 R-600A Specifications 2

u-line.com

SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE • 

SERVICE

WARNING

!

Only skilled and well trained service technicians 
permitted to service R-600a equipped products.

All tools and equipment must be approved for 
use with R-600a refrigerant.

Local, state and federal laws, standards must be 
observed along with proper certification and 
licensing.

Ventilation is required during servicing.

No conversions to R-600a from any other 
refrigerants. OEM R-600a equipped unit only.

Service area must be free of ignition sources.

No smoking is allowed in the service area.

All replacement electrical components must be 
OEM and installed properly (sealed and 
covered).

If the evaporator is cold prior to service, it must 
be thawed prior to service.

When using a vacuum pump, start pump before 
opening refrigeration system. 

Vacuum pump and recovery equipment should 
be at least 10 feet from the work area. 

It is recommended that a simple LPG gas 
detector is on site during service.

Ensure that all R-600a is removed from the 
system prior to brazing any part of the sealed 
system.

Only a clean, dry leak free system should be 
charged with R-600a.

R-600A SPECIFICATIONS/LABELING

R-600a equipped products are labeled (both the unit and 
the compressor).

R-600a is colorless and odorless.

R-600a is considered non-toxic, but is flammable when 
mixed with air.

Do not remove or alter any R-600a labeling on the 
product.

Use only a refrigerant grade R-600a from a properly 
labeled container.

RECOVERING/RECLAIMING R-600A

(R-600a has been exempted from recovery/reclaiming 
requirements by the US EPA)

Recovery/Reclaiming equipment must be approved for use 
with R-600a.

Ensure the evaporator is at room temperature prior to 
recovery/reclaiming R-600a.

Use a common piercing pliers or piercing valve to remove 
R-600a from the compressor process tube. (Note: Piercing 
devices must not be left on the system and must be 
replaced with a Schrader type valve.)

50

Summary of Contents for 2260DC

Page 1: ...USER GUIDE SERVICE MANUAL SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE 2000 Series 2260DC 60 cm Drinks Cabinet RIGHT PRODUCT RIGHT PLACE RIGHT TEMPERATURE SINCE 1962 ...

Page 2: ...Plinth Installation Door Swing Door Stop Door Adjust Maintenance Cleaning Cleaning Condenser Extended Non Use Operating Instructions First Use Control Operation Sabbath Mode Airflow and Product Loading U Line Wine Guide Recommended Wine Storage Service Interior Shelves Wine Rack Installation Troubleshooting Wire Diagram Product Liability Warranty Claims Parts Ordering Replacement Parts R600a Speci...

Page 3: ...8 00 am to 4 30 pm CST T 1 414 354 0300 Service Email onlineservice u line com Parts Email onlineparts u line com GENERAL INQUIRIES U Line Corporation 8900 N 55th Street Milwaukee Wisconsin 53223 USA Monday Friday 8 00 am to 4 30 pm CST T 1 414 354 0300 Email sales u line com u line com CONNECT WITH US Designed engineered and assembled in WI USA WELCOME TO U LINE Congratulations on your U Line pur...

Page 4: ...oughout this guide This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience or knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with this appliance DANGER This un...

Page 5: ...ever install or operate the unit behind closed doors Be sure front grille plinth strip base fascia is free of obstruction Obstructing free airflow can cause the unit to malfunction and will void the warranty Failure to clean the condenser every six months can cause the unit to malfunction This could void the warranty Allow unit temperature to stabilize for 24 hours before use Do not block any inte...

Page 6: ...freezer take off the doors and leave shelves in place so children may not easily climb inside If the unit is being removed from service for disposal check and obey all federal state and local regulations regarding the disposal and recycling of refrigeration appliances and follow these steps completely 1 Remove all consumable contents from the unit 2 Unplug the electrical cord from its socket 3 Rem...

Page 7: ... F 10 C and 90 F 32 C Higher ambient temperatures may reduce the unit s ability to reach low temperatures and or reduce ice production on applicable models For best performance keep the unit out of direct sunlight and away from heat generating equipment In climates where high humidity and dew points are present condensation may appear on outside surfaces This is considered normal The condensation ...

Page 8: ...g area dry If the detachable type electric supply cord is damaged it must be replaced by an equivalent cord available from the manufacturer or its service agent NOTICE Electrical installation must observe all state and local codes This unit requires connection to a grounded three prong polarized receptacle that has been placed by a qualified electrician The unit requires a grounded and polarized 2...

Page 9: ...the front grille plinth strip base fascia must NOT be obstructed CAUTION Unit can NOT be installed behind a closed cabinet door U Line products are designed and manufactured to be installed in the specified cutout openings shown and variance to the floors or cabinetry must be accounted for in your installation CUTOUT DIMENSIONS Metric measurements rounded and optimized 4 102 mm 7 178 mm 33 7 8 860...

Page 10: ...ne com SAFETY INSTALLATION INTEGRATION OPERATING INSTRUCTIONS MAINTENANCE SERVICE Product Dimensions 3 5 8 to 4 5 8 92 mm to 118 mm 33 11 16 to 34 11 16 856 mm to 881 mm 23 7 16 590 mm 23 5 8 600 mm Includes 3 4 20 mm integrated panel 10 ...

Page 11: ...ut Dimensions in each unit s Installation Guide Each door can be opened individually one at a time without interference However to ensure unobstructed door swing opening both doors at the same time 1 4 6 4 mm of space needs to be maintained between the units Hinge by Hinge Installation Mullion When installing two units hinge by hinge 13 16 22 mm is required for integrated models Additional space m...

Page 12: ... drill bit drill 3 pilot holes 5 8 16 mm deep into bottom of counter top Use the anti tip bracket as a template 4 Install 3 8x5 8 screws into the plate using a 2 Phillips head screwdriver SIDE MOUNT Side mount position is used when you are unable to mount the bracket to the underside of your countertop 1 Remove the pre installed anti tip bracket from the top mount position and align the bracket to...

Page 13: ... total unit rear height of 1 8 3 mm less than the opening s rear height Shorten the unit height in the front by adjusting the front legs This allows the unit to be gently tipped into the opening Adjust the front legs to level the unit after it is correctly positioned in the opening INSTALLATION 1 Plug in the power electrical cord 2 Gently push the unit into position Be careful not to entangle the ...

Page 14: ...20 lbs 10 kg It is important to ensure that all drilled holes are drilled to the correct depth in order to avoid splits in the wood when hardware is installed 1 Cut the panels to the dimensions listed in the diagram below 2 Optional Stain or finish panel to desired stain or color Be sure to closely follow the instructions provided by the manufacturer 3 Optional Install handles and hardware NOTICE ...

Page 15: ...e door The appliance will need up to 34 1 2 876 mm to the underside of the counter to leave room for leveling adjustments A single prepared frame with insert must not weigh more than 20 lbs 10 kg Integrated Frame Preparation 1 Cut the main panel to the appropriate dimensions below For details see the drawings on the next page 2 Create the top design for the handleless feature and the 1 8 3 mm notc...

Page 16: ...RVICE Handleless Integrated Frame Dimensions 3 4 20 mm 28 13 16 732 mm 2 3 4 70 mm 2 3 4 70 mm R 5 8 R 16 mm 1 8 3 mm 1 4 6 mm Wooden Insert Notch Depth 1 8 3 mm 2 3 8 60 mm 7 8 22 mm Ref Cutout for Frame Units Top Detail Insert Notch Top Design 1 8 3 mm 3 1 2 89 mm 23 1 2 595 mm Wooden Insert Dimensions 23 1 2 595 mm 16 ...

Page 17: ... dimensions listed in the appropriate diagram on the next page 2 Optional Stain or finish panel to desired stain or color Be sure to closely follow the instructions provided by the manufacturer 3 Optional Install handles and hardware NOTICE The door panel must not weigh more than 20 lbs 10 kg It is important to ensure that all drilled holes are drilled to the correct depth in order to avoid splits...

Page 18: ...ted Panel Integrated Panel Integrated Frame Front Side Front Side 3 5 16 89 mm to 4 5 16 114 mm Floor Cabinet 3 5 16 89 mm 3 5 16 89 mm to 1 25 mm U Line Unit Extended Integrated Panel Extended Integrated Frame Floor Cabinet 3 5 16 89 mm to 1 25 mm U Line Unit Integrated Panel Panel can extend beyond the door frame A minimum of 1 25 mm from the floor is required for proper ventilation 18 ...

Page 19: ...integrated frame is 2 3 4 70 mm The top bottom border of the frame must account for any additional length BACK SURFACE MUST HAVE AMPLE FLAT SURFACE TO MOUNT OVERLAY FRAME FLAT AND WITHOUT INTERFERENCE 2 3 4 MIN 70 mm MIN Integrated Frame 3 4 20 mm 23 1 2 595 mm 32 7 8 to 33 7 8 834 mm to 860 mm A minimum of 1 25 mm is required from the floor to the bottom of the extended integrated panel frame for...

Page 20: ...a panel to match your surrounding furniture Finish front back and edges to prevent warping Carefully follow the manufacturer s recommendations for finish application and cure times 3 Apply double sided tape to the backside of the integrated grill plinth strip base fascia Use the diagram below for reference U Line recommends 3M VHB tape a high strength bonding tape 4 Remove backing paper from doubl...

Page 21: ...pe will not damage panel finish upon removal 7 Using a 7 64 3 mm drill bit drill 6 pilot holes into the wood panel 1 2 12 mm deep using the holes in the door frame as a guide NOTICE It is important to ensure that all drilled holes are drilled to the correct depth in order to avoid splits in the wood when hardwood is installed 8 Locate 6 of the 6x 1 1 2 38 mm screws provided with your unit 9 Using ...

Page 22: ...e fascia When using the unit the grille plinth strip base fascia must be installed WARNING DO NOT touch the condenser fins The condenser fins are SHARP and can be easily damaged Removing the grille plinth strip base fascia 1 Disconnect power to the unit 2 Loosen the two screws 1 3 Remove grille plinth strip base fascia 2 from unit Installing the grille 1 Align cabinet and grille holes and secure b...

Page 23: ... installed adjacent to a wall 1 2 13 mm clearance is recommended from wall on hinge side to allow the door to open 90 Allow for additional space for any knobs or pulls installed on the integrated panel frame Units have a zero clearance when installed adjacent to cabinets Wall 90 Door Swing Space Required For any Knobs or Pulls 1 2 13 mm 23 ...

Page 24: ...approximately 90 2 Remove hinge cover by lifting top and bottom of hinge cover and sliding the cover inwards to remove from hinge 3 Once cover is removed slide hinge pin into hole as shown Pin should slide into place stopping the door at 90 if the pin does not go into the hole shown hold the door less than 90 open and try again 4 To fully seat the pin tap it lightly with a hammer 5 Carefully slide...

Page 25: ...e that it is firmly in contact with the cabinet Also make sure the door gasket is not pinched on the hinge side of the door CAUTION Do not attempt to use the door to raise or pivot your unit This would put excessive stress on the hinge system Alignment and Adjustment Procedure 1 Open door and remove gasket near the hinges 2 Using a T 25 Torx Bit loosen each pair of Torx head screws on both the upp...

Page 26: ...ove caps from screw heads on opposite side 2 on top and 2 on bottom Using 2 Phillips bit remove the 4 underlying screws Reinstall the screws and caps on the opposite side 5 Partially install screw 1 in the outer most holes on top and bottom Rotate door 180 align hinge over screw 1 and slide seat into position Reinstall screw 2 on top and bottom Tighten both screws and install hinge cover Align and...

Page 27: ...t the factory Initial startup requires no adjustments NOTICE U Line recommends allowing the unit to run overnight before loading with product When plugged in the unit will begin operating under the factory default settings If the unit was turned off during installation simply press and the unit will immediately switch on To turn the unit off press 27 ...

Page 28: ...ROL FUNCTION GUIDE FUNCTION COMMAND DISPLAY OPTIONS ON OFF Press and release Unit will immediately turn ON or OFF Toggle lights Press and release to leave interior light on for 3 hours Glass door wine and beverage centers only Adjust refrigerator set point Press and release When the F or C in the display is flashing press to adjust the set point temperature View temperature in unit Press together ...

Page 29: ...tain internal temperatures and set points View a full list of Star K certified U Line units at www star k org To enable Sabbath Mode 1 Press 4 and hold for ten seconds and release the F C symbol will flash briefly at the end of the ten second period 2 The interior light and control display 3 will go dark until user resets mode 3 NOTE Although the display will not be visible the temperature control...

Page 30: ...ween the internal fans or vents and product loaded Anything blocking the required airflow circulation will result in uneven temperature distribution in the cabinet and can also freeze product Do not install the unit behind a door When properly loaded your U Line unit will store up to 123 12 oz 330 ml cans or 79 12 oz 330 ml bottles and 10 750 ml bottles of wine For optimal airflow leave approximat...

Page 31: ...e subject of wine is your own palate Do not be afraid to make mistakes Experiment discover but most of all enjoy yourself and your new U Line product Guide To Common Styles Of Wine Matching Food and Wine Although there are no hard fast rules for matching wine to food observe some guidelines Delicate dishes should be accompanied by lighter more delicate wines Full flavored foods should be matched w...

Page 32: ...he presentation of the cork has a rich and fascinating history dating back to the late 1800 s A phylloxera root louse devastation to the vineyards severely limited the supply of great wines Restaurateurs would remove labels on inferior wines and replace them with labels from superior wines This made it necessary for patrons to protect themselves by checking the branding on the cork to ensure that ...

Page 33: ...hat sediment is left undistributed and particles are not suspended vibration in a storage environment is not an issue Wines can become flat or tired when voids and vacuums are created inside the wine bottle In order to create voids and vacuums within a liquid aggressive motion or shaking of the wine bottle would have to occur Terminology Description Acidity A critical element of wine that is respo...

Page 34: ... Each U Line Wine Captain model is designed to impress and inspire anyone with an interest in wine by providing cellar conditions in stylish undercounter units U Line Wine Captain models offer stable storage temperatures a 50 internal relative humidity and protection from UV light rays U Line has the largest product offering available making storing presenting and sharing your wine effortless and ...

Page 35: ...n the bottles so the wine remains in contact with the cork which ensures the cork does not become dry U Line recommends arranging wine bottles as shown in the illustrations below Rack 1 Rack 2 Larger diameter bottles may be stored on the shaded racks illustrated below NOTE After stocking allow unit to stabilize product temperatures for 24 hours Use These Racks For Larger Diameter Bottles Champange...

Page 36: ...lf Height Shelf height may be adjusted to accommodate a broad range of product To alter your shelf spacing follow the instructions below 1 Remove the 4 Shelf clips from the shelf clip holes 2 Move shelf clips as a group to the desired shelf height 3 Insert shelf clips into the holes of the desired shelf height Be certain shelf clip is fully seated into shelf clip hole CAUTION Clips MUST be install...

Page 37: ...cotchbrite will cause the graining in the stainless steel to become blurred Rust not cleaned up promptly can penetrate the surface of the stainless steel and complete removal of the rust may not be possible Integrated Models To clean integrated panels use household cleaner per the cabinet manufacturer s recommendation INTERIOR CLEANING Disconnect power to the unit Clean the interior and all remove...

Page 38: ...e drain pan and possibly damaging water sensitive flooring the unit must be removed from cabinetry To defrost 1 Disconnect power to the unit 2 Remove all products from the interior 3 Prop the door in an open position 2 in 50 mm minimum 4 Allow the frost to melt naturally 5 After the frost melts completely clean the interior and all removed components See INTERIOR CLEANING 6 When the interior is dr...

Page 39: ...en necessary Depending on environmental conditions more or less frequent cleaning may be necessary WARNING Disconnect electric current to the unit before cleaning the condenser NOTICE DO NOT use any type of cleaner on the condenser unit Condenser may be cleaned using a vacuum soft brush or compressed air 1 Remove the grille plinth strip base fascia See GRILLE PLINTH INSTALLATION 2 Clean the conden...

Page 40: ...e cabinet NOTICE Do not remove the track rails from the cabinet To insert wine racks in the cabinet 1 Align the left and right rack channels with the tracks in the cabinet Ensure an even track engagement on both sides by gently pushing the rack into the cabinet until it stops 2 Before reloading the rack ensure proper movement of the travel stops in the left and right track rails by pulling the rac...

Page 41: ...it is returned to service 3 If ice is on the evaporator allow ice to thaw naturally 4 Clean and dry the interior of the unit Ensure all water has been removed from the unit 5 The door must remain open to prevent formation of mold and mildew Open door a minimum of 2 50 mm to provide the necessary ventilation WINTERIZATION If the unit will be exposed to temperatures of 40 F 5 C or less the steps abo...

Page 42: ... listed Compressor The compressor makes a hum or pulsing sound that may be heard when it operates Evaporator Refrigerant flowing through an evaporator may sound like boiling liquid Condenser Fan Air moving through a condenser may be heard Automatic Defrost Drain Pan Water may be heard dripping or running into the drain pan when the unit is in the defrost cycle TROUBLESHOOTING GUIDE DANGER ELECTROC...

Page 43: ... openings and the time the door is open The time the internal light is illuminated This mainly affects product on the top rack or shelf Digital Display Shows 1 16 or 99 A factory test mode may be enabled Adjust the temperature to 99 and press the LIGHT icon Product Is Freezing Because product in contact with the rear wall may freeze ensure no product is touching the rear wall Adjust the temperatur...

Page 44: ...LUG 220 240 VOLT PLUG OVERLOAD NEUTRAL WHITE 115v DARK BLUE 220 240v TO COMPRESSOR NEUTRAL WHITE 115v DARK BLUE 220 240v BLUE 115V LIGHT BLUE 220V 240V TO COMPRESSOR 1 10 CONTROL BOARD ZONE TEMP FUSE 16 8 9 1 6 1 10 5 EVAP TEMP L T DOOR SWITCH AMBIENT TEMP R B LIGHT L T LIGHT COND FAN EVAP TEMP R B DOOR SWITCH CAP P R O G R A M I N G T O D I S P L A Y OPEN A N T E N N A J9 J10 HOT LIGHT BLUE OVERL...

Page 45: ...ent of a part the servicer is authorized to replace the part in question The part that caused the damage must be returned to U Line in its entirety The part must be clearly labeled with the serial number of the unit it was removed from the date and the servicer who removed the part If the service technician determines the damage is the result of installation issues water connection drain etc the c...

Page 46: ...ashes 12 represents the production month In most cases warranty status can be verified by the production date information within the serial number Alternatively a Proof of Purchase or equivalent may submitted with the warranty claim to document warranty status We also accept the following information to verify warranty status New Construction Occupancy Documents Closing Paperwork Final Billing Rem...

Page 47: ...ator cover 80 54042 00 15 Glass shelf 1 w brackets 80 54041 00 16 Grille w screws 80 54040 00 17 Hinge covers 2 pcs 80 54001 00 18 Hinge mounting hole covers 80 54024 00 19 Hinges 2 w screws and covers 80 54013 00 20 LED light strip and cover assy 80 54000 00 21 Leg Levelers 4 80 54019 00 22 Main board no wires or case 80 54008 00 23 Packaging 80 54027 00 24 Rack assembly bottom 80 54091 00 25 Rac...

Page 48: ...ts will be shipped at no charge after U Line confirms warranty status Please provide the model serial number part number and part description Some parts will require color or voltage information If U Line requires the return of original parts we will inform you when the parts order is taken This requirement will be noted on your packing list A prepaid shipping label will be included with the repla...

Page 49: ... federal state and local laws regarding refrigerants Gloves and Eye Protection must be used R 600a is considered non toxic but is flammable when mixed with air Keep a dry powder type fire extinguisher in the work area R 600a is heavier than air do not allow any leakage migration to low areas such as basements and stairs Never use a torch on a fully charged refrigeration system Never substitute U L...

Page 50: ...y equipment should be at least 10 feet from the work area It is recommended that a simple LPG gas detector is on site during service Ensure that all R 600a is removed from the system prior to brazing any part of the sealed system Only a clean dry leak free system should be charged with R 600a R 600A SPECIFICATIONS LABELING R 600a equipped products are labeled both the unit and the compressor R 600...

Page 51: ...the system prior to repair simple venting is not sufficient Evacuate and charge with dry nitrogen for leak checks Repair leaks or replace system parts as required When re brazing the system must be purged with dry nitrogen and at least one access point open to the atmosphere When re brazing proper ventilation is required along with constant monitoring for the presence of R600a refrigerant The filt...

Page 52: ...pe access port on the compressor process stub Evacuate the system to 100 microns prior to charging Weigh in the R 600a charge using a refrigerant scale run compressor an extra two minutes to clear the charging hoses Seal the Schrader Type access port a proper cap and seal must be used to close the system SUMMARY Safely handling R 600a requires proper procedures and training R 600a approved service...

Page 53: ...e Lower than normal Warm near room temperature Hot Warm Warm Extremely cold near inlet Outlet below room temperature Lower than normal Partial Restriction Somewhat lower than normal vacuum Warm near room temperature Very hot Top passes warm Lower passes cool near room temperature due to liquid Room temperature cool or colder Extremely cold near inlet Outlet below room temperature backing up Lower ...

Page 54: ...grounded to an electrical ground or grounded water pipe Handle circuit boards carefully and avoid touching components To measure the start winding resistance measure across the C and S pins To measure the run winding resistance measure across the C and R pins Also check S to R and you should get the sum of the run and start windings To ensure the windings are not shorted check the S and R to groun...

Page 55: ...outputs located on the relay power board Included in this section are some diagnostic tips and of course if additional help is required please contact the U Line Corp Customer Care Facility at 1 800 779 2547 for assistance NORMAL OPERATING SOUNDS All models incorporate rigid foam insulated cabinets to provide high thermal efficiency and maximum sound reduction for its internal working components D...

Page 56: ...Refer to 14 Error Log in Service Mode Thermistor failure Check Error Log in Service Mode OHM thermistor Frost Buildup Inside Unit Door Ajar or Restricted from Closing Check door clearance to adjoining cabinetry Check distribution of product in unit Evaporator fan not operating Use Relay Toggle Component Testing in Service Mode Thermistor failure Check Error Log Display Not Working Unit placed in S...

Page 57: ... into overload The compressor will automatically deactivate during an overload and will remain deactivated until the overload switch cools This could take some time It is important to allow the compressor at least 5 minutes off time between relay cycles 2 Toggle the relay Its related component should activate deactivate with the switching of the relay If it does not test component Other Suspected ...

Page 58: ...ed magnetic force pulls the reed to its contact and closes the circuit which turns the light and display off When the door is open the reed pulls away from the contact and opens the circuit If the door is left open for longer than 5 minutes the switch will trigger an error code and set an audible warning Magnet Close To Switch Door Closed Switch Closed Magnet Away From Switch Door Open Switch Open...

Page 59: ...igates through service menu LED activated with button activation 3 Down Button Decreases temperature Navigates through service menu LED activated with button activation 4 Light Button Activates light for 3 hours on select models Used to select items in service menu LED activated with button activation 5 Power Button Turns unit off on LED activated with button activation only turning unit off 6 Cle...

Page 60: ...nter exit this mode hold the light key and the power key for 5 seconds The display will flash once and beep and the degree symbol will begin to flash When the degree symbol is flashing the unit will allow the use of the control for demonstrations The unit can be left in this mode indefinitely SERVICE MODE This mode has options available for service diagnostics To enter the mode hold the hidden key...

Page 61: ...in the refrigerator section 13 ADJUST DEFROST DURATION 0 TO 99 MINUTES The length of the defrost can be adjusted 0 to 99 minutes long The other defrost parameters still apply Lengthening a defrost may cause higher than normal temperatures in the refrigerator section Service Mode Menu Item 1 View thermistor 1 no offsets 2 View thermistor 2 no offsets 3 View thermistor 3 no offsets 4 View thermistor...

Page 62: ...an will continue to run at the end of a cooling cycle Adjustable 0 99 minutes 19 INDIVIDUAL COMPONENT TOGGLE 20 MODEL NUMBER INDICATOR Displays the two digit model number of the specific unit See model list table 21 LIGHT ALL LED SEGMENTS This will illuminate all the LEDs on the display to ensure they work properly 22 VIEW DEFROST CYCLES Displays the number of defrosts that have occurred in the pa...

Page 63: ...econds use the up and down arrow buttons to select the appropriate model number See Above Model List 5 Press the light bulb button once 6 The display will blink and then will appear as the programmed display 1000 MODEL INDICATOR 2000 120V MODEL INDICATOR 2000 230V MODEL INDICATOR 1215R 07 2218R 05 2245R 55 1215WC 12 2218RGL 04 2245DC 54 1224BEV 13 2218WC 06 2245WC 56 1224DWR 08 2224BEV 00 2260DC 5...

Page 64: ...ht Evaporator Fan Condenser Fan N A N A 2218WC N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N A 2224BEV N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N A 2224R N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N A 2224RGL N A N A N A N A N A Compressor Light Evaporator Fan Condenser Fan N A N A 2224WC N A N A N A N A N A Compress...

Page 65: ...he Control Operations Service section This unit has three thermistors Thermistor one Zone Located along the right hand side wall It is used to maintain the operating temperature within that zone Thermistor two Evaporator Located on the evaporator It is used for defrost Thermistor three Ambient Located in the base of the unit secured to the condenser It is used to monitor the ambient temperature wi...

Page 66: ...ata Temp F Temp C Nominal Resistance OHMS 40 40 169157 31 35 121795 22 30 88766 13 25 65333 4 20 48614 5 15 36503 14 10 27681 23 5 21166 32 0 16330 41 5 12696 50 10 9951 59 15 7855 68 20 6246 77 25 5000 86 30 4029 95 35 3266 104 40 2665 113 45 2186 122 50 1803 131 55 1495 140 60 1247 149 65 1044 158 70 879 167 75 743 176 80 631 5 66 ...

Page 67: ...F C 1224 RF 12 45 15 9 1215 1224 2218 2245 2224 2260 WC ZWC 12 45 45 7 1215 1224 2218 2245 2224 2260 R RSOD RDC BEV DC DWR RGL 12 45 42 6 CO29 F 12 18 n a CO1224 F 12 18 45 7 1224FZR Freezer Mode 6 45 42 6 1224FZR Refrigerator Mode 12 45 42 6 Defrost Settings by Zone 3000 Series Zones Compressor Run Time Between Defrost Hours Duration in Minutes Minimum Duration in Minutes Maximum Stop Temperature...

Page 68: ...condensation that may have appeared on glass doors and shelves Note If the unit is set to sabbath mode the evaporator fan will no longer respond to the state of the door switch In order to operate efficiently the evaporator fan blade and vents should be unobstructed and free of any dust buildup Evaporator Fan Replacement Should the evaporator fan need to be replaced follow the steps below 1 Remove...

Page 69: ...rator cover vents and push air out at fan mounting location 15 Installation is the reverse of removal 16 Care must be taken to assure the bottom of the evaporator cover is reinstalled behind the front edge of the train trough 17 Use sealant gum to seal any openings at rear of unit before replacing rear cover 18 Reinstall unit taking care to level space and secure as found 69 ...

Page 70: ...anty arising by operation of law U Line will not be responsible for any consequential or incidental damages arising from the breach of these warranties or any other warranty whether express implied or statutory Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you These warranties give you specific lega...

Reviews: