reV: 16i
SMoGHoG
®
SHM Series Models
3
3. INSTALLATION
3.1 INSPECTION AND OFF LOADING
as soon as your equipment arrives, it should be carefully
inspected to make certain that it is in good condition and
that all items listed on the packing list have been received.
even though the items are carefully loaded and tied
down at the time of shipment, it is possible for them to be
damaged or become dislodged in transit.
report any damage(s) and/or shortage(s) immediately. it
becomes increasingly difficult for either the carrier or the
supplier to assume responsibility for any damages after
too much time has elapsed. check all loads separately.
the following steps should be taken immediately
upon receipt of your shipment; this will assure and
expedite claim payments and replacement of missing or
damaged items.
1. Begin your inspection of the shipment Before it is
unloaded.
2. Check for damage to any exposed items, particularly at
the tie‐down locations.
3. Photograph any damage. do this Before the
equipment is unloaded.
4. check Bill of Lading quantities and description. note
any discrepancies on all copies of the Bill of Lading
and have them acknowledged (the carrier should sign).
damage description should also be written directly on,
or attached to, the Bill of Lading, and should also be
signed by the driver.
contact the insurance company and the shipper at once
so that damages and/or shortages can be corrected and a
claim can be filed without delay.
TIP OVER HAZARD
Lift the SHM unit and components by the packing
skids or on the lifting eyes located on the top of the
unit in each corner. do not lift the unit by placing
lift truck forks through the legs on the underside of
the unit.
Filter Elements
Stage 1: Mist-Stop fine fiber aluminum mesh
Stage 2: Primary coalescer featuring PeacH
®
Saturated
depth coalescing technology - or - fiberglass bag
Blower Cabinet
Most units will have a blower cabinet where the motorized
impeller style blower is housed, as well as the electrical
controls.
2.3 PRINCIPAL OF OPERATION
the purpose of the SHM is to collect fugitive mist generated
by various industrial processes during operation. the
collected contaminate is drained off of the coalescing
filters into the sump below or directly back into the
machine. the sump is attached to a drain system of the
customers choice for recycling or disposal, or emptied
manually at regular intervals.
do not let the oil level in the sump reach the height of
the air inlet opening.
Differential Pressure
differential pressure, also referred to as pressure drop
(Δ P), is an indication of the resistance to airflow across
the filter elements. differential pressure is commonly
measured in inches of water column (W.c.) or Pascals
(Pa). it is normal for the differential pressure to increase as
the collector operates. any sudden increase or decrease
in differential pressure may indicate a problem in the
collector (blinded filters, leaks or other cause) that requires
immediate attention. See trouble shooting guide in Section
6 for assistance.
the operating differential pressure displayed on the
unit will typically run between 0.5 to 4 in. W.c. (124 to 995
Pa) for a fiberglass Bag filter, and between 0.75 to 4 in.
W.c. (187 to 995 Pa) for a coalescing cartridge filter. the
expected pressure range for the after-filters is 0.5 to 3.0
in. W.c. (124 to 746 Pa).
!
D A N G E R
CAUTION
Summary of Contents for SMOGHOG SHM-C Series
Page 1: ...Model SHM 11C Shown SMOGHOG Media Mist Collector l Models SHM C SHM F OWNER S MANUAL...
Page 11: ...REV 16I SMOGHOG SHM Series Models 7 61 10126 Figure 4 Remote Panel Touchscreen Connection...
Page 23: ...REV 16I SMOGHOG SHM Series Models 19 Figure 6 SHM Replacement Parts SHM 11C SHM 11F...
Page 24: ...REV 16I SMOGHOG SHM Series Models 20 APPENDIX WIRING DIAGRAMS BASIC CONTROLS A1 04 001682...
Page 25: ...REV 16I SMOGHOG SHM Series Models 21 A2 REMOTE PANEL BASIC CONTROLS 04 001799...
Page 26: ...REV 16I SMOGHOG SHM Series Models 22 A3 ONE BLOWER AND CONTROLS 04 001695...
Page 27: ...REV 16I SMOGHOG SHM Series Models 23 A4 TWO BLOWER AND CONTROLS 04 001696...
Page 28: ...REV 16I SMOGHOG SHM Series Models 24 A5 THREE BLOWER AND CONTROLS 04 001697...
Page 29: ...REV 16I SMOGHOG SHM Series Models 25 A6 REMOTE PANEL TOUCH CONTROLS 04 001802...
Page 30: ...REV 16I SMOGHOG SHM Series Models 26 A7 ONE BLOWER AND REMOTE CONTROLS 04 001798...
Page 31: ...REV 16I SMOGHOG SHM Series Models 27 A8 TWO BLOWER AND REMOTE CONTROLS 04 001797...
Page 32: ...REV 16I SMOGHOG SHM Series Models 28 A9 THREE BLOWER AND REMOTE CONTROLS 04 001796...
Page 33: ...REV 16I SMOGHOG SHM Series Models 29 A10 575 480 TRANSFORMER 04 001717...
Page 34: ...This page intentionally left blank...