7
WARNING
If you do not follow these instructions exactly,
a fire or explosion may result causing property
damage or personal injury.
DANGER
Do not install boiler where gasoline or other
flammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners, chemicals,
sprays, paint removers, fabric softeners, etc.) are
used or stored.
NOTICE
Due to the low water content of the boiler, mis-
sizing of the boiler with regard to the heating
system load will result in excessive boiler cycling
and accelerated component failure. U.S. Boiler
DOES NOT warrant failures caused by mis-sized
boiler applications. DO NOT oversize the boiler to
the system. Modular boiler installations greatly
reduce the likelihood of boiler oversizing.
A
.
Installation must conform
to the requirements of the
authority having jurisdiction. In the absence of such
requirements, installation must conform to the
National
Fuel Gas Code
, ANSI Z223.1/NFPA 54, and/or
Natural
Gas and Propane Installation Code
, CAN/CSA B149.1.
Where required by authority having jurisdiction,
installation must conform to Standard for
Controls and
Safety Devices for Automatically Fired Boilers
, ANSI/
ASME CSD-1.
B.
Appliance is design certified
for installation on
combustible flooring. Do not install boiler on
carpeting.
C.
Provide clearance
between boiler jacket and
combustible material in accordance with local fire
ordinance. Refer to Figure 1 for minimum listed
clearance from combustible material. Recommended
service clearance is 24 (610 mm) inches from left side,
right side and front. Service clearances may be reduced
to minimum clearances to combustible materials.
D.
Install on level floor.
For basement installation provide
solid base such as concrete, if floor is not level or if
water may be encountered on floor around boiler. Floor
must be able to support weight of boiler, water and all
additional system components.
I. PRE-INSTALLATION
E.
Protect gas ignition system components
from water
(dripping, spraying, rain, etc.) during boiler operation
and service (circulator replacement, condensate trap,
control replacement, etc.).
F.
Provide combustion and ventilation air
in accordance
with the section “Air for Combustion and Ventilation,”
of the
National Fuel Gas Code
, ANSI Z223.1/NFPA 54,
or Sections 8.2, 8.3 or 8.4 of
Natural Gas and Propane
Installation Code
, CAN/CSA-B149.1, or applicable
provisions of local building codes.
WARNING
Adequate combustion and ventilation air must
be provided to assure proper combustion.
The following guideline is based on the
National Fuel Gas
Code
, ANSI Z223.1/NFPA 54.
1. Determine volume of space (boiler room). Rooms
communicating directly with space (through
openings not furnished with doors) are considered
part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space.
Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total
Input.
a. If result is greater than or equal to 50 ft³ per
1,000 Btuh, space is considered an
unconfined
space
.
b. If result is less than 50 ft³ per 1,000 Btuh, space
is considered a
confined space
.
4. Determine building type. A building of
unusually
tight construction
has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a
rating of 1 perm or less with openings gasketed
and sealed, and;
b. Weather-stripping has been added on openable
windows and doors, and;
c. Caulking or sealants applied in joints around
window and door frames, between sill plates and
floors, between wall-ceiling joints, between wall
panels, at plumbing and electrical penetrations,
and at other openings.
5. For boiler located in an
unconfined space in a
building of
other than unusually tight construction
,
adequate combustion and ventilation air is normally
provided by fresh air infiltration through cracks
around windows and doors.
Summary of Contents for PVG3
Page 14: ...14 Figure 4 Horizontal Vent Installation III Venting continued...
Page 16: ...16 Figure 7 Attic Offset Figure 6 Vertical Vent Installation III Venting continued...
Page 29: ...29 Figure 17 Wiring Connection Diagram VI Electrical continued...
Page 31: ...31 Figure 19 Circulator Zoned System Wiring Diagram VI Electrical continued...
Page 32: ...32 Figure 20 Zone Valve Zoned System Wiring Schematic VI Electrical continued...
Page 34: ...34 Figure 21 Modular Boiler Piping VII Modular Installation continued...
Page 36: ...36 Figure 22 Operating Instructions VIII System Start up continued...
Page 51: ...51 Figure 29 Flue and Burner Cleanout 1 Burner XI Service continued...
Page 54: ...54 XII Repair Parts continued...
Page 56: ...56 XII Repair Parts continued...
Page 60: ...60 XII Repair Parts continued...
Page 67: ...67 SERVICE RECORD DATE SERVICE PERFORMED...
Page 68: ...68 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...