66

xIII.  TROUBLE  SHOOTING (continued)

F.

  USE BOILER CONTROL DISPLAY 

STA

 (STATUS) NUMBER TO GUIDE TROUBLESHOOTING 

 

The Boiler Control will flash “

STA

” followed by a number.  Use this number to identify the boiler problem in the table below: 

1.  Burner and Circulator Off

Display / Status

Recommended Corrective Action

STA1

Standby

Burner off

Circulator off

The boiler has not detected a call for heat (

hr

 = 

off

 and dh = 

off

). 

Ensure there is power to the boiler control.
Check the thermostat:

-   When a thermostat call for heat is detected boiler control display “

hr

” will show “

on

-   Make sure thermostat is calling for heat and contacts (including appropriate zone controls) 

    are closed.  Check for loose connection.
Check the DHW demand:

-   When a domestic call for heat is detected boiler control display “

dh

” will show “

on

-   Make sure the DHW aquastat contact is closed.  Check for loose connection.

4.  Circulator is On, But Oil Primary is in Standby

Display / Status

Recommended Corrective Action

STA15

Limit Open

Heat Request occurs and start of operating sequence is halted due to an open limit.  Open limits may include 

Auxiliary High Limit or Low Water Cut-off Cards (when installed).  If Boiler Control shows "

StA 15

" proceed to 

Paragraph F.

3.  Burner is On, But Circulator is Off

Display / Status

Recommended Corrective Action

StA 8

Burner on

Circulator off

Domestic Hot Water (DHW) Priority Forcing Circulator Off
-   When there is a DHW heat request wired to the boiler control’s ZR terminal the System Circulator will be 

    “forced off” for the duration of the DHW heat request.  When the DHW heat request ends the System 

    Circulator “force off” is removed, the circulator can respond normally.  When the Priority Time, (

PT_

)

    Parameter is set to “

off

” the System Circulator is not “forced off” for a DHW call for heat.  

-   When there is DHW heat request and an Outdoor Air Reset IQ Card is installed the System Circulator will be 

    forced off for the duration of the Reset Card’s Priority Time (

PT_

) parameter.  Check Priority Time (

PT_

    parameter using the Outdoor Air Reset IQ Option Card Adjustment Mode (see Reset Card Adjustment Mode 

    Instructions).
Wiring / Circulator Issue:
-   Check wiring for loose connection, miswiring

-   Check circulator

Display / Status

Recommended Corrective Action

STA1

Circulator

Pre-purge

Burner off

Circulator on

The boiler is warm and circulator is providing residual boiler heat to building:
Check boiler temperature

-   The boiler will not start until boiler water temperature is less than the Setpoint (

SP

) minus differential (

df

)

-   If boiler water temperature is higher than Start Temperature (

ST_

, default = 140 F) and the Circulator Pre-purge 

    (

PP_

, default = 2 minutes) time has not expired, boiler start will be delayed until water temperature drops or time 

    expires.  To permit the boiler to start sooner increase Start Temperature parameter.  Refer to Operation Section 

    for additional information.

2.  Circulator is On, But Burner is Off

Summary of Contents for MPO-IQ

Page 1: ...n on boiler provide Boiler Model Number and Serial Number as shown on Rating Label Boiler Model Number MPO IQ Boiler Serial Number Installation Date Heating Contractor Phone Number Address As an ENERG...

Page 2: ...oke and unburned fuel to pass out of the combustion chamber and clog the flueways of the boiler 8 COLD OIL If the oil temperature approaching the fuel pump is 40 F or lower poor combustion or delayed...

Page 3: ...osed Note The Safety Monitoring Circuit SMC is designed to provide lockout in the event of a stuck or welded motor relay C IQ OIL BOILER CONTROL When a problem occurs with the boiler operation the IQ...

Page 4: ...ce control if problem persists Err 8 Manual Reset Lockout resettable Set if Err 4 was invoked four times in a row Check wiring and clear Lockout by pressing all three user keys for 30 seconds XIII TRO...

Page 5: ...uel supply lines and filter for obstructions ErP 10 No Ignition Check Ignition Transformer The burner was not lit and spark was not detected Check the electrodes spring contacts or high voltage wires...

Page 6: ...iring ErP 84 LWCO Option Card Low Water Event Low water level Limit has caused the boiler to shutdown Make sure that the water level has reached the probe Limit will re close automatically after water...

Page 7: ...Water DHW Priority Forcing Circulator Off When there is a DHW heat request wired to the boiler control s ZR terminal the System Circulator will be forced off for the duration of the DHW heat request...

Page 8: ...heck fuel lines and filter are free of obstructions Check fuel lines are fully purged of air Use the pump priming feature to purge the system of air Check that the burner motor is spinning and the pum...

Page 9: ...install card If problem persists replace card Err 5 Limit Output OFF in ON State Check limit string wiring replace the Option Panel Err 6 Incorrect Wiring Check boiler wiring Err 7 Internal Option Pan...

Reviews: