background image

PAGE 1 OF 6 

0621 TH-6621

1-800-295-5510

uline.com

H-6621

INDUSTRIAL DEHUMIDIFIER

OPERATING ISSUE

CAUSES

RECOMMENDATIONS

The unit is not working.

The breaker tripped.

The unit is plugged into a GFI protected 

circuit. 

The unit is being run from a generator.

The extension cord is not the correct 

gauge for the distance run.  

(14 AWG up to 25' and 12 AWG over 25') 

Reset breaker.

Remove from area. Excessive moisture will trip GFI.

Check output does not fluctuate, as the unit will 

not operate at low voltage.

Verify voltage while unit is starting. Start up will 

cause the highest current draw and largest 

voltage drop. Even if plugged directly to outlet, 

there can be a significant voltage drop. Never 

assume the voltage is okay without verifying.

The unit shuts down and displays 

an error code.

ER 1: Overflow switch remaining closed 

for over two minutes.

Plugged or kinked drain hose.

Bad connection in pump circuit.

Defective condensate pump.

ER 2: Internal pressure switch indicates 

refrigerant pressure is too high.

Air filter is dirty or plugged.

The coil is dirty.

Loose or faulty electrical connections 

to pressure switch.

Fan is not working.

Defective pressure switch.

Remove obstruction.

Check connections.

Replace pump.

Clean or replace air filter.

Clean coil.

Check connections.

Replace fan.

Replace pressure switch.

TROUBLESHOOTING

Para Español, vea páginas 3-4.

Pour le français, consulter les pages 5-6.

Summary of Contents for Н-6621

Page 1: ...t voltage drop Even if plugged directly to outlet there can be a significant voltage drop Never assume the voltage is okay without verifying The unit shuts down and displays an error code ER 1 Overflow switch remaining closed for over two minutes Plugged or kinked drain hose Bad connection in pump circuit Defective condensate pump ER 2 Internal pressure switch indicates refrigerant pressure is too...

Page 2: ...learance all around it Clean coil Unit moves some water but not as much as expected Air filter is dirty or airflow obstructed Evaporator coil dirty Restrictive or kinked exhaust ducting if used Unit should have a minimum of 10 clearance all around it Clean air filter and ensure adequate airflow space around unit Clean coil Straighten out ducting Fan does not run Compressor runs briefly but cycles ...

Page 3: ...el consumo de corriente más alto y la caída mas baja de voltaje Aun si estuviera conectado directamente a un enchufe puede existir una baja significante de voltaje Nunca asuma que el voltaje está bien sin verificarlo La unidad se apaga y aparece un código de error en la pantalla ER 1 El interruptor de rebose permanente cerrado por más de dos minutos Manguera de drenaje tapada o torcida Conexión ma...

Page 4: ...ella Limpie la bobina La unidad saca un poco de agua pero no la cantidad esperada El filtro de aire está sucio o el flujo de aire obstruido La bobina del evaporador está sucia Los ductos están restringidos o torcidos si se utilizan La unidad debería de tener un mínimo de 10 de espacio libre alrededor de ella Limpie el filtro de aire y asegúrese que haya suficiente flujo de aire espacio libre alred...

Page 5: ...ie par une grande chute de tension se produit lors du démarrage Même si l appareil est branché directement à la prise il peut y avoir une chute de tension importante Ne présumez jamais que la tension est correcte sans avoir vérifié L appareil s éteint et affiche un code d erreur ER 1 Le commutateur de débordement reste fermé pendant plus de deux minutes Le tuyau de vidange est bloqué ou plié La co...

Page 6: ...in L appareil vide l eau mais pas autant que prévu Le filtre à air est sale ou la circulation d air est obstruée Le serpentin d évaporateur est sale Les conduits de canalisation sont étroits si utilisés L appareil doit avoir un minimum de 10 po d espace libre autour Nettoyez le filtre à air et assurez vous qu il y a suffisamment d espace autour de l appareil Nettoyez les serpentin Redressez les co...

Reviews: