Ubiflux W300(+) / W400(+) / W450+
7
6
Ubiflux W300(+) / W400(+) / W450(+)
Version
Chapter 3
Ubiflux W400
Supply voltage [V/Hz]
230/50
Protection degree
IP30
Dimensions (w x h x d) [mm]
675 x 765 x 564
Duct diameter [mm]
Ø180
External diameter condensate discharge [mm]
Ø32
Weight [kg]
38
Filter class
G3 (F7 optional for supply)
Fan setting (factory setting)
1
2
3
Ventilation capacity [m
3
/h]
50
100
200
300
Permissible resistance ducts system [Pa]
3 - 6
6 - 20
25 - 49
56 - 178
Rated power (excl. preheater)[W]
8,6
9.5 - 15
29 - 40
72 - 98
Rated current (excl. preheater)[AA]
0,10
0.12 - 0.14
0.24 - 0.31
0.51 - 0.7
Max. rated current (with preheater switched on) [A]
6
Cos φ
0,38
0.45 - 0.40
0.56 - 0.58
0.60 - 0.61
Sound power Ubiflux W400
Ventilation capacity [m
3
/h]
100
200
225
300
400
Sound power
level Lw (A)
Static pressure [Pa]
9
40
38
80
47
100
84
175 240 150 225
Housing emission [dB(A)
28.5 31.5 39.5 40.5 42.5 46.5 50.0 52.0 53.0 53.5 56.0
Duct “from dwelling” [dB(A)]
30.5 33.5 45.5 47.0 47.5 49.0 55.5 56.0 57.0 58.0 59.0
Duct “to dwelling” [dB(A)]
41.5 46.5 56.0 58.0 59.5 61.5 65.0 67.5 68.5 69.5 70.5
In practice, the value may deviate 1 dB(A) as a result of measuring tolerances