107
107672-01- 7/17
XII. Operation
(continued)
8. DHW Two boiler Start
When the Indirect Water Heater (IWH) parameter is
set to “Primary Piped” and the DHW Two Boiler Start
parameter is set to “Enabled” two boilers are started
without delay in response to a DHW call for heat.
This feature allows rapid recovery of large IWH’s and
multiple IWH’s.
9. Optimized Boiler Modulation
Boiler firing rate is managed to increase smoothly
as boilers are started. For example, when a second
boiler is started the initial firing rate is 100%/2 or 50%,
when the third boiler is started the firing rate starts at
200%/3 or 66%. After the initial start, the Sequence
Master develops a unison firing rate demand based on
it’s setpoint and sensed header temperature.
10. Innovative Condensing Boiler Control
During low loads, the Sequence Master limits firing rates
to a “Base Load Common Rate” to ensure modulating
condensing boiler peak operating efficiency. Lower
firing rates boost efficiency by helping increase the
amount of flue gas water vapor condensation. The
Control maintains a “Base Load Common Rate” until
the last lag boiler is started. At this point, the “Base
Load Common Rate” is released to allow boilers to
modulated as required to meet heat load.
11. Advanced Boiler Sequencing
After there is a Call For Heat input, both header water
temperature and boiler firing rate percent are used to start
and stop the networked boilers. The control starts and
stops boilers when the water temperature is outside the
user selected “Diff Above” and “Diff Below” settings.
Also, in order to minimize temperature deviations, the
control adjusts the number of boilers running based
on the firing rate. This combination allows the boilers
to anticipate slow load changes before they disrupt
water temperature yet still respond quickly to sudden
load changes. These special sequencer features help
reduce energy wasting system temperature swings and
the resulting unnecessary boiler cycling.
12. Stop All Boilers
All boilers are stopped without delay if the Call for
Heat input is removed or if the header temperature is
higher than 195°F (90.6°C) (field adjustable).
Summary of Contents for K2WT-080B
Page 83: ...83 107672 01 7 17 PAGE LEFT INTENTIONALLY BLANK...
Page 89: ...89 107672 01 7 17 X Wiring continued Figure 10 5 Internal Ladder Diagram...
Page 90: ...90 107672 01 7 17 X Wiring continued...
Page 91: ...91 107672 01 7 17 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued...
Page 102: ...102 107672 01 7 17 Lighting and Operating Instructions XI Start Up and Checkout continued...
Page 147: ...147 107672 01 7 17 XV Service Parts continued...
Page 151: ...151 107672 01 7 17 XV Service Parts continued...
Page 153: ...153 107672 01 7 17 XV Service Parts continued 85 86 91 95...
Page 162: ...162 107672 01 7 17...
Page 163: ...163 107672 01 7 17...
Page 164: ...164 107672 01 7 17...
Page 165: ...165 107672 01 7 17...
Page 166: ...166 107672 01 7 17...
Page 167: ...167 107672 01 7 17...