 

when

 

the

 

telephone

 

is

 

being

 

called.

 

 

Press

 

6

 

 

and

 

a

 

message

 

will

 

announce

 

Assign

 

Flat

 

Numbers”

 

followed

 

by

 

“Handset

 

1

 

 

Flat

 

Number

 

1

 

If

 

telephone

 

ID

 

1

 

is

 

fitted

 

in

 

flat

 

number

 

1

 

then

 

press

 

the

 

 

key,

 

if

 

not…

   

Enter

 

the

 

flat

 

number

 

NN

 

which

 

has

 

telephone

 

ID

 

1

 

fitted

 

followed

 

by

 

the

 

 

key

 

A

 

message

 

will

 

announce

 

“Handset

 

1

 

 

Flat

 

Number

 

NN

 

followed

 

by

 

“Handset

 

2

 

 

Flat

 

Number

 

2

 

Repeat

 

for

 

all

 

flat

 

numbers

 

with

 

telephones

 

fitted

 

 

Note:

 

from

 

new,

 

or

 

if

 

defaults

 

are

 

reloaded

 

the

 

door

 

panel

 

will

 

not

 

announce

 

flat

 

numbers

 

 

to

 

enable

 

this

 

feature

 

see

 

section

 

7.07.

 

Flat

 

numbers

 

can

 

be

 

a

 

maximum

 

of

 

4

 

digits,

 

alpha

 

numeric

 

numbers

 

e.g.

 

1A,

 

1B,

 

etc.

 

are

 

not

 

possible.

  

 
 
 
 
 

Summary of Contents for ENTEL i2

Page 1: ...product improvement and reserves the right to modify the specification of its products If any variation to the details in this document are suspected please contact Tynetec s Technical Support on 01670 352371 Tynetec a business unit of Legrand Electric Ltd Unit 10 Cowley Road Blyth Riverside Business Park Blyth Northumberland NE24 5TF Tel 01670 352 371 Fax 01670 362 807 Email sales tynetec co uk W...

Page 2: ...oc No FM0589 issue A Page 2 CONTENTS Section Topic Page 1 Overview 3 2 Controller 4 3 Door Panels 5 4 Telephones 8 5 Lock Release 10 6 Easikey Option 11 7 Programming 12 8 Test Mode 16 9 Commissioning 18 ...

Page 3: ...anel and the controller 1 x 4 pair 0 5mm CW1308 BT spec Line Power Connection 1 x 2 5mm Earth If a Oneprox reader is fitted in the door panel then an additional 6 core 7 0 2 cable will be required to the PAC Easikey controller Note door panel backboxes and fascias must be bonded to the spare Mains Earth terminal in the controller using a 2 5 mm2 cable Cable length to a door panel should not exceed...

Page 4: ...e IP65 rating of the enclosure 2 02 EARTH BONDING All door entry metalwork eg controller cabinet door panel backbox fascia fireman s switches etc must be bonded to Earth via the Mains Earth terminal using a minimum of 2 5 mm2 cable 2 03 MAINS SUPPLY The 240V AC mains connection should be taken from the landlords supply and terminated in the fused screw terminal block provided in the controller Rep...

Page 5: ...N All door panels have a 40mm square cut out and 4 off M3 x 20mm studs for a PAC 20049 Oneprox panel mount reader ordered separately If the reader is not supplied then a Tynetec Logo blanking plate is fitted Door panels with a PAC reader fitted will require an additional 6 core 7 0 2mm cable connected to the PAC Easikey controller see section 6 3 03 TRADE TIMES The door panel has an integral real ...

Page 6: ... components or keypad Cable entry into the backbox should be through the side or rear 20mm knockouts provided Important the backbox and fascia must be bonded to the spare Earth terminal in the controller using 2 5 mm2 cable The height above finished floor level at which the backbox is mounted should be clarified with the Supervising Officer The backbox should be cut into the brick work or door scr...

Page 7: ...RING FROM CONTROLLER The 4 pair cable must be looped once through the ferrite core before being connected to the door panel board The ferrite core suppresses Electro Static Discharge ESD transients which could otherwise travel down the wiring and cause damage to components in the door panel 3 08 DOOR PANEL CONNECTION Two separate cables should be installed from the controller to the door panel a 4...

Page 8: ... FUNCTION When the telephone has been called and the handset is lifted the pushbutton is used to release the door lock The lock release duration is programmable from 1 to 99 seconds see section 7 09 4 03 DOOR OPEN INDICATION The LED indicator will illuminate green on all telephones when the entrance door is open provided a N C door contact is connected across the door panel T G 0V terminals Note t...

