background image

 

u::Lux NetCon / u::Lux NetCon Power - Manual

 

 

 

Version: 1.07 

01.10.2014 

Page: 5/10 

 

Mounting order 

1.

 

u::Lux NetCon

 or 

u::Lux NetCon Power

 must snap into place on the top-hat rail. 

2.

 

Connect the network cable (not included in the scope of delivery) for the 

u::Lux Switch RJ45

 

to LAN1 or/and LAN2. 

 

We recommend the use of a Patchpanel (taking  into account the potential equalization) so 
that a shielded network cable can be lead to ground or to get a better ground-contact from the 
installation  cable  to  the  Patch  cable.  When  indicated,  already  existing  local  connecting 
instructions must absolutely be obeyed.  

3.

 

For  the  control  or  cascading  connect  the  network  cable  (not  included  in  the  scope  of 
delivery) to LAN3 or/and LAN4. 

 

4.

 

Connect the energy supply.  
A plug connector (Phoenix - MSTBA 2,5/ 2-ST-5,08) is included in the scope of delivery.  
Connect  the  negative  supply  voltage  of  the  energy  supply  to  Pin  –  VCC  and  the  positive 
supply voltage to +VCC (see Chapter General Information). 

 

 

Startup 

After connecting the power supply all green LEDs have to illuminate. With these LEDs the presence 
of the following voltages is indicated: 

 

1.

 

Energy supply with supply voltage 

VCC

2.

 

Internal voltage generation 

3,3 volts. 

3.

 

Internal voltage generation 

48 volts

 (on ports LAN1 and LAN2).

 

 
If  a  network  cable  is  connected  to  each  of  LAN1  –  LAN4  and  a  physical  connection  (LINK)  is 
established, the corresponding yellow LED illuminates permanently. As soon as there is traffic  on 
the connection (ACTIVITY) it will be signalized by this flashing LED. Regarding the LAN ports we 
recommend the connection of the following network subscribers:  

 

LAN1:  is used exclusively to connect up to 10 

u::Lux Switches RJ45

.  

LAN2:  is used exclusively to connect up to 10 

u::Lux Switches RJ45

.  

LAN3:  is used to connect a PLC control or to connect another 

u::Lux NetCon Power

 module 

(cascading) or a computer.  

LAN4:  is used to connect a PLC control or to connect another 

u::Lux NetCon Power

 module 

(cascading) or a computer. 

 

Startup order 

1.

 

Control of the green LED. All 4 LEDs have to illuminate.  

Summary of Contents for NetCon

Page 1: ...u Lux NetCon u Lux NetCon Power Manual www u lux com office u lux com Tel 43 662 450 351 13 Fax 43 662 450 351 16 u Lux GmbH Rechtes Salzachufer 42 5020 Salzburg Austria ...

Page 2: ...07 01 10 2014 Page 2 10 Contents General Information 3 Mounting 3 Mounting order 5 Startup 5 Startup order 5 Practical example 6 Network wiring 7 Technical Data 8 Hazard warnings 9 CE marking 9 Guarantee 9 Ordering Information 9 Version Management 10 ...

Page 3: ... NetCon and u Lux NetCon Power except in case of an explicit distinction between the models The energy supply of the u Lux NetCon is carried out via direct voltage through the connections VCC and VCC The voltage has to be sufficiently filtered max voltage ripples 2VSS and it must be within the following range u Lux NetCon 48V DC u Lux NetCon Power 22V 30V DC Mounting The mechanical assembly of the...

Page 4: ...ote that these vents are not covered and a sufficient distance to adjacent components is kept The housing height is approx 80mm Please note that for the Ethernet connections on the front there will be added approx 50mm additionally to the housing depth Altogether a free installation depth of approx 130mm is necessary Please take this into consideration when selecting an appropriate junction box wa...

Page 5: ...upply voltage to VCC see Chapter General Information Startup After connecting the power supply all green LEDs have to illuminate With these LEDs the presence of the following voltages is indicated 1 Energy supply with supply voltage VCC 2 Internal voltage generation 3 3 volts 3 Internal voltage generation 48 volts on ports LAN1 and LAN2 If a network cable is connected to each of LAN1 LAN4 and a ph...

Page 6: ...l A maximum of 2x10 u Lux Switches RJ45 per u Lux NetCon Power can be supplied with energy Therefore 2 units of u Lux NetCon Power are required for the energy supply of all 40 u Lux Switches RJ45 The u Lux Switches RJ45 are connected to the ports LAN1 and LAN2 of the u Lux NetCon Power Both ports of LAN3 are connected to each other cascading One of the two LAN4 ports forms the connection to the co...

Page 7: ...anual Version 1 07 01 10 2014 Page 7 10 Network wiring An u Lux Switch line may not exceed the total length of 200 m because of the cable resistance voltage drop We recommend not exceeding the max length of 50 m of a single sub segment ...

Page 8: ... the bottom of the housing Displays At the network connections per port there is a yellow LED for LINK or ACTIVITY and respectively a green LED for displaying the voltages VCC 3V3 und 2x 48V Network 100BaseT Ambient temperature 10 C to 40 C Storage temperature 30 C to 80 C Protection type IP30 Protection class III Assembly type Vertical on horizontal top hat rail 35mm Installation dimensions 95mm ...

Page 9: ... device fire or other dangers u Lux NetCon or u Lux NetCon Power are devices which do not correspond to the PoE standard CE marking The CE marking is exclusively addressed to the governmental supervising authorities of the Member States and facilitates the free movement of goods The CE marking does not represent any guarantee of specific features Guarantee The guarantee complies with the statutory...

Page 10: ...eation of the document 1 01 17 12 2012 THSI Correction Release 1 02 18 12 2012 AK Correction Release 1 03 14 01 2013 KH Addition Network connections via patchpanel 1 04 21 01 2013 KH Addition Connections 1 05 14 01 2014 THSI Addition of new order numbers 1 06 07 07 2014 KH u Lux switch u Lux switch RJ45 1 07 01 10 2014 AK Contact updated ...

Reviews: