69
107672-01- 7/17
Model
Max. (Natural & LP)
Min. (Natural)
Min. (LP)
080-120
14.0”
2.5”
11.0”
Table 8.2: Minimum and Maximum Inlet Pressures
VIII. Gas Piping
(continued)
CaUTiOn
Support the weight of the gas line piping independently from the boiler gas connection fitting located on the
bottom of the boiler.
If an additional regulator is used to reduce boiler inlet pressure below 1/2 psig (3.4 kPa) it must be at least 6
to 10 ft. upstream of the boiler.
It is very important that the gas line is properly purged by the gas supplier or utility company.
Figure 8.1: Gas Connection to Boiler
*MANUAL SHUT-OFF VALVE
(FACTORY SUPPLIED - MUST
BE INSTALLED WITHIN 6FT
OF THE BOILER)
GROUND
JOINT
UNION
TEE
GAS
SUPPLY
CAP