35
Ubiflux W300(+) / W400(+) / W450(+)
Ubiflux W300(+) / W400(+) / W450+
36
11.3 Couple through eBus contact;
all appliances equal air flow rate
Electric connections accessories
Chapter 11
A
=
Multiple switch
B
=
2-pole connector
M
=
Ubiflux (Master)
C1 t/m C* =
Ubiflux (Slave); couple
not more than 10 appliances through Ebus
All Ubiflux models have the same air flow rates as the Ubiflux
set as “Master”.
A maximum of 10 appliances
(1 9 Slave max.)
For M (Master):
Set parameter 9 to 0 (= factory setting).
Display shows ventilation mode 1, 2 or 3.
For C1 (Slave1):
set parameter 9 to 1 (= Slave 1).
Display always shows ventilation
mode □.
Important:
Because of polarity sensitivity, always connect contacts X1-1 to X1-1 and contacts X1-2 to X1-2. Never connect
X1-1 and X1-2.
230V
50Hz
230V
50Hz
230V
50Hz
For C2 (Slave2):
Set parameter 9 to 2 (= Slave 2).
Display always shows ventilation
mode □.
Step
nr.
Description
Factory
setting
Range
8
Communica
-
tion type
eBus
0t ( = Opentherm)
eBus
9
eBus address
0
0 = master
1- 9 = slave 1 - 9
11.4 Connection RH (huminity)- sensor
Step
nr.
Description
Factory
setting
Range
30 Activating
RH-sensor
OFF
OFF
= not active
ON
= active
31 Sensitivity
0
-2
most ensitive
-1
↑
0
default setting RH-sensor
+1
↓
+2
least sensitive
E
A = Ubiflux
B = Control board
C = RH (huminity) - sensor
D = Cable supplied with RH sensor
E = Duct from dwelling
C1 = brown
C2 = blue
C3 = green/yellow
230V
50Hz