Page 9: ...phone ID s must run sequentially starting from 1 through to 15 For ease of programming set telephone ID 1 in the lowest flat number in the building TEL ID DIL SWITCH NUMBER 1 2 3 4 1 ON OFF OFF OFF 2 OFF ON OFF OFF 3 ON ON OFF OFF 4 OFF OFF ON OFF 5 ON OFF ON OFF 6 OFF ON ON OFF 7 ON ON ON OFF 8 OFF OFF OFF ON 9 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF...

Page 10: ...pplied during the lock release period With LK1 in position B 0V is removed during the lock release period LINK No LINK POSITION A LINK POSITION B LK1 standard lock fail safe lock A standard lock requires power to unlock fail secure A fail safe lock requires power to lock fail open 5 03 LOCK RELEASE DURATION The time the lock release remains open is programmable from 1 to 99 seconds see section 7 0...

Page 11: ...resistant stainless steel readers can be surface mounted separately The Easikey 250 controller is available in its own metal box complete with power supply or unboxed with an inner door mounting kit for fitting inside the Entel i2 controller A maximum of 250 Oneprox tokens can be used with the Easikey 250 system Up to 3 of these tokens must be retained as Editors which are needed when adding delet...

Page 12: ...to 99 Secs 10 Secs 10 Set Telephone Privacy Time 0 on off or 1 to 99 Mins 10 Mins 11 Set Door Panel Audio Level 1 to 5 3 12 Set Telephone Audio Level 1 to 5 3 13 Set Number of Ring Cycles 1 to 10 5 14 Set Trade Start Time 1 00 00 15 Set Trade Stop Time 1 00 00 16 Set Trade Start Time 2 00 00 17 Set Trade Stop Time 2 00 00 18 Set Trade Start Time 3 00 00 19 Set Trade Stop Time 3 00 00 20 Enable Dis...

Page 13: ...de Note the day and year is not cleared if defaults are loaded 7 05 ASSIGN ENTRANCE KEYS TO TELEPHONES This allows the door panel buttons to be set to call the correct telephones Press 5 and a message will announce Assign Entrance Keys Press the door panel buttons in order from lowest to highest flat number See Note After each door panel key press a message will announce Handset 1 Handset 2 etc If...

Page 14: ... for which a telephone can be turned off by the user 1 to 99 minutes If set to 0 the telephone can be switched on off manually without a timed automatic reset Press 10 and a message will announce Privacy Time 10 Minutes e g current setting Enter a new privacy time MM 1 to 99 minutes followed by enter 0 for on off A message will announce the new privacy time setting Privacy Time MM Minutes Ready 7 ...

Page 15: ...t Time 2 Press 17 for Trade Stop Time 2 Press 18 for Trade Start Time 3 Press 19 for Trade Stop Time 3 7 17 ENABLE DISABLE TRADE OPERATION If enabled the door panel TRADE button will release the door lock or the lock will be released for the entire Trade period if no Trade button is enabled If disabled the Trade periods set above will be ignored they are retained in memory if they need to be re en...

Page 16: ...nce Test Mode Disabled When a test option is selected you have 15 minutes to perform the test 8 01 TEST 1 HANDSET TEST Press ENTER and the door panel will announce Handset Test Please Wait After a short delay the door panel should announce Zero Faults followed by Test 1 Handset Test If faults exist the telephone ID s with faults will be announced Check the wiring ID settings in these telephones Pr...

Page 17: ...ift the handset and press the lock button You will hear a message recorded in TEST 3 playback in the earpiece Press again to repeat the message Return to the door panel and press EXIT The door panel will announce the current test mode Press UP to select the next test 8 06 TEST 6 HANDSET RING LEVEL Press ENTER and the door panel will announce Handset Ring Level Press Lock Key to Start Go to a telep...

Page 18: ...ime period the door panel TRADE button should not function Enter program mode and reset the system time to within a trade time period Exit program mode Press the door panel TRADE button a message should announce Door Open Please Enter and the door lock will release Return to the program mode and reset the correct time 9 02 TYPICAL FAULTS FAULT POSSIBLE CAUSE Door panel dead 12V Supply LED not lit ...

Page 19: ...ume Default 3 Level ___ Press to Exit Button Fitted Yes No Telephone Volume Default 3 Level ___ Door Lock Type Fail Safe Fail Secure Flat No Speech Enabled Disabled Firmware Version V _____ Controller Part No ZE200I Other ___________ Serial No ________________ Trade Times Trade Option Enabled Disabled Trade Period 1 Start ___ ___ Stop ___ ___ Auto BST Enabled Disabled Trade Period 2 Start ___ ___ ...

Page 20: ...A Page 20 Tynetec a business unit of Legrand Electric Ltd Unit 10 Cowley Road Blyth Riverside Business Park Blyth Northumberland NE24 5TF Tel 01670 352 371 Fax 01670 362 807 Email sales tynetec co uk Web www tynetec co uk ...

Reviews: