background image

106636-04 - 8/22

26

X-2

Installation, Operating & Service Manual

11 

Operation 

Status Codes displayed in

 STA 

Mode

Status

STA

Description

Standby 

(Burner off

Circulator off)

1

No call for heat detected

Circulator

Pre-purge

(burner off

circulator on)

1

Either condition is true:
a.  Call for heat detected and boiler   

     temperature higher than operating    

     setpoint.

b.  Call for heat detected and boiler 

     temperature higher than Start 

     Temperature (140°F default) and 

     Circulator Pre-purge Time has not 

     expired.

Self Test

17

Control internal checking

Drive Damper 

Open

18

Damper is energized. Control is 

waiting for damper switch to close.  

If damper end switch doesn't close 

within 60 seconds, control goes to 

STA

 20

Pre-purge

4

Damper is open for a 2 second delay

Spark

6

Pilot fuel valve is open and sparking 

has started.

Flame 

Proving

7

Main fuel valve is open and flame is 

being proven.

Running

8

Burner runs until call for heat is 

satisfied or operating setpoint is 

reached.

Table 11-1:  Sequence of Operation

Status Codes displayed in

 STA 

Mode

Status

STA

Description

Retry / 

Recycle 

Delay

10

If burner fails to light off (no flame 

signal), it waits 5 minutes and retries 

or if control loses flame signal during 

running, it will wait 10 seconds and 

then recycle.

Soft Lockout

13

System is shut down and will restart 

following a one hour enforced delay.

Hard Lockout

14

System is locked out. A manual or 

power reset is required to light off 

again.

Limit Open

15

There is a call for heat from 

thermostat, but Limit is open.

Flame 

Present Out 

of Sequence

16

Flame signal is still present when 

expected to be 0 (no flame).

Damper 

Failed to 

Open

20

Damper is still energized and damper 

end switch has not closed.

Table 11-2: Sequence Fault

1.  Boiler Sequence of Operation (See Table 11-1).

A.  When thermostat calls for heat, control starts 

system circulator.   

B.  If thermostat is not satisfied with residual 

heat in boiler, or boiler water temperature is 

less than start temperature (140oF) setpoint, 

start sequence continues by energizing vent 

damper. Once vent damper is fully open, 

ignition sequence is started. Damper must be 

in open position when appliance main burners 

are operating.

C. If thermostat is not satisfied and operating set 

point has been reached, system circulator 

will continue to operate and burners will stop. 

When boiler water temperature drops below 

setpoint less differential setting, burners will 

restart.  

D. After thermostat is satisfied, burners and 

circulator are stopped and vent damper is 

closed. 

E.  When indirect water heater thermostat is wired 

to DHW input, aquastat calls for heat and 

control starts DHW circulator. Vent damper is 

energized without delay and ignitor sequence 

is started.

2.  Boiler Fault.
 

If boiler fails to start, control provides status 

information to help determine cause of problem. 

Table 11-2 provides a list of boiler status codes 

that are reported.

3.  Using Display.
 

Control is located inside boiler front door.  

The control display, along with Up 

, Down 

, and “

I

I

” keys 

may be used to view boiler operating status (Figure 11-4).  

Summary of Contents for X-202

Page 1: ...er Read Before Proceeding 3 2 User Homeowner Read Before Proceeding 4 3 Specifications 5 4 Locating Boiler 6 5 Preparing Boiler 9 6 Venting 9 7 Water Piping 12 8 Gas Piping 16 9 Electrical 17 10 Syste...

Page 2: ...rate injury WARNING Indicates a hazardous situation that if not avoided could result in death or serious injury DANGER Explosion Hazard DO NOT store or use gasoline or other flammable vapors or liquid...

Page 3: ...l and free of pressure and that your clothing will protect you from a release of hot water or steam Do not rely solely on boiler temperature and pressure gauge when making this judgement Install all g...

Page 4: ...er installing CO alarms near bedrooms in all levels of building to warn you and your family of potential CO exposure Do not block air flow into or around boiler or opening for fresh air into boiler ro...

Page 5: ...26 47 1 X 203 254 180 39 26 47 2 X 204 304 231 39 26 47 3 X 205 357 284 39 26 47 4 X 206 405 332 39 26 47 5 X 207 462 382 39 35 47 6 X 208 518 438 39 35 47 7 X 209 564 484 39 35 47 8 Table 3 3 Weights...

Page 6: ...stible materials gasoline or other flammable liquids from area around boiler 8 Check for and remove any potential combustion air contaminants from area around boiler See Table 4 1 Clearances 1 Provide...

Page 7: ...room exhausts so they will operate at maxi mum speed Do not operate a summer exhaust fan Close fireplace dampers Before Removing Existing Boiler Take pictures and measure and or mark existing steam an...

Page 8: ...ontal section of vent connector within reach of vent damper harness Area of each opening to be 1 sq inch for each 1 000 BTU hr 1 MBH input with minimum of 100 sq inches Height of opening should be hal...

Page 9: ...uctions in Section 4 Locating Boiler when removing a boiler from an existing vent system Maintain clearances to vent piping and draft hood per Figures 4 1 and 4 2 Do not use CPVC PVC Polypropylene or...

Page 10: ...alled 6 Venting continued Figure 6 1 Vent Damper Installation Figure 6 2 Vent Damper Position Indicator A Vent damper must be same size as outlet of vent supplied with boiler see Table 3 2 Unpack damp...

Page 11: ...terminal not less than 1 4 in per foot F Support horizontal portions of venting system to prevent sagging Use pipe straps brackets or hangers spaced 4 ft or less G Vent pipe must be inserted into but...

Page 12: ...m leaks repairing fittings and using non permeable materials in distribution system 2 Install circulator with flanges gaskets and bolts provided 3 Install Safety Relief Valve See Figure 7 1 Safety Rel...

Page 13: ...a boiler bypass if boiler is to be operated in a system which has a large volume or excessive radiation where low boiler water temperatures may be encountered i e converted gravity circulation system...

Page 14: ...tem Zone Valves Zone Circulators Full Port Isolation Valves Flow Check From System Full Port Isolation Valves Drain Valve Safety Relief Valve Pipe within 6 of floor or drain Drain Valve IWH Return IWH...

Page 15: ...Drain Valve IWH Return IWH Supply Indirect Water Heater IWH Air Separator Air Vent Expansion Tank Backflow Preventer Fill Valve Cold Water Return Full Port Isolation Valves Unions Flow Check IWH Circu...

Page 16: ...petroleum gas C Install sediment trap ground joint union and manual shut off valve upstream of boiler gas control valve See Figure 8 2 within 6 ft of boiler D All above ground gas piping upstream fro...

Page 17: ...ee Figures 9 1 and 9 2 4 For installations using zone valves provide separate transformer for zone valve wiring Consult zone valve manufacturer for assistance See Figure 9 3 9 Electrical WARNING Elect...

Page 18: ...106636 04 8 22 18 X 2 Installation Operating Service Manual Figure 9 1 Wiring Connection Diagram 9 Electrical continued...

Page 19: ...106636 04 8 22 19 X 2 Installation Operating Service Manual Figure 9 2 Schematic Ladder Diagram 9 Electrical continued...

Page 20: ...106636 04 8 22 20 X 2 Installation Operating Service Manual 9 Electrical continued Figure 9 3 Wiring Schematic Zone Valves Figure 9 4 Wiring Schematic Zone Circulators...

Page 21: ...essure reducing valve system will automatically fill to 12 psi K Remove hose from drain valve DANGER Explosion Hazard Do not use matches candles open flames or other ignition sources to check for leak...

Page 22: ...106636 04 8 22 22 X 2 Installation Operating Service Manual Figure 10 1 Operating Instructions 10 System Start up and Checkout continued...

Page 23: ...Figure 10 3 Natural Gas Pilot Flame Figure 10 4 LP Gas Pilot Flame Figure 10 2 Top View of Gas Valve LP Gas Only Pilot burner produces three 3 flames The center flame should be steady medium hard blu...

Page 24: ...ge that blows out manometer fluid B Adjust regulator on gas valve so manifold pressure matches values listed on rating label C Turning regulator adjustment screw clockwise increases pressure D Turning...

Page 25: ...er should shut down Set thermostat to call for heat and push TEST button on IDL 1200 to simulate low water condition Amber LOW WATER LED will illuminate and burner will shut down Release TEST button a...

Page 26: ...o light off again Limit Open 15 There is a call for heat from thermostat but Limit is open Flame Present Out of Sequence 16 Flame signal is still present when expected to be 0 no flame Damper Failed t...

Page 27: ...F High Limit Differential Setpoint tt Heat Request Status dh DHW Heat Request Status FLA Flame Current run Run Time Hours CYC Boiler Cycles Err Error Press I key on control to change from one paramete...

Page 28: ...oiler water temperature is less than 140 F This feature helps save energy by satisfying home heating needs with residual boiler heat rather than cycling boiler E Start Temperature Amount of heat avail...

Page 29: ...ter Demand dh IWH limit is wired to DHW terminal on control DHW circulator is wired to DHW Circulator on control wire harness Table 11 6 shows circulator status with different combinations of TT Input...

Page 30: ...ressure Checked gas manifold pressure Checked CO level in vent Checked vent damper operation Check ignition system safety shut off device Tested LWCO functionality Tested high limit operation Tested a...

Page 31: ...ing that is sufficiently tight around potential entry points for RCF dust 3 Gloves 4 Eye protection such as goggles safety glasses with side shields or full facepiece Take steps to assure adequate ven...

Page 32: ...ns in vent pipe and chimney B If masonry chimney is lined verify lining is in good condition and there are no openings into chimney C Remove soot accumulations with wire brush and vacuum D Repair or r...

Page 33: ...e and ground wire at Boiler Control F Install Burner Access Panel Connect Flame Rollout Switch wires 5 Inspect Water Piping A Check all system piping for leaks B Repair any leaks before placing back i...

Page 34: ...Provides adequate dilution air and ensures proper draft for boiler operation Blocked Vent Switch If vent becomes blocked switch will open requiring manual reset and cause burners to shut down 4 Flame...

Page 35: ...106636 04 8 22 35 X 2 Installation Operating Service Manual 3 5 4 6 7 On rear of boiler 8 2 1 Rear of Boiler 3 A B 14 How It Works continued...

Page 36: ...rious and potentially dangerous condition In the event the IDL 1200 detects a low water condition the system must be inspected by a qualified service technician before the boiler is returned to servic...

Page 37: ...If 24 VAC is present unplug vent damper harness from control With wire harness unplugged check for 24 VAC between P6 5 on Control and ground If voltage present replace control If voltage not present...

Page 38: ...draft Always follow recommended clearances combustion air requirements and venting requirements Check Flame Rollout Switch in event of excessive blockage of boiler section flue passageways is develop...

Page 39: ...recommended corrective action Flame sensed during pre purge before gas valve signaled open Check gas valve for proper operation Replace gas valve if problem persists Hard Lockout When a hard lockout...

Page 40: ...upply tubes of air b If no gas flow check following 24 volts across PV and MV PV at gas valve If voltage ok replace defective gas valve Check for break in wiring harness to gas valve 24 volts across c...

Page 41: ...617 03 1 109617 04 1 109617 05 1 109617 06 1 109617 07 1 109617 08 1 109617 09 1 Not Shown Blocked Vent Switch see Figure 6 1 109742 01 1 All X 2 Series Service Parts may be obtained through your loca...

Page 42: ...09613 08 1 Nat Gas 109613 09 1 2B Base Tray 2C Burner Tray 2D Base Side Insulation 2E Base Rear Insulation 2F Base Front Insulation 2G Drip Shields 2H Manifold Support Bracket LP Gas 110097 03 1 LP Ga...

Page 43: ...A in Gas Manifold N A 109731 07 1 109731 08 1 109731 09 1 3C Burner Orifices Natural Gas 46 109732 01 1 47 109733 01 1 16 orifices Burner Orifices LP Gas 1 25 mm 109735 01 1 1 20 mm 109734 01 1 16 ori...

Page 44: ...y No Description Part Number Quantity X 202 X 203 X 204 X 205 X 206 X 207 X 208 X 209 4A Control 103966 02 1 4B Transformer 106034 01 1 4C Temperature Sensor LWCO 106495 02 1 Not Shown Temperature Sen...

Page 45: ...cket Wrap around Jacket Panel 106357 03 1 106357 04 1 106357 05 1 106357 06 1 106357 07 1 106357 08 1 106357 09 1 5B Jacket Vestibule Panel 110126 02 1 110126 03 1 110126 04 1 110126 05 1 110126 06 1...

Page 46: ...9 6A Supply Water Manifold 109614 01 1 6B Temperature Pressure Gauge 105894 01 1 6C 30 PSI Relief Valve 109038 01 1 6D Drain Valve Obtain Locally 3 4 in NPT boiler connection 6E Vent Damper 109634 01...

Page 47: ...ity X 202 X 203 X 204 X 205 X 206 X 207 X 208 X 209 7A Power Supply Harness 109639 01 1 7B Main Control Harness 109640 01 1 7A 7B Key No Description Part Number Quantity X 202 X 203 X 204 X 205 X 206...

Page 48: ...e Appendix A Combination Refrigeration Heating System Water Chiller Shut off valves Shut off valves Expansion Tank Circulator Supply main to combined heating cooling system Return main from combined h...

Page 49: ...valvemayopenfrequently resultinginregular additions of make up water D If an automatic fill valve is installed installation of a water meter in fill line is strongly recommended so routine additions o...

Page 50: ...condensing during these heating season shoulders is unlikely to cause problems Larger volume systems during the shoulder heating seasons or systems with aggressive set back or low temperature systems...

Page 51: ...s A strap on temperature sensor measures boiler inlet temperatures This temperature signal is sent to a variable speed pump that will ensure boiler inlet temperatures are always greater than the facto...

Page 52: ...106636 04 8 22 52 X 2 Installation Operating Service Manual U S Boiler Company LLC P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net...

Reviews: