background image

23

VI:  SYSTEM START-UP (continued)

F.

  START  OIL  BURNER.

1.  Open vent fitting on fuel pump.

2.  PRESS RED RESET BUTTON on primary control, 

hold for one (1) second and release to reset primary 

control.

3.  TURN  ‘ON’  BURNER  service switch and 

allow burner to run until oil flows from vent 

fitting in a SOLID stream without air bubbles for 

approximately 10 seconds.  

 NOTE: 

 For Primary Control "Pump Priming 

Cycle" details, see Paragraph I, No. 2., Step a.,  Item 

ii

 .

4.  Close vent fitting and burner flame should start 

immediately after prepurge is completed.  Prepurge 

prevents burner flame until 15 seconds has elapsed 

after initial power is applied to burner.  During 

prepurge the motor and igniter will operate but the 

oil valve will remain closed.  Refer to Oil Primary 

Control Instructions for more details.

5.  Adjust oil pressure.

a.  When checking a fuel unit's operating pressure, a 

reliable pressure gauge may be installed in either 

the bleeder port or the nozzle port.  For Beckett 

burner refer to Figure 19.  

b.  Locate oil pressure adjusting screw and turn 

screw to obtain proper pump pressure, refer to 

Table 4.

c.  To check the cut-off pressure, deadhead a reliable 

pressure gauge onto the copper connector tube 

attached to the nozzle port.  Run the burner for 

a short period of time.  Shut the burner off.  The 

pressure should drop and hold.

d.  Turn "OFF" the burner.  Remove the pressure 

gauge and install port/bleeder plug and/or 

reconnect the nozzle port line and tighten.  Start 

the burner again.

G.

  ADJUST  OIL  BURNER  WHILE  OPERATING.

  

(flame present)

1.  ADJUST  DRAFT  REGULATOR  for a draft 

of zero to maximum of  -.03" (water gauge) in the 

breeching after chimney has reached operating 

temperature and while burner is running.  Burner 

will operate with a positive draft over fire and zero 

draft in the breeching.  Adjust Draft Regulator such 

that maximum draft of  -.03" is reached in coldest 

weather.

2.  READJUST  THE  AIR  DAMPER  SETTING 

(Air Band/Air Shutter/Air Gate)  on burner for a 

light orange colored flame while the draft over the 

fire is -.02" water column (water gauge).  Use a 

smoke tester and adjust air for minimum smoke (not 

to exceed #1) with a minimum of excess air.  Make 

final check using suitable instrumentation to obtain 

a CO

2

 of 11.5 to 12.5% with draft of  -.02"  water 

column over the fire.  These settings will assure a 

safe and efficient operating condition.  If the flame 

appears stringy instead of a solid fire, try another 

nozzle of the same type.  Flame should be solid and 

compact.  After all adjustments are made recheck for 

a draft of  -.02"  water column over the fire.

 

NOTE

:  Paragraph G, Step 1 

MUST BE

 repeated 

every time the Air Damper Setting is readjusted.

3.  ONLY  READJUST  THE  HEAD  SETTING,  if 

necessary.

 

Beckett AFG Burners

a.  Beckett MB(L1) Head burner has a fixed head 

which is non-adjustable.  Check "Z" Dimension 

as outlined in Paragraph 2, Step 2c of this 

section.

 

 

NOTE:  Step outlined in Paragraph G, Steps 1 and 

2 above 

MUST BE

 repeated every time the Head or 

air Damper Setting is readjusted.

WARNING

DO NOT  loosen  or  remove  any  oil  line  fittings 

while burner is operating.

4.   FLAME  FAILURE
  The V1 RO/FO boiler controls operate the burner 

automatically. If for unknown reasons the burner 

ceases to fire and the reset button on the primary 

control has tripped, the burner has experienced 

ignition failure. Refer to Oil Primary Control 

features, Paragraph I, Step 2 of this section and 

Section X, Troubleshooting, Paragraph B.  If the 

Figure 19:  Adjusting Fuel Pump Pressure

Summary of Contents for V13A RO/FO

Page 1: ...vice or repairs to boiler call your heating contractor or oil supplier When seeking information on boiler provide Boiler Model Number and Serial Number as shown on Rating Label located on top of the b...

Page 2: ...ace rust on cast iron sections may be attributed to the manufacturing process as well as condensation during storage Surface rust is normal and does not affect the performance or longevity of a boiler...

Page 3: ...contractor to see that all controls are correctly installed and are operatingproperlywhentheinstallationiscompleteincludingverifyingthatthelimitsensorisfullyinstalled Failure to properly install Limit...

Page 4: ...e joints may be signs of condensing fluegases Fluegascondensateiscorrosive whichrequiresspecialconsiderationandmustbeaddressed immediately Refer to Venting Natural Draft Chimney listed in Table of Con...

Page 5: ...5 SECTION I GENERAL INFORMATION Figure 1 VI RO FO Water Boiler with Tankless Heater Beckett AFG Burner...

Page 6: ...rking Pressure Water 30 PSI Water Only Boiler Model No Burner Capacity AHRI NET Ratings Tankless Heater Capacity Minimum Chimney Requirements AFUE GPH MBH DOE Heating Capacity MBH Water MBH V1 2 Heate...

Page 7: ...space Iftheresultislessthan50ft3 1000 BTU per hour then the space is considered a confined space 4 For boiler located in an unconfined space of a conventionally constructed building the fresh air infi...

Page 8: ...r Tilt boiler and remove crate skid Care should be exercised to prevent damage to Jacket or Burner C MOVE BOILER TO PERMANENT POSITION by sliding or walking D INSPECT COMBUSTION TARGET WALL 1 OPEN FLA...

Page 9: ...njury or loss of life due to elevated operating temperatures and or pressures III INSTALLATION INSTRUCTIONS continued Figure 4 Limit Sensor Insertion Figure 5 Securing Limit Sensor 3 Securing Limit Se...

Page 10: ...pany s standard warranty There are many possible causes of oxygen contamination such as a Addition of excessive make up water as a result of system leaks b Absorption through open tanks and fittings c...

Page 11: ...it must be mounted in the system piping above the boiler The minimum Figure 8 Recommended Piping for Combination Heating Cooling Refrigeration System III INSTALLATION INSTRUCTIONS continued safe wate...

Page 12: ...is accomplished by installing hose bibs as illustrated in Figure 9 and allowing water at city pressure to run into hose bibA through the heater and out hose bib B until the discharge is clear The tees...

Page 13: ...THE OUTLET OF THE BOILER TO THE CHIMNEY MUST BE INSTALLED ACCORDINGTONFPA211 ORLOCALCODES Refer to Figures 11 12 and 13 Figure 11 Installation of FO in a Confined Space with Adjacent Chimney NOTE 1 Ty...

Page 14: ...lon of fuel input to the burner 3 Keep right side of boiler accessible for flue cleanout and tankless coil maintenance 4 Boiler is heavily insulated and is suitable for 1 clearance from jacket surface...

Page 15: ...of boiler accessible for flue cleanout and tankless coil maintenance 4 Boiler is heavily insulated and is suitable for 1 clearance from jacket surface to combustibles 5 Boiler is of wet base design an...

Page 16: ...efficiency than the boiler being replaced That probably means that the stack temperature from the new boiler will be lower than that from the old boiler and with less room air being drawn up the chimn...

Page 17: ...jacket junction boxes and or control boxes 3 Use armored cable BX over all exposed line voltage wiring 4 If an indirect water heater is used use priority zoning Do not use priority zoning for Hydro Ai...

Page 18: ...CTRICAL continued Figure 15 Schematic Wiring Diagram with Tankless Heater Warm Start Control Beckett Burner Refer to Figure 16 for Schematic wiring diagram of appropriate burner and oil primary contro...

Page 19: ...ELECTRICAL continued Figure 16 Schematic Wiring Diagrams For Beckett GeniSys Oil Primary Control NOTE APPLY THIS BURNER SCHEMATIC TO APPROPRIATE STEAM OR WATER BOILER CONTROL SCHEMATIC REFER TO FIGUR...

Page 20: ...When zone valve is completely purged of air close zone valve or shut off valve Open zone valve to the next zone to be purged Repeat this step until all zones have been purged At completion open all z...

Page 21: ...osen the splined nut and hex head screw securing the escutcheon plate to the burner housing ii Place the end of a ruler at the leading edge of the head and using a straight edge across the end of the...

Page 22: ...22 VI SYSTEM START UP continued Figure 17 L1 Fixed Head Electrode Positioning and Gun Setting Beckett AFG Figure 18 F Fixed Head Electrode Positioning and Gun Setting Beckett AFG...

Page 23: ...chimney has reached operating temperature and while burner is running Burner will operate with a positive draft over fire and zero draft in the breeching Adjust Draft Regulator such that maximum draf...

Page 24: ...with a clean cloth until clean then replace and readjust oil pressure If dripping or after burn persist replace fuel pump I TEST CONTROLS 1 Check thermostat operation Raise and lower thermostat setti...

Page 25: ...and the resistance measured with a meter in the conventional way Conduct these tests with flame present see chart below Flame Detection Range Normal 0 1600 ohms Limited 1600 ohms to lockout 3 Check Oi...

Page 26: ...g The burner should shut down and circulators continue running c Allow the temperature to drop below control setting The burner must restart d Boiler installation is not considered complete until this...

Page 27: ...hermostat is not satisfied and the Operating Setpoint SP is reached the system circulator will continue to operate and the burner will stop When the boiler water temperature drops below the setpoint l...

Page 28: ...F Adjust Low Limit Setting Ldf 10 25 F Adjust Low Limit Differential Setting ZC_ ZR or dh ZC and ZR Terminal Function Or_ 0 10 minutes Pump Overrun Time PP_ 0 20 minutes Pump Pre purge Time St_ 140 1...

Page 29: ..._ 2 Minutes g Start Temperature The amount of Heat available is calculated by taking the difference between measured boiler water temperature and the Start Temperature setting Useful Heat Available is...

Page 30: ...ervice heating zone 1 A second zone s thermostat may be wired to the ZR input to energize heating zone 2 circulator wired to the ZC output Both outputs function independently TT input controls only th...

Page 31: ...as previously described test the pH of the water in the system This can easily be done by drawing a small sample of boiler water and testing with hydrion paper which is used in the same manner as lit...

Page 32: ...corners 3 Always keep the manual fuel supply valve shut off if the burner is shut down for an extended period of time 4 To recondition the heating system in the fall season after a prolonged shut down...

Page 33: ...immediately C TO CLEAN TOP OF BOILER SECTION 1 Remove smokepipe from flue collar of canopy see Figure 1 2 Using wire or fibre bristle brush and vacuum clean top of boiler through flue collar of canop...

Page 34: ...Long sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clothes separatel...

Page 35: ...ay pattern from the nozzle The smaller the firing rate the smaller the slots become in the nozzle and the more prone to plugging it becomes with the same amount of dirt 6 WATER Water in the fuel in la...

Page 36: ...the oil primary control Hard Lockout will occur if the Oil Primary Control locks out three 3 times during a call for heat This is indicated by red light reset button solid on C INTELLIGENT OIL BOILER...

Page 37: ...ng safety output relay check sequence or un powered during running or powered in idle in combination with water temperature above 264 F limit Cycle power to the control Replace control if problem pers...

Page 38: ...le distributor Should you require assistance in locating a U S Boiler Company Distributor in your area or have questions regarding the availability of U S Boiler Company products or repair parts pleas...

Page 39: ...l 1 1 8202701 7 Tie Rod Sets Tie Rods 3 8 16 x 12 1 2 Lg 2 80861010 Tie Rods 3 8 16 x 17 Lg 2 80861011 Hex Nuts 3 8 16 4 4 80860400 Flat Washers 3 8 4 4 80860600 8 Burner Mounting Plate Insulation 1 1...

Page 40: ...40 XI REPAIR PARTS continued Figure 25 Flush Jacket Components...

Page 41: ...RO FO Top Rear Wrapper Assembly 1 60422034 1 60422044 4 Jacket Right Side Heater Panel Assembly 1 60422033 1 60422043 5 Jacket RO FO Front Panel Assembly 1 1 6042212 6 Additional Boiler Top Insulatio...

Page 42: ...42 XI REPAIR PARTS continued Figure 26 V1 RO FO Trim and Controls...

Page 43: ...askets Taco 00 2 2 806602006 Temperature Sensor Clip 1 1 102422 01 Cable Clamp 5 16 3 3 8136073 Sheet Metal Screw 8 x 1 2 3 3 80860000 3 Miscellaneous Parts Bag Group Shipped in Misc Parts Carton 3A D...

Page 44: ...BURNER PARTS CONTACT YOUR WHOLESALER OR THE BURNER MANUFACTURER R W BECKETT CORP 38251 CENTER RIDGE RD P O BOX 1289 ELYRIA OHIO 1 800 645 2876 44036 XI Repair Parts continued FIGURE 27 BECKETT AFG OI...

Page 45: ...ulkhead 3666 3666 Connector Tube Assembly 5394 5394 Electrode Clamp 149 149 Electrode Clamp Screw 4219 4219 Electrode Insulator Assembly Kit 5780 5780 Nozzle Line LT Assembly Less Head Electrodes LT05...

Page 46: ...to connect the probe LWCO to the supply or return piping as shown below Select the appropriate size tee using the LWCO manufacturer s instructions Often the branch connection must have a minimum diame...

Page 47: ...ow the LWCO probe It may be necessary to open relief valve seat to allow air into system for the water to drain close drain valve and relief valve once completed Generate a boiler demand by turning up...

Page 48: ...48 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...

Reviews: