103448-10 - 6/18
57
Table 13: Recommended Circulators for 50 ft. Equivalent ft. Near Boiler Piping [Approximately 20 ft.
Straight Pipe, (4) 90° Elbows, and (2) Full Port Ball Valves]
Boiler
Model
Boiler Supply
Connection,
Inch, FPT
Boiler
Return
Connection,
Inch, FPT
Near-Boiler
Piping
Supply Pipe
Size, Inch
Near-Boiler
Piping
Return Pipe
Size, Inch
Flow, GPM
@ 25°F
Temp.
Differential
Combined
Boiler &
Piping Loop
Head Loss, Ft.
Recommended
Circulator
Make & Model
ALP080B
1
1
1
1
7.3
(1)
14.7
Taco 0015 (Speed 3)
Grundfos UPS
15-58 (Speed 2)
ALP105B
1
1
1
1
7.7
14.3
Taco 0015 (Speed 3)
Grundfos UPS
26-99 (Speed 1)
ALP150B
1
1
1
1
11.0
11.7
Taco 0015 (Speed 3)
Grundfos UP
26-99 (Speed 2)
ALP210B
1
1
1¼
1¼
15.5
11.7
Taco 0014
Grundfos UP
26-99 (Speed 2)
ALP285B
1¼
1¼
1½
1½
21.5
12.3
Taco 0011
Grundfos UP
26-99 (Speed 3)
Notes:
(1)
Temperature Differential = 20°F
All Circulators shown are not equipped with internal flow check valve (IFC).
When selecting Circulators other than recommended, contact Circulator Manufacturer for sizing information.
Near-Boiler Piping Size shown is based on 2 to 5.5 Ft/Sec. velocity range to avoid potential noise and pipe erosion.
VI. Water Piping and Trim
(continued)
C. Standard Installation Requirements
Observe the following guidelines when making
the actual installation of the boiler piping:
1. Safety Relief Valve (Required)
- The relief
valve is packaged loose with boiler and
must be installed in the location shown in
Figure 20 “Factory Supplied Piping and Trim
Installation”. The relief valve must be installed
with spindle in vertical position. Installation
of the relief valve must comply with ASME
Boiler and Pressure Vessel Code, Section IV.
The standard factory shipped relief valve is
rated for 30 PSI maximum working pressure
for ALP080B through ALP285B. Optional 50
PSI, 80 PSI and 100 PSI maximum working
pressure rated relief valves are available. If
the valve is to be replaced, the replacement
valve must have a relief capacity equal or
exceeding the boiler DOE Heating Capacity
(models ALP080B through ALP285B). Pipe
the relief valve discharge to a location where
hot water or steam will not create hazard or
property damage if the valve opens. The end
of the discharge pipe must terminate in an
unthreaded pipe. If the relief valve is not piped
to a drain, it must terminate at least 6” above
the floor. Do not run relief valve discharge
piping through an area prone to freezing. The
termination of discharge piping must be in
an
area where it will not become plugged by
debris.
2 Circulator (Required)
–
Usually at least two
circulators will be required to properly install a
Alpine™ Series boiler. See Paragraph B above
for information on sizing the circulators.
3. Expansion Tank (Required)
–
If this boiler
is replacing an existing boiler with no other
changes in the system, the old expansion tank
can generally be reused. If the expansion tank
must be replaced, consult the expansion tank
manufacturer’s literature for proper sizing.
4. Fill Valve (Required)
–
Either manual
(recommended) or automatic fill valve may be
used. However, if automatic refill is employed,
a water meter must be added to evaluate the
makeup water volume taken after initial fill
and eliminate any water leakage as early as
possible.
5. Automatic Air Vent (Required)
–At least one
automatic air vent is required. Manual vents
will usually be required in other parts of the
system to remove air during initial fill.
Burn Hazard. Safety relief
valve discharge piping must be piped such
that the potential of severe burns is eliminated.
DO NOT pipe in any area where freezing could
occur. DO NOT install any shut-off valves,
plugs or caps. Consult local codes for proper
discharge piping arrangement.
CAUTION
Summary of Contents for Alpine ALP080B
Page 76: ...76 103448 10 6 18 VIII Electrical continued...
Page 77: ...103448 10 6 18 77 VIII Electrical continued Figure 27 Wiring Connection Diagram...
Page 78: ...78 103448 10 6 18 Figure 28 Ladder Diagram VIII Electrical continued...
Page 146: ...146 103448 10 6 18...
Page 147: ...103448 10 6 18 147...