background image

11.1.2 Connecting wireless remote control (without filter indication)

 

A = Ubiflux Vigor appliance (For example a Ubiflux Vigor appliance type 4-0)
B = Receiver for wireless remote control
C = Transmitter with 4 settings (for example kitchen)
D = Transmitter with 2 settings (for example bathroom)
E = Any additional 2- or 4-settings transmitters (maximum of 6 transmitters can be signed on to 1 receiver)
F = Modular cable: Note: For the modular cable that is used, the “tab” of both modular connectors must be mounted facing

the mark on the modular cable. Wire colors C1 - C6 may vary dependent on the type of modular cable used.

 

Ubiflux Vigor W400 615912-D

Ubbink / 39

Summary of Contents for Ubiflux W400 +

Page 1: ...INSTALLATION REGULATIONS Ubiflux Vigor W400 English...

Page 2: ......

Page 3: ...may only switch the appliance on or off but only if supervised or if they have received clear instructions on the safe use of the appliance and understand the possible dangers on the condition that t...

Page 4: ...liance 24 7 1 Switching appliance on and off 24 7 2 Setting the air flow 24 7 3 Other settings for installer 25 7 4 Factory settings 25 8 Fault 26 8 1 Fault analysis 26 8 2 Display Codes 26 9 Maintena...

Page 5: ...on The delivery size of the heat recovery appliance type Ubiflux Vigor W400 consists of the following components 1 Heat recovery appliance 2 Wall mounting bracket consisting of 1x mounting bracket 2 x...

Page 6: ...e in two types the Ubiflux Vigor W400 The Ubiflux Vigor W400 Plus The Ubiflux Vigor W400 Plus has compared with standard Ubiflux Vigor W400 an extra pcb giving this more functions connection possibili...

Page 7: ...r W 7 6 7 8 10 3 11 5 23 0 31 4 62 5 87 0 126 6 160 0 Rated current excl preheater A 0 12 0 12 0 15 0 16 0 25 0 33 0 58 0 77 1 01 1 24 Max rated current incl preheater switched on A 6 Cos j 0 270 0 27...

Page 8: ...left hand version the warm connections from dwelling 3 and to dwelling 1 are on the left hand side of the appliance the condensate discharge is then mounted at the right hand opening below the applia...

Page 9: ...s Diameter of all collars is 180 mm 1 To dwelling 2 To outside 3 From dwelling 4 From outside 5 Electrical connections 6 Siphon connection 7 Exhaust air filter 8 Supply air filter 9 Mounting Ubiflux V...

Page 10: ...SB connector X13 13 Motor bypass valve 3 Service connector 14 Discharge filter 4 LED indicator 15 Bypass valve 5 Maximum protection preheater 16 Power cable 230 volt 6 Preheater 17 Relay output X19 7...

Page 11: ...ly cooler outside air The warm air in the dwelling is then replaced as much as possible by cooler outside air The bypass valve opens and closes automatically when a number of conditions are met see ta...

Page 12: ...with more connections for various applications This extra control board is located in a plastic housing behind the existing control board on top of the appliance It is also possible to remove the ent...

Page 13: ...pliance must be mounted to a solid wall with a minimum mass of 170 kg m2 A gypsum block or metal stud wall does not suffice Additional measures such as double panelling or extra studs are required in...

Page 14: ...ended to use a 32 mm connection with gasket HT DN32 not supplied with the appliance so that the siphon can be cleaned easily in the future Important During assembly always apply a lubricant such as ac...

Page 15: ...pe The outside air supply should be arranged from the shadowed side of the dwelling preferably from the wall or an overhang The discharge duct must be fed through the roof boarding in such a way that...

Page 16: ...iple switch The multiple switch not supplied with the appliance is connected to the modular connector type RJ12 connector X14 that is placed on the rear of the display cap of the appliance Exploded vi...

Page 17: ...bus red connector X15 can for example be used for coupling appliances Coupling appliances using external Bus page 18 The function of this connector can be adjusted using step number 14 1 to 14 4 in t...

Page 18: ...e cable M Master appliance For example a Ubiflux Vigor appliance type 4 0 S1 S2 Slave appliances For example a Ubiflux Vigor appliance type 4 0 connect max of 10 appliances via external Bus All Ubiflu...

Page 19: ...cted ventilation flow rate In this example the active ventilation flow rate is 100 m3 h 5 Active control 6 Filter message only displayed if applicable 7 Fault only displayed if applicable 8 Access to...

Page 20: ...menu you can change the various values For all setting values of standard appliance Setting values standard appliance page 51 The Plus version of the appliance has various setting values Setting valu...

Page 21: ...ep number 15 4 to yes Control using humidity sensor Control using CO2 sensor Control using demand driven ventilation Break contact active or make contact active This appliance is set as Master applian...

Page 22: ...no Symbol on display Description 4 Internet connection Network connection Signal strength USB connection active 5 11 07 Current set time of the device 6 02 01 2020 Current date Ubiflux Vigor W400 6159...

Page 23: ...button takes you back 1 step in the menu Briefly press the display shorter than 5 seconds to switch on the display backlight without changing anything in the menu the display lights up for 2 minutes B...

Page 24: ...rom the appliance by pulling the power plug 7 2 Setting the air flow Good ventilation contributes to healthy air in the home optimal comfort and the proper functioning of the installation The air flow...

Page 25: ...functioning of the appliance changes of settings not described here require consultation with Ubbink NV Incorrect settings may seriously affect the proper performance of the appliance 7 4 Factory set...

Page 26: ...a fault cannot be solved please contact the installer 1 Requested supply flow rate is not reached Locking fault When the appliance detects a locking fault it will no longer work With a locking fault t...

Page 27: ...weather or when there is no air from below the tiles take the voltage from the appliance and replace air temperature sensor NTC E105 E1100 Supply fan defective general message Appliance goes to standb...

Page 28: ...exhaust fan and supply fan E123 E2400 External ModBus fault general fault message Operation via Modbus does not work Check cabling of accessories replace if damaged Check accessories replace if defec...

Page 29: ...een followed and confirmed then the filter wizard is closed by pressing the Home button and the display then returns to the main screen the filter message is reset and the filter message now disappear...

Page 30: ...9 2 Maintenance siphon Cleaning the siphon Every year the siphon must be disconnected and cleaned For example a Ubiflux Vigor appliance type 4 0 Ubiflux Vigor W400 615912 D...

Page 31: ...changer internal preheater and fans Dependent on the conditions this must done about once every three years 1 Remove the power supply by pulling out the plug Open the filter door 2 Remove the two filt...

Page 32: ...am parts in the appliance 5 Wash the heat exchanger with hot water max 45 C and a regular detergent Then rinse the exchanger with hot water 6 Take EPS assembly with which the fan is inserted into the...

Page 33: ...f a revolution in the appliance 8 Tilt the fan in such a way that this can be taken out of the EPS assembly disconnect both fan cables from the fan 9 Now take the fan out of the appliance Ubiflux Vigo...

Page 34: ...hen doing so take care that the EPS parts and rails in the appliance are not damaged which could otherwise leads to internal leaks in the appliance Take care when returning the heat exchanger that the...

Page 35: ...10 Electrical diagram Ubiflux Vigor W400 615912 D Ubbink 35...

Page 36: ...ilation 2 0 option X14 Analog output 0 or 10 V 19 Plus pcb option X15 Analog output 2 0 or 10 V 20 Connection on ModBus system option X16 NTC 10K 21 X12 is Jumper terminating resistance 120 W ModBus r...

Page 37: ...ved in order to gain access to this modular connector Plus version page 12 Depending on the type of multiple switch that is connected one can use either an RJ11 or RJ12 plug It is best to use a 4 way...

Page 38: ...Vigor appliance type 4 0 B 4 way switch with filter indication C Modular cable Note For the modular cable that is used the tab of both modular connectors must be mounted facing the mark on the modular...

Page 39: ...ple kitchen D Transmitter with 2 settings for example bathroom E Any additional 2 or 4 settings transmitters maximum of 6 transmitters can be signed on to 1 receiver F Modular cable Note For the modul...

Page 40: ...Multiple switch with filter indication B2 Extra multi switch with filter indication C Splitter D Modular cable Note For the modular cable that is used the tab of both modular connectors must be mount...

Page 41: ...ter indication C Receiver for wireless remote control D Transmitter with 2 settings or 4 settings E Splitter F Modular cable Note For the modular cable that is used the tab of both modular connectors...

Page 42: ...onnecting Air Control A Ubiflux Vigor appliance B Air Control option C Two core control cables D Green two pole screw connector E Position green eBus connector to rear of control Ubiflux Vigor W400 61...

Page 43: ...ance 2 Basis pcb 3 Cover 4 The cable that comes with RH cable 5 RH humidity sensor 6 Duct from dwelling To switch on and set the sensitivity of the humidity sensor go to step number 7 1 and 7 2 in the...

Page 44: ...s D CO2 sensor s connect a maximum of 4 E Connection X17 eBus and X18 24V on Ubiflux Vigor appliance For switching the CO2 sensor s on and off select the right setting at step number 6 1 in the settin...

Page 45: ...itch of course remains a possibility as well For further information regarding setting operating and connecting demand driven ventilation 2 0 refer to the installation instructions supplied with the d...

Page 46: ...1 brown C2 blue C3 green yellow C4 black C5 white 2 Maximum safety with manual reset 3 2 pole eBus connection X17 on appliance 4 Temperature sensor 5 PCB type UVP1 6 Airflow direction 7 Dipswitch sett...

Page 47: ...wn C2 blue C3 green yellow C4 black C5 white 2 Maximum safety with manual reset 3 2 pole eBus connection X17 on appliance 4 Temperature sensor 5 PCB type UVP1 6 Airflow direction 7 Dipswitch setting p...

Page 48: ...rature sensor to no 1 and no 2 of the 2 pole connectorX 16 A Min temperature B Max temperature I To dwelling II To outside III From dwelling IV From outside When using a geo heat exchanger parameter 1...

Page 49: ...ber the year of production and the name of the part N B Appliance type serial number and year of production are stated on the identification plate behind the plastic front panel on the appliance Examp...

Page 50: ...ly applicable with Plus version 0883246 9 Mains plug and cable 230 V 0883261 10 Internal preheater incl maximum security 0883263 11 Mounting bracket 0121203 12 Temperature sensor NTC 10K 0704637 13 Co...

Page 51: ...4 Air flow rate setting 3 300 m h Adjustable between 50 m h and 400 m h not lower than step no 1 3 1 5 Imbalance permissible Yes Yes No 1 6 Imbalance Open fireplace 0 0 20 1 7 Offset supply 0 15 15 fa...

Page 52: ...4 Min PPM eBus CO2 sensor 2 400 PPM 6 5 Max PPM eBus CO2 sensor 2 1200 PPM 6 6 Min PPM eBus CO2 sensor 3 400 PPM 6 7 Max PPM eBus CO2 sensor 3 1200 PPM 6 8 Min PPM eBus CO2 sensor 4 400 PPM 6 9 Max PP...

Page 53: ...rian Latvian 15 2 Date format dd mm yyyy dd mm yyyy mm dd yyyy 15 3 Date 15 4 Time format 24h 12h 24h 15 5 Time 15 8 Display No Yes No Display half an hour active as multiple switch when yes is select...

Page 54: ...an off Fan runs at absolute minimum Fan at setting 1 Fan at setting 2 Fan at setting 3 Fan at step 0 Fan according to multiple switch Fan runs at absolute maximum No exhaust fan control 9 5 Make or br...

Page 55: ...minimum voltage input 2 0V 0V 10V Connector X 13 10 6 maximum voltage input 2 10V 0V 10V 11 Geo heat exchanger 11 1 Switching on and off Off On Off 11 2 Switch temperature 1 5 C 0 0 C 10 0 C 11 3 Swi...

Page 56: ...ype Ubiflux Vigor W400 Ubiflux Vigor W400 Plus The product described above complies with the following directives 2014 35 EU low voltage directive 2014 30 EU EMC directive RoHS 2011 65 EU substances d...

Page 57: ...entilation appliance with heat recovery Fan EC fan with infinitely variable control Type of heat exchanger Recuperative plastic cross counterflow heat exchanger Thermal efficiency 92 Maximum flow rate...

Page 58: ...sification from 1 January 2016 SEC class Average climate zone SEC in kWh m a A Most efficient SEC 42 A 42 SEC 34 B 34 SEC 26 C 26 SEC 23 D 23 SEC 20 G Least efficient 20 SEC 10 Ubiflux Vigor W400 6159...

Page 59: ...ling Sustainable materials are used in the manufacture of this appliance The packaging should be disposed of in a responsible manner and in accordance with governmental regulations Ubiflux Vigor W400...

Page 60: ......

Page 61: ...Jan Samijnstraat 9 B 9050 Gentbrugge Tel 32 0 9 237 11 00 www ubbink be info ubbink be Ubbink UK Ltd Unit 2 Redbourne Park Liliput Road Brackmills Ind Est Northampton NN4 7DT T 44 0 1604 433000 F 44 0...

Reviews: