background image

35

X:  TROUBLESHOOTING

A.

  COMBUSTION

1.  NOZZLES — Although the nozzle is a relatively 

inexpensive device, its function is critical to the 

successful operation of the oil burner. The selection 

of the nozzle supplied with the V1 RO/FO boiler 

is the result of extensive testing to obtain the best 

flame shape and efficient combustion. Other brands 

of the same spray angle and spray pattern may be 

used but may not perform at the expected level of 

CO

2

 and smoke. Nozzles are delicate and should be 

protected from dirt and abuse. Nozzles are mass-

produced and can vary from sample to sample. For 

all of those reasons a spare nozzle is a desirable item 

for a serviceman to have.

2.  FUEL  LEAKS — Any fuel leak between the 

pump and the nozzle will be detrimental to good 

combustion results. Look for wet surfaces in the air 

tube, under the ignitor, and around the air inlet. Any 

such leaks should be repaired as they may cause 

erratic burning of the fuel and in the extreme case 

may become a fire hazard.

3.  SUCTION LINE LEAKS — Any such leaks should 

be repaired, as they may cause erratic burning of 

the fuel and in extreme cases may become a fire 

hazard.  Whatever it takes, 

The Oil Must Be Free 

of Air

.  This can be a tough problem, but it must be 

resolved.  Try bleeding the pump through a clear 

tube.  There must be no froth visible.  There are 

various test kits available to enable you to look at 

the oil through clear tubing adapted to the supply 

line at the pump fitting.  Air eliminators are on the 

market that have potential.  Also, electronic sight 

glasses are being used with good success.  At times, 

new tubing must be run to the tank or new fittings 

put on.  Just make sure you get the air out before 

you leave.

  Any air leaks in the fuel line will cause an unstable 

flame and may cause delayed ignition noises.  Use 

only flare fittings in the fuel lines.

4.  GASKET  LEAKS — If 11.5 to 12.5% CO

2

 with a 

#1 smoke cannot be obtained in the breeching, look 

for air leaks around the burner mounting gasket, 

observation door, and canopy gasket. Such air leaks 

will cause a lower CO

2

 reading in the breeching. The 

smaller the firing rate the greater effect an air leak 

can have on CO

2

 readings.

5.  DIRT — A fuel filter is a good investment. 

Accidental accumulation of dirt in the fuel system 

can clog the nozzle or nozzle strainer and produce a 

poor spray pattern from the nozzle. The smaller the 

firing rate, the smaller the slots become in the nozzle 

and the more prone to plugging it becomes with the 

same amount of dirt.

6.  WATER — Water in the fuel in large amounts will 

stall the fuel pump. Water in the fuel in smaller 

amounts will cause excessive wear on the pump, 

but more importantly water doesn’t burn. It chills 

the flame and causes smoke and unburned fuel to 

pass out of the combustion chamber and clog the 

flueways of the boiler.

7.  COLD  OIL — If the oil temperature approaching 

the fuel pump is 40°F or lower, poor combustion or 

delayed ignition may result.  Cold oil is harder to 

atomize at the nozzle. Thus, the spray droplets get 

larger and the flame shape gets longer. An outside 

fuel tank that is above grade or has fuel lines in a 

shallow bury is a good candidate for cold oil. The 

best solution is to locate the tank near the boiler in 

the basement utility room or bury the tank and lines 

deep enough to keep the oil above 40°F.  Check 

environmental issues with local authorities having 

jurisdiction.

8.  FLAME  SHAPE — Looking into the combustion 

chamber through the observation port, the flame 

should appear straight with no sparklers rolling up 

toward the crown of the chamber. If the flame drags 

to the right or left, sends sparklers upward or makes 

wet spots on the target wall, the nozzle should be 

replaced. If the condition persists look for fuel leaks, 

air leaks, water or dirt in the fuel as described above.

9.  HIGH  ALTITUDE  INSTALLATIONS — Air 

openings must be increased at higher altitudes. Use 

instruments and set for 11.5 to 12.5% CO

2

.

10.  START-UP  NOISE — Late ignition is the cause 

of start-up noises. If it occurs recheck for electrode 

settings, flame shape, air or water in the fuel lines.

11.  SHUT  DOWN  NOISE — If the flame runs out of 

air before it runs out of fuel, an after burn with noise 

may occur. That may be the result of a faulty cut-off 

valve in the fuel pump, or it may be air trapped in the 

nozzle line. It may take several firing cycles for that 

air to be fully vented through the nozzle. Water in the 

fuel or poor flame shape can also cause shut down  

noises.

NOTICE

CHECK TEST PROCEDURE. A very good test for 

isolating fuel side problems is to disconnect the 

fuel system and with a 24" length of tubing, fire 

out of an auxiliary five gallon pail of clean, fresh, 

warm #2 oil from another source. If the burner runs 

successfully when drawing out of the auxiliary 

pail then the problem is isolated to the fuel or fuel 

lines being used on the jobsite.

Summary of Contents for V13A RO/FO

Page 1: ...vice or repairs to boiler call your heating contractor or oil supplier When seeking information on boiler provide Boiler Model Number and Serial Number as shown on Rating Label located on top of the b...

Page 2: ...ace rust on cast iron sections may be attributed to the manufacturing process as well as condensation during storage Surface rust is normal and does not affect the performance or longevity of a boiler...

Page 3: ...contractor to see that all controls are correctly installed and are operatingproperlywhentheinstallationiscompleteincludingverifyingthatthelimitsensorisfullyinstalled Failure to properly install Limit...

Page 4: ...e joints may be signs of condensing fluegases Fluegascondensateiscorrosive whichrequiresspecialconsiderationandmustbeaddressed immediately Refer to Venting Natural Draft Chimney listed in Table of Con...

Page 5: ...5 SECTION I GENERAL INFORMATION Figure 1 VI RO FO Water Boiler with Tankless Heater Beckett AFG Burner...

Page 6: ...rking Pressure Water 30 PSI Water Only Boiler Model No Burner Capacity AHRI NET Ratings Tankless Heater Capacity Minimum Chimney Requirements AFUE GPH MBH DOE Heating Capacity MBH Water MBH V1 2 Heate...

Page 7: ...space Iftheresultislessthan50ft3 1000 BTU per hour then the space is considered a confined space 4 For boiler located in an unconfined space of a conventionally constructed building the fresh air infi...

Page 8: ...r Tilt boiler and remove crate skid Care should be exercised to prevent damage to Jacket or Burner C MOVE BOILER TO PERMANENT POSITION by sliding or walking D INSPECT COMBUSTION TARGET WALL 1 OPEN FLA...

Page 9: ...njury or loss of life due to elevated operating temperatures and or pressures III INSTALLATION INSTRUCTIONS continued Figure 4 Limit Sensor Insertion Figure 5 Securing Limit Sensor 3 Securing Limit Se...

Page 10: ...pany s standard warranty There are many possible causes of oxygen contamination such as a Addition of excessive make up water as a result of system leaks b Absorption through open tanks and fittings c...

Page 11: ...it must be mounted in the system piping above the boiler The minimum Figure 8 Recommended Piping for Combination Heating Cooling Refrigeration System III INSTALLATION INSTRUCTIONS continued safe wate...

Page 12: ...is accomplished by installing hose bibs as illustrated in Figure 9 and allowing water at city pressure to run into hose bibA through the heater and out hose bib B until the discharge is clear The tees...

Page 13: ...THE OUTLET OF THE BOILER TO THE CHIMNEY MUST BE INSTALLED ACCORDINGTONFPA211 ORLOCALCODES Refer to Figures 11 12 and 13 Figure 11 Installation of FO in a Confined Space with Adjacent Chimney NOTE 1 Ty...

Page 14: ...lon of fuel input to the burner 3 Keep right side of boiler accessible for flue cleanout and tankless coil maintenance 4 Boiler is heavily insulated and is suitable for 1 clearance from jacket surface...

Page 15: ...of boiler accessible for flue cleanout and tankless coil maintenance 4 Boiler is heavily insulated and is suitable for 1 clearance from jacket surface to combustibles 5 Boiler is of wet base design an...

Page 16: ...efficiency than the boiler being replaced That probably means that the stack temperature from the new boiler will be lower than that from the old boiler and with less room air being drawn up the chimn...

Page 17: ...jacket junction boxes and or control boxes 3 Use armored cable BX over all exposed line voltage wiring 4 If an indirect water heater is used use priority zoning Do not use priority zoning for Hydro Ai...

Page 18: ...CTRICAL continued Figure 15 Schematic Wiring Diagram with Tankless Heater Warm Start Control Beckett Burner Refer to Figure 16 for Schematic wiring diagram of appropriate burner and oil primary contro...

Page 19: ...ELECTRICAL continued Figure 16 Schematic Wiring Diagrams For Beckett GeniSys Oil Primary Control NOTE APPLY THIS BURNER SCHEMATIC TO APPROPRIATE STEAM OR WATER BOILER CONTROL SCHEMATIC REFER TO FIGUR...

Page 20: ...When zone valve is completely purged of air close zone valve or shut off valve Open zone valve to the next zone to be purged Repeat this step until all zones have been purged At completion open all z...

Page 21: ...osen the splined nut and hex head screw securing the escutcheon plate to the burner housing ii Place the end of a ruler at the leading edge of the head and using a straight edge across the end of the...

Page 22: ...22 VI SYSTEM START UP continued Figure 17 L1 Fixed Head Electrode Positioning and Gun Setting Beckett AFG Figure 18 F Fixed Head Electrode Positioning and Gun Setting Beckett AFG...

Page 23: ...chimney has reached operating temperature and while burner is running Burner will operate with a positive draft over fire and zero draft in the breeching Adjust Draft Regulator such that maximum draf...

Page 24: ...with a clean cloth until clean then replace and readjust oil pressure If dripping or after burn persist replace fuel pump I TEST CONTROLS 1 Check thermostat operation Raise and lower thermostat setti...

Page 25: ...and the resistance measured with a meter in the conventional way Conduct these tests with flame present see chart below Flame Detection Range Normal 0 1600 ohms Limited 1600 ohms to lockout 3 Check Oi...

Page 26: ...g The burner should shut down and circulators continue running c Allow the temperature to drop below control setting The burner must restart d Boiler installation is not considered complete until this...

Page 27: ...hermostat is not satisfied and the Operating Setpoint SP is reached the system circulator will continue to operate and the burner will stop When the boiler water temperature drops below the setpoint l...

Page 28: ...F Adjust Low Limit Setting Ldf 10 25 F Adjust Low Limit Differential Setting ZC_ ZR or dh ZC and ZR Terminal Function Or_ 0 10 minutes Pump Overrun Time PP_ 0 20 minutes Pump Pre purge Time St_ 140 1...

Page 29: ..._ 2 Minutes g Start Temperature The amount of Heat available is calculated by taking the difference between measured boiler water temperature and the Start Temperature setting Useful Heat Available is...

Page 30: ...ervice heating zone 1 A second zone s thermostat may be wired to the ZR input to energize heating zone 2 circulator wired to the ZC output Both outputs function independently TT input controls only th...

Page 31: ...as previously described test the pH of the water in the system This can easily be done by drawing a small sample of boiler water and testing with hydrion paper which is used in the same manner as lit...

Page 32: ...corners 3 Always keep the manual fuel supply valve shut off if the burner is shut down for an extended period of time 4 To recondition the heating system in the fall season after a prolonged shut down...

Page 33: ...immediately C TO CLEAN TOP OF BOILER SECTION 1 Remove smokepipe from flue collar of canopy see Figure 1 2 Using wire or fibre bristle brush and vacuum clean top of boiler through flue collar of canop...

Page 34: ...Long sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clothes separatel...

Page 35: ...ay pattern from the nozzle The smaller the firing rate the smaller the slots become in the nozzle and the more prone to plugging it becomes with the same amount of dirt 6 WATER Water in the fuel in la...

Page 36: ...the oil primary control Hard Lockout will occur if the Oil Primary Control locks out three 3 times during a call for heat This is indicated by red light reset button solid on C INTELLIGENT OIL BOILER...

Page 37: ...ng safety output relay check sequence or un powered during running or powered in idle in combination with water temperature above 264 F limit Cycle power to the control Replace control if problem pers...

Page 38: ...le distributor Should you require assistance in locating a U S Boiler Company Distributor in your area or have questions regarding the availability of U S Boiler Company products or repair parts pleas...

Page 39: ...l 1 1 8202701 7 Tie Rod Sets Tie Rods 3 8 16 x 12 1 2 Lg 2 80861010 Tie Rods 3 8 16 x 17 Lg 2 80861011 Hex Nuts 3 8 16 4 4 80860400 Flat Washers 3 8 4 4 80860600 8 Burner Mounting Plate Insulation 1 1...

Page 40: ...40 XI REPAIR PARTS continued Figure 25 Flush Jacket Components...

Page 41: ...RO FO Top Rear Wrapper Assembly 1 60422034 1 60422044 4 Jacket Right Side Heater Panel Assembly 1 60422033 1 60422043 5 Jacket RO FO Front Panel Assembly 1 1 6042212 6 Additional Boiler Top Insulatio...

Page 42: ...42 XI REPAIR PARTS continued Figure 26 V1 RO FO Trim and Controls...

Page 43: ...askets Taco 00 2 2 806602006 Temperature Sensor Clip 1 1 102422 01 Cable Clamp 5 16 3 3 8136073 Sheet Metal Screw 8 x 1 2 3 3 80860000 3 Miscellaneous Parts Bag Group Shipped in Misc Parts Carton 3A D...

Page 44: ...BURNER PARTS CONTACT YOUR WHOLESALER OR THE BURNER MANUFACTURER R W BECKETT CORP 38251 CENTER RIDGE RD P O BOX 1289 ELYRIA OHIO 1 800 645 2876 44036 XI Repair Parts continued FIGURE 27 BECKETT AFG OI...

Page 45: ...ulkhead 3666 3666 Connector Tube Assembly 5394 5394 Electrode Clamp 149 149 Electrode Clamp Screw 4219 4219 Electrode Insulator Assembly Kit 5780 5780 Nozzle Line LT Assembly Less Head Electrodes LT05...

Page 46: ...to connect the probe LWCO to the supply or return piping as shown below Select the appropriate size tee using the LWCO manufacturer s instructions Often the branch connection must have a minimum diame...

Page 47: ...ow the LWCO probe It may be necessary to open relief valve seat to allow air into system for the water to drain close drain valve and relief valve once completed Generate a boiler demand by turning up...

Page 48: ...48 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...

Reviews: