background image

using the furnished connector.  Connect the wire
to the load side of the switch.  Connect the line side
of the remote switch to fused, positive battery.
The actual load draw through the remote switch is
less than .1 amp.  The fuse should not be larger
than the amp capacity of the switch or the hookup
wire.  A recommended fuse is a Bussman SFE-4
or Littlefuse 311-004.
   3.07  120 VAC Output
        3.07.1
 The 120 VAC output of the inverter
is provided by the GFCI receptacle output on the
front of the inverter.

 4. START UP  /   OPERATION
     4.01 
To operate the inverter turn the switch to
“ON”.  Make sure that the output breaker and
Ground Fault Circuit Interrupter are reset.
     4.02  Turn the switch to “Off” when not in use.

 5.  TROUBLESHOOTING
    5.01
  Dimensions  offers free phone consulta-
tion concerning installation or troubleshooting.  Call
the Customer Service Department at 800-553-
6418 or (651) 653-7000, fax: 651-653-7600; e-
mail: inverterinfo@sensata.com

   5.02 If the inverter fails to operate, use the
following troubleshooting procedure.
     5.02.1 Connect a 100 watt light bulb to the
inverter output.
      5.02.2  Make sure the inverter is turned on,
the output circuit breaker is reset and that the line
fuse is good.
     5.02.3 Observe the fault indicating light on the
front of the inverter. If the low battery light is lit,
turn inverter “Off” for 5 seconds, then turn “On”
again.  If the low battery light turns on again, check
battery wiring, battery state-of-charge and volt-
age.
       5.02.4 If the inverter feels hot, it may have
shut down by over temperature. The inverter

must be left to cool to 40 degrees C (104 degrees
F).  Check to see that the inverter is not in a closed
compartment.
             5.02.5    If the above steps are com-
pleted and the inverter still will not operate satisfac-
torily call Sensata for a return authorization num-
ber.

Page 4

Reviews: