background image

61

A.

 

COMBUSTION

1. NOZZLES — Although the nozzle is a relatively 

inexpensive device, its function is critical to the successful 

operation of the oil burner. The selection of the nozzle 

supplied with the MPO-IQ boiler is the result of extensive 

testing  to  obtain  the  best  flame  shape  and  efficient 

combustion. Other brands of the same spray angle and 

spray pattern may be used but may not perform at the 

expected level of CO

2

 and smoke. Nozzles are delicate 

and should be protected from dirt and abuse. Nozzles are 

mass-produced and can vary from sample to sample. For 

all of those reasons a spare nozzle is a desirable item for 

a serviceman to have.

2. FLAME  SHAPE — Looking into the combustion 

chamber through the observation port, the flame should 

appear straight with no sparklers rolling up toward the 

crown of the chamber. If the flame drags to the right or 

left, sends sparklers upward or makes wet spots on the 

chamber walls, the nozzle should be replaced. If the 

condition persists look for fuel leaks, air leaks, water or 

dirt in the fuel as described above.

3.  FUEL  LEAKS — Any fuel leak between the pump 

and the nozzle will be detrimental to good combustion 

results. Look for wet surfaces in the air tube, under the 

ignitor, and around the air inlet. Any such leaks should 

be repaired as they may cause erratic burning of the fuel 

and in the extreme case may become a fire hazard.

4.  AIR  LEAKS — Any such leaks should be repaired, as 

they may cause erratic burning of the fuel and in extreme 

cases may become a fire hazard.

5.  GASKET  LEAKS — If 11.5 to 12.5% CO

2

 with a #1 

smoke cannot be obtained in the breeching, look for air 

leaks around the burner mounting gasket, observation 

door, and canopy gasket. Such air leaks will cause a lower 

CO

2

 reading in the breeching. The smaller the firing rate 

the greater effect an air leak can have on CO

2

 readings.

6.  DIRT — A fuel filter is a good investment. Accidental 

accumulation of dirt in the fuel system can clog the nozzle 

or nozzle strainer and produce a poor spray pattern from 

the nozzle. The smaller the firing rate, the smaller the slots 

become in the nozzle and the more prone to plugging it 

becomes with the same amount of dirt.

7.  WATER — Water in the fuel in large amounts will stall 

the fuel pump. Water in the fuel in smaller amounts will 

cause excessive wear on the pump, but more importantly 

water doesn’t burn. It chills the flame and causes smoke 

and unburned fuel to pass out of the combustion chamber 

and clog the flueways of the boiler.

8.  COLD  OIL — If the oil temperature approaching the 

fuel pump is 40°F or lower, poor combustion or delayed 

ignition may result.  Cold oil is harder to atomize at 

the nozzle. Thus, the spray droplets get larger and the 

flame  shape  gets  longer. An  outside  fuel  tank  that  is 

xIII.  TROUBLE  SHOOTING

above grade or has fuel lines in a shallow bury is a good 

candidate for cold oil. The best solution is to locate the 

tank near the boiler in the basement utility room or bury 

the tank and lines deep enough to keep the oil above 40°F.  

Check environmental issues with local authorities having 

jurisdiction.

9.  HIGH  ALTITUDE  INSTALLATIONS — Air openings 

must be increased at higher altitudes. Use instruments 

and set for 11.5 to 12.5% CO

2

.

10.  START-UP  NOISE — Late ignition is the cause of 

start-up noises. If it occurs recheck for electrode settings, 

flame shape, air or water in the fuel lines.

11.  SHUT  DOWN  NOISE — If the flame runs out of air 

before it runs out of fuel, an after burn with noise may 

occur. That may be the result of a faulty cut-off valve in 

the fuel pump, or it may be air trapped in the nozzle line. 

It may take several firing cycles for that air to be fully 

vented through the nozzle. Water in the fuel or poor flame 

shape can also cause shut down noises.

NOTICE

CHECK TEST PROCEDURE. A very good test for 

isolating fuel side problems is to disconnect the 

fuel  system  and  with  a  24"  length  of  tubing,  fire 

out  of  an  auxiliary  five  gallon  pail  of  clean,  fresh, 

warm #2 oil from another source. If the burner runs 

successfully when drawing out of the auxiliary pail 

then the problem is isolated to the fuel or fuel lines 

being used on the jobsite.

B.

 

OIL  PRIMARY  CONTROL (Oil Primary)

1.  Burner (Oil Primary) will not come on.

a.  No power to Oil Primary.
b.  Oil Primary is in lockout or restricted mode.  Press 

reset button for one (1) second to exit lockout.  If 

control has recycled three times within the same 

call for heat, it will enter into restricted mode.  To 

reset from restricted mode, refer to Section XI, 

Paragraph I, No. 2 for details.

c.  CAD cell seeing light.
d.  CAD assembly defective.
e.  Control motor relay is stuck closed (see note 

below).

2.  Burner (control) will light, then shut down after a short 

time, then restart after one (1) minute.
a.  CAD cell is defective.
b.  Air leaking into oil line causing flame out.
c.  Defective nozzle causing flame to be erratic.
d.  Excessive airflow or draft causing flame to leave 

burner head.

e.  Excessive back pressure causing flame to be erratic.

Summary of Contents for MPO-IQ

Page 1: ...n on boiler provide Boiler Model Number and Serial Number as shown on Rating Label Boiler Model Number MPO IQ Boiler Serial Number Installation Date Heating Contractor Phone Number Address As an ENERG...

Page 2: ...oke and unburned fuel to pass out of the combustion chamber and clog the flueways of the boiler 8 COLD OIL If the oil temperature approaching the fuel pump is 40 F or lower poor combustion or delayed...

Page 3: ...osed Note The Safety Monitoring Circuit SMC is designed to provide lockout in the event of a stuck or welded motor relay C IQ OIL BOILER CONTROL When a problem occurs with the boiler operation the IQ...

Page 4: ...ce control if problem persists Err 8 Manual Reset Lockout resettable Set if Err 4 was invoked four times in a row Check wiring and clear Lockout by pressing all three user keys for 30 seconds XIII TRO...

Page 5: ...uel supply lines and filter for obstructions ErP 10 No Ignition Check Ignition Transformer The burner was not lit and spark was not detected Check the electrodes spring contacts or high voltage wires...

Page 6: ...iring ErP 84 LWCO Option Card Low Water Event Low water level Limit has caused the boiler to shutdown Make sure that the water level has reached the probe Limit will re close automatically after water...

Page 7: ...Water DHW Priority Forcing Circulator Off When there is a DHW heat request wired to the boiler control s ZR terminal the System Circulator will be forced off for the duration of the DHW heat request...

Page 8: ...heck fuel lines and filter are free of obstructions Check fuel lines are fully purged of air Use the pump priming feature to purge the system of air Check that the burner motor is spinning and the pum...

Page 9: ...install card If problem persists replace card Err 5 Limit Output OFF in ON State Check limit string wiring replace the Option Panel Err 6 Incorrect Wiring Check boiler wiring Err 7 Internal Option Pan...

Reviews: