General Information
Field Descriptions:
Note:
Relay 2 will cycle with relay 7, this is considered normal.
Field
Value
Field
Value
1
Time in seconds since unit plugged in.
22
Relay 3 (unassigned). “3” = active, “---” = inactive.
2
Temperature of Left Zone in °F/°C.
23
Left Valve Relay “4” = active, “---” = inactive.
3
Temperature of Right Zone in °F/°C.
24
Right Valve Relay 5. “5” = active, “---” = inactive.
4
Left evaporator temperature in °F/°C.
25
Relay 6 (unassigned). “6” = active, “---” = inactive.
5
Right evaporator temperature in °F/°C.
26
Compressor relay. “7” = active, “---” = inactive.
6
Ambient temperature in base of unit °F/°C.
27
Left evaporator fan. “1” = active, “---” = inactive.
7
Board processor temperature.
28
Right evaporator fan. “2” = active, “---” = inactive.
8
Left Zone identification tag.
29
Condensor fan. “3” = active, “---” = inactive.
9
Left Zone set point in °F/°C.
30
Left LED intensity, provided in %.
10
Left Zone Differential value in °F/°C.
31
Right LED intensity, provided in %.
11
Left Zone offset value in °F/°C.
32
Energy Saver mode indicator. “E” = active.
12
Left evaporator offset value in °F/C.
33
Sabbath mode indicator. “S” = active.
13
Right Zone identification tag.
34
Soft power indicator. “P” = unit in “On” mode.
14
Right Zone set point in °F/°C.
35
Compressor state change timer, in seconds.
15
Right Zone Differential value in °F/°C.
36
Compressor cumulative run time, in seconds.
16
Right Zone offset value in °F/°C.
37
Max remaining defrost time, in seconds.
17
Right evaporator offset value in °F/C.
38
Left Evaporator fan state change timer, in seconds.
18
Left door indicator. “L” = Open, “---” = closed.
39
Right Evaporator fan state change timer, in sec.
19
Right door indicator. “R” = Open, “---” = closed.
40
L Cumulative time spent in limp mode, in seconds.
20
Relay 1 (unassigned). “1” = “active”, “---” = inactive.
41
R Cumulative time spent in limp mode, in seconds.
21
Relay 2 (unassigned). “2” = “active”, “---” = inactive.