13
Figure 8C: U.S. Boiler Company Gasket-Less
Female and Gasketed Male Vent Joint Detail
2. Procedure for joining the female end of U.S. Boiler
Company Gasket-Less Vent with the male end of
U.S. Boiler Company Gasketed Vent. See Figure
8C.
a. Clean joints of pipe or fittings using an alcohol
pad to remove any dirt and grease.
b. Slip a locking band over female (bell) end of
pipe/fitting.
c. Apply a continuous ¼ inch bead of sealant
around male end of joint no more than 1/8 inch
from end.
d. Align weld seams in pipes and use a slight
twisting motion to FULLY insert male end into
female end of joint.
e. Smooth sealant around joint for a continuous
seal. Reapply sealant if necessary.
f. Slip the locking band over joint and align closest
bead in locking band with bead in male end of
pipe.
g. Tighten locking band by HAND with a 5/16" nut
driver until snug plus ¼ turn. DO NOT
SECURE JOINTS WITH SHEET METAL
SCREWS OR POP RIVETS. DO NOT
PUNCTURE THE VENT SYSTEM!
h. Once the installation is complete, operate boiler
and inspect all joints to ensure that flue gases
and/or liquid condensate will not escape.
G.
Horizontal (Through Wall) Vent Installation.
1. Recommended Installation: Maintain minimum ¼
inch per foot slope in horizontal runs. Slope toward
vent terminal. Position weld seams in vent pipes in
all horizontal runs at the top to avoid condensate
from lying on the seams. See Figure 9.
2. Alternate Installation: Maintain minimum ¼ inch
per foot slope in horizontal runs. Slope toward
boiler. Install a horizontal condensate drain tee after
first elbow. Position seams in vent pipes in
horizontal runs at top to avoid condensate from
lying on the seams.
Figure 9: Horizontal Vent Installation
V. Venting (continued)
CAUTION
Moisture and ice may form on surfaces around
vent terminal. To prevent deterioration, surfaces
should be in good repair (sealed, painted etc.)
3. Vent terminal location restricted per following:
a. Minimum 12 inches above grade or normally
expected snow accumulation level, or 7 feet
above grade if located adjacent to public
walkway. Do not install over public walkway
where local experience indicates condensate or
vapor from Category III appliances creates a
nuisance or hazard .
b. Minimum 3 feet above any forced air inlet
located within 10 feet.
c. Minimum 4 feet below, 4 feet horizontally from,
or 1 foot above any door, window, or gravity air
inlet.
d. Minimum 4 feet horizontally from electric
meters, gas meters, regulators, and relief valves.
e. Minimum 12 inches from overhang or corner.
4. Use single wall thimble when passing through
combustible outside wall (thimble use optional for
noncombustible wall). Insert thimble through wall
from outside. Secure outside flange to wall with
nails or screws, and seal with adhesive material.
Install inside flange to inside wall, secure with nails
or screws, and seal with adhesive material.
5. For noncombustible wall when thimble is not used,
size opening such that female (bell) end with
locking band attached cannot pass through.
6. Join vent terminal to vent pipe. Locate vent pipe
such that bell/locking band is flush with outside wall
(or outside flange of thimble, if used) when joined to
inside vent piping. See Figure 10.
7. Insert vent pipe through thimble/opening from
outside and join to vent system. Apply sealant
between vent pipe and opening/thimble to provide
weathertight seal.
Summary of Contents for INDEPENDENCE IN3PV
Page 7: ...7 Figure 4 Steam Piping IN3PV Figure 3 Trim Installation III Steam Piping and Trim continued...
Page 29: ...29 SERVICE RECORD DATE SERVICE PERFORMED...
Page 42: ...42 SERVICE RECORD DATE SERVICE PERFORMED...
Page 43: ...43 SERVICE RECORD DATE SERVICE PERFORMED...
Page 44: ...44 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...