background image

reV: 16i

SMoGHoG

®

SHM Series Models 

6

3.5  ELECTRICAL CONNECTION

the SHM is available with various controls configurations. 

refer  to  the  section  headings  below  and  follow  the 

section instructions that best align with your specific unit. 

Multiple sections may apply to the same unit. the SHM 

customer  electrical  connections  are  located  on  the  rear 

of  the  unit  as  shown  in  figure  1B.  the  supply  voltage 

and fLa will be noted on the nameplate. the blower and 

pulse  cleaning  system  controls  are  factory  pre-wired  for 

operation. the touchscreen controls are also pre-wired for 

the integral option, but require field wiring and connections 

for the remote display enclosure option. Wiring diagrams 

for  the  various  SHM  controls,  blower  arrangement  and 

supply voltage options are available within the appendix 

of  this  manual.  note  that  the  SHM  does  not  contain 

the  main  disconnect  or  fuses  for  the  supply  power. 

electrical installation should be completed by a qualified 

professional  and  done  in  accordance  with  all  applicable 

codes and regulations.
Power cord and connection into unit will be supplied by 

the customer.
unit is available in the voltages shown below:

TABLE 1

SHM Voltage and Full Load Amps

Note: 

When making the main power connections to the 

unit, fan rotation check is not required.

 

VOLT

PH

#

BLWR

HZ

RPM

FLA

XFMR

208

3

1

50-60

3370

6.5

---

230

3

1

50-60

3370

5.7

---

240

3

1

50-60

3370

5.5

---

380

3

1

50-60

4200

6.7

---

480

3

1

50-60

4200

5.5

---

575

3

1

50-60

4200

---

6kVA

208

3

2

50-60

3370

13.5

---

230

3

2

50-60

3370

11.5

---

240

3

2

50-60

3370

11.0

---

380

3

2

50-60

4200

13.9

---

480

3

2

50-60

4200

11.0

---

575

3

2

50-60

4200

---

10kVA

208

3

3

50-60

3370

18.9

---

230

3

3

50-60

3370

16.4

---

240

3

3

50-60

3370

15.5

---

380

3

3

50-60

4200

19.1

---

480

3

3

50-60

4200

15.5

---

575

3

3

50-60

4200

---

15kVA

FOR BASIC CONTROLS ON SHM-11, SUBTRACT

0.5 AMP FROM FLA VALUES ABOVE. 

TABLE 2

Wire Diagrams

3.5.1 ELECTRICAL SUPPLY POWER

the  main  power  supply  is  connected  to  the  SHM  unit 

through  a  1˝  FNPT  coupling  located  on  the  rear  of  the 

unit shown in figure 1B. after feeding wires through the 

coupling,  terminations  are  made  on  the  main  bus  bar 

terminal for each phase and frame ground connection. the 

rear electrical panel also contains the unit circuit breakers 

and  dc  power  supply  for  the  controls  components. 

utilize  table  1  for  wire,  fuse  and  disconnect  sizing  for 

your  respective  product  model.  A  second  plugged  1˝ 

fnPt coupling is also located on the rear of the cabinet 

for  low  optional  voltage  connections  using  the  Machine 

interlock  feature  to  automate  operation.  ensure  that  the 

rear electrical panel cover is in place and secured prior to 

operating the unit. refer to the electrical wiring diagrams 

in table 2 for additional wiring information.

3.5.2 ELECTRICAL BASIC CONTROLS

the basic electrical controls consist of a thermal motor 

protection disconnect on the side of the unit. this is set 

for  the  fLa  of  the  single  blower  motor.  this  is  factory 

prewired to the blower motor. When installing this unit in 

the field the customer will connect their factory power to 

the disconnect on the line side of the thermal protector. 

the disconnect on/off will supply power to the unit and 

allow the blower on/off switch on the front of the unit to 

control the blower. inside the door on the front of the unit 

there is a blower speed adjustment. this will control the 

speed of the blower from off to full speed. this should 

be  adjusted  by  the  customer  to  meet  their  process 

requirements.

Descrip�on of Wire Diagram 

Appendix

Basic Controls 

A1

Remote Panel Basic Controls

A2

One Blower & Controls

A3

Two Blower & Controls

A4

Three Blower & Controls

A5

Remote Panel Touch Controls

A6

One Blower & Remote Controls

A7

Two Blower & Remote Controls

A8

Three Blower & Remote Controls

A9

Transformer 575:480

A10

Summary of Contents for SMOGHOG SHM-11C

Page 1: ...Model SHM 11C Shown SMOGHOG Media Mist Collector l Models SHM C SHM F OWNER S MANUAL ...

Page 2: ... following information available when contacting UAS UAS ORDER _________________________________________________________________ UNIT MODEL ________________________________________________________________ UNIT SERIAL _________________________________________________________________ SYSTEM ACCESSORIES ______________________________________________________________________________ ___________________...

Page 3: ...on 8 3 6 1 Installation Procedure for After Filters 8 3 6 1 1 Hold Down 8 3 6 1 2 Enclosed 10 3 7 Drains 10 4 UNIT OPERATION 10 4 1 Start up 10 4 2 System Operation 10 4 2 1 Airflow Adjustment Using Manual Speed Control 10 4 2 2 Airflow Adjustment Using Auto Flow Control 10 4 3 Touchscreen Operation 11 4 3 1 Start Up And Home Screen 11 4 3 2 Standard Format 11 4 3 3 Basic Screens 12 4 3 4 Auto Flo...

Page 4: ...terials and vapors such as gasoline away from the unit The unit should be inspected frequently and contaminants removed to prevent excessive accumulation which may result in flash over or fire damage Operate only in a safe and serviceable condition Operating temperature to the air stream should not exceed 120 F 49 C DANGER WARNING WARNING CAUTION C A U T I O N This is the safety alert symbol This ...

Page 5: ...re assistance in the installation startup operation maintenance or troubleshooting of your air cleaning equipment contact your local UAS sales representative 2 1 SMOGHOG NOMENCLATURE SMOGHOG oil mist air cleaners are available in a variety of configurations and sizes The model string for each given unit represents the base configuration The model number completely identifies the design and can be ...

Page 6: ...REV 16I SMOGHOG SHM Series Models 2 FIGURE 1B SHM Equipment Description 61 10113 FIGURE 1A SHM Equipment Description ...

Page 7: ... the unit in each corner Do not lift the unit by placing lift truck forks through the legs on the underside of the unit Filter Elements Stage 1 Mist Stop fine fiber aluminum mesh Stage 2 Primary coalescer featuring Peach Saturated Depth Coalescing Technology or fiberglass bag Blower Cabinet Most units will have a blower cabinet where the motorized impeller style blower is housed as well as the ele...

Page 8: ...eering drawings of your specific equipment and options will be provided These and all available documentation for your system should be thoroughly reviewed prior to beginning any installation work This includes the unit and electrical controls Ensure to leave an appropriate amount of room around your unit to allow for maintenance and servicing A minimum of 2 1 2 feet 0 76 m of clearance is recomme...

Page 9: ...iguration Secure the unit at all four corners using the standard unit feet or extension leg foot pads At least one of the two holes per foot pad on the extension legs should be secured See Figure 1 for reference Ceiling mounted units are suspended by means of 1 2 threaded rods item 1 in Figure 3 which run through weld nuts item 2 in Figure 3 in the top corners of the units Refer to Figure 2 for we...

Page 10: ...LS ON SHM 11 SUBTRACT 0 5 AMP FROM FLA VALUES ABOVE TABLE 2 Wire Diagrams 3 5 1 ELECTRICAL SUPPLY POWER The main power supply is connected to the SHM unit through a 1 FNPT coupling located on the rear of the unit shown in Figure 1B After feeding wires through the coupling terminations are made on the main bus bar terminal for each phase and frame ground connection The rear electrical panel also co...

Page 11: ...REV 16I SMOGHOG SHM Series Models 7 61 10126 Figure 4 Remote Panel Touchscreen Connection ...

Page 12: ... INTERLOCK DRY CONTACT The customer has the option to control the SHM On Off operation with the oil mist generating equipment or process This will allow the operator to control the SHM with a dry contact off another piece of equipment Refer to the wiring diagrams in the appendix for wiring of this option and to Section 4 for Machine Interlock set up on the touchscreen Wiring will be terminated to ...

Page 13: ...REV 16I SMOGHOG SHM Series Models 9 61 10115 Figure 5B SHM Filter Removal Installation Figure 5A SHM Filter Removal Installation ...

Page 14: ... other equipment will need to be engaged as well 7 Verify performance of the system by measuring airflow or evaluating capture at each collection point It is recommended to record baseline performance parameters so the system can be reset in case of an upset condition or system change The recorded data should include the static pressure at each collection hood system amperage draw and filter press...

Page 15: ...After Filter monitoring or unique screens required for a special application These screens are based on customer order and loaded at the factory Figure 6 4 3 2 Standard Format The icon key Table 3 outlines the various icons that are used on the screen for various reasons and may indicate status or conditions The Home Settings and Information icons are shown at the bottom of most screens and will t...

Page 16: ...n arrows The second method of airflow adjustment is to touch the box that shows the percentage of the airflow A number pad will be shown in a pop up screen You can enter any number between 20 and 100 This will correspond to the percentage of blower capability The blower is capable of 4 200 RPM at 100 3150 RPM for 75 2100 RPM for 50 and 1050 RPM for 20 These number are approximate and may display s...

Page 17: ...are not password protected To select one of the items just touch the box with the item you want to make a change too The Locked Settings selection will allow the operator to select options of the system One option is Machine Interlock With Machine Interlock the operator can allow another device CNC machine center plasma table or weld machine to turn the SHM on when the primary device is in operati...

Page 18: ...ocked Settings group on the Customer settings screen The Auto Flow is an option that is selected at order time and loaded into the SHM at the factory The Auto Flow Settings will allow the unit to maintain a precise operating point based on a desired air volume The operator will select an air volume setting in the airflow set point box using the up down arrows or the selection box If the screen is ...

Page 19: ...r hose This filter can be replaced if contaminants become impossible to remove or due to excessive wear Always wear proper PPE including goggles dust mask and work gloves when installing or replacing filter elements Oil accumulated on the filter elements can result in irritation of the lungs skin and or eyes Remove used filter elements from the collector and dispose of properly in accordance with ...

Page 20: ... into place prior to hanging the individual bags loops For units that are two filters deep be sure to push the first filter all way toward the back of the primary filter cabinet until it contacts the stop Reference balloon 1 in Figure 5A The hanging rod is to be inserted through each filter loop and hung from a bracket on each side of the primary filter cabinet Work from the back of the cabinet to...

Page 21: ...ker Open rear panel on unit and switch breaker if necessary Loose or disconnected wires Inves gate wiring in the rear panel Disconnect is switched to OFF posi on Switch disconnect to ON posi on Improper source power Refer to data plate to verify required input power Screen Displayed Warning Possible Causes Recommended Solu ons Filter Cau on Filter is approaching max life Replace filter s soon Yello...

Page 22: ...ILTER HEPA 99 97 0 3 μm 5 33 10117 ALUMINUM MESH PRE FILTER 6 33 10128 COALESCING CARTRIDGE FILTER 9 OD PEACH MEDIA 33 LENGTH 3 33 10129 CABINET AFTER FILTER MICROGUARD O M 95 0 3 μm 7 39 10008 0006 CONTROLS PANEL LATCH 10mm HEX 8 39 10058 FLUSH MOUNT FILTER CABINET LATCH NOT SHOWN 42 0168 FILTER CABINET GASKET NOT SHOWN 42 1549 SEALANT NOT SHOWN 20 10413 PRESSURE TRANSDUCER NOT SHOWN 38 10145 BUL...

Page 23: ...REV 16I SMOGHOG SHM Series Models 19 Figure 6 SHM Replacement Parts SHM 11C SHM 11F ...

Page 24: ...REV 16I SMOGHOG SHM Series Models 20 APPENDIX WIRING DIAGRAMS BASIC CONTROLS A1 04 001682 ...

Page 25: ...REV 16I SMOGHOG SHM Series Models 21 A2 REMOTE PANEL BASIC CONTROLS 04 001799 ...

Page 26: ...REV 16I SMOGHOG SHM Series Models 22 A3 ONE BLOWER AND CONTROLS 04 001695 ...

Page 27: ...REV 16I SMOGHOG SHM Series Models 23 A4 TWO BLOWER AND CONTROLS 04 001696 ...

Page 28: ...REV 16I SMOGHOG SHM Series Models 24 A5 THREE BLOWER AND CONTROLS 04 001697 ...

Page 29: ...REV 16I SMOGHOG SHM Series Models 25 A6 REMOTE PANEL TOUCH CONTROLS 04 001802 ...

Page 30: ...REV 16I SMOGHOG SHM Series Models 26 A7 ONE BLOWER AND REMOTE CONTROLS 04 001798 ...

Page 31: ...REV 16I SMOGHOG SHM Series Models 27 A8 TWO BLOWER AND REMOTE CONTROLS 04 001797 ...

Page 32: ...REV 16I SMOGHOG SHM Series Models 28 A9 THREE BLOWER AND REMOTE CONTROLS 04 001796 ...

Page 33: ...REV 16I SMOGHOG SHM Series Models 29 A10 575 480 TRANSFORMER 04 001717 ...

Page 34: ...This page intentionally left blank ...

Page 35: ...This page intentionally left blank ...

Page 36: ...ranty as to goods manufactured or supplied by others This warranty is subject to any limitations in UAS quotation and may not be modified except by a written instrument signed by the President or Vice President of Sales of UAS THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER WRITTEN ORALOR IMPLIED INCLUDINGANYIMPLIED WARRANTYOF MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE...

Reviews: