69
109838-01 - 5/20
X-PV
Installation, Operating & Service Manual
Appendix C
(continued)
Primary-Secondary Pumping:
Best Alternative
: U.S. Boiler offers a system by-pass kit [part number 107795-01] that addresses these
situations.
A strap on temperature sensor measures boiler inlet temperatures. This temperature signal is sent to a variable
speed pump that will ensure boiler inlet temperatures are always greater than the factory by-pass kit set point of
120oF.
Kit includes all fittings, pump, sensor and instructions.
This is an improvement over simple by-pass
piping to reduce condensation. Again this is a
fixed system. It can not adapt to variations in
temperature and flow.