USER GUIDE
Control Operation - Service 4
SAFETY • INSTALLATION & INTEGRATION • OPERATING INSTRUCTIONS • MAINTENANCE •
SERVICE
To access Relay Toggle
1. Use Down
to select “Relay Toggle”.
2. Press Select .
3. Use Up
and Down to scroll through each relay or
DC output.
4. Press Select
to toggle.
To exit the Relay Toggle menu use Up to select “Return
to Menu” and press Select to confirm.
Input Status
Input status displays the current state of each available
input as well as the current USB connection state.
Note:
USB status shows current connection state. In order
to make a successful connection USB connection type
must be properly set in “USB Port” under the service
menu.
To access Input Status
1. Use Down to select “Input Status”.
2. Press Select .
3. Use Up and Down to scroll through available
information.
To exit the Input Status menu use Up to select “Return
to Menu” and press Select to confirm.
Outputs
Outputs is used to monitor the state of DC outputs.
To access Outputs
1. Use Down to select “Outputs”.
2. Press Select
3. Use Up
and Down to scroll through available
information.
To exit the Outputs Status menu use Up to select
“Return to Menu” and press Select to confirm.
F3
Condenser Fan (Not Used)
AC
L1
Cabinet Lighting
DC
L2
Cabinet Lighting (Not Used)
DC
WV
Water Valve
AC
Pump
Circulation Pump
AC
Harvest
Harvest
AC
ID
Description
States
Door
Door Switch
Open - Closed
IN2
Input 2 - Not Used
Open
Test Input
Factory Test Input
Open
USB
USB Connection State
Flash - Com Port
Up
Select
Down
RETURN TO MENU
INPUT STATUS
DOOR OPEN
IN2 OPEN
ID
Description
States
Evap Fan
Evaporator Fan
0 - 100%
Condenser Fan
Condenser Fan
0 - 100%
Light
Interior Lighting
Off - Low - Med - High
Up
Select
Down
RETURN TO MENU
OUTPUTS
EVAP FAN=0%
CONDENSER FAN=0%
56