Part # XXXXXXX (02/07)
Page 8
TESTING AND ADJUSTMENT
Testing
All fittings and pipe connections must be tested for
leaks. Use approved gas leak detectors, soap solution
or equivalent, checking over and around all the fittings
and pipe connections. DO NOT USE A FLAME!
Accessibility to all gas lines and fittings require that
valve panel(s) lower front panel(s), and/or oven rack(s)
be removed. It may be necessary to remove, or at least
raise and securely prop griddle(s), hot top(s), and/or top
grate(s). All parts removed, (including fasteners), should
be stored safely for re-installation.
. Be sure that all valves and thermostats are in the
“OFF” position.
2. Turn on the main gas supply valve. Light all top
section pilots.
3. Leak test all valves and fittings as described at the
beginning of this section. Correct any leaks as
required and recheck.
4. Light the oven pilot.
5. In either case, now set the oven thermostat to
maximum. Leak test all valves and fittings as
described at the beginning of this section. Correct
any leaks as required and recheck.
6. Shut off all valves and set thermostat dials to
“OFF” or lowest position. All units are tested and
adjusted at the factory, however, burners and pilots
should be checked upon installation and adjusted if
necessary.
CAUTION: Gas will flow to the top section burners
even if top section pilots are not lit. Gas will not be
interrupted. It is the responsibility of the operator
to confirm the proper ignition of each burner as it
is turned on. Should ignition fail to occur 5 seconds
after turning a burner on, turn the burner off, wait 5
minutes, and try again.
D. Make certain new piping and connections have
been made in a clean manner and have been purged
so that piping compound, chips, etc. will not clog
pilots, valves or burners. Use pipe joint compound
approved for natural and liquefied petroleum
gases.
NOTE: Gas pressure should be checked when the unit
is installed and all other equipment on the same line
is on. The operating gas pressure must be the same as
that specified on the rating plate. If necessary, pressure
adjustment may be made at the pressure regulator
supplied with the appliance.
The appliance and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of that system pressures in excess
of 1/2 PSIG (3.45kPa.)
INSTALLATION Continued
Summary of Contents for U36-6S
Page 15: ...Part XXXXXXX 02 07 Page 15 NOTES...
Page 16: ......