Doc. 85588U - Rev. 22/10/2020
USER MANUAL
USER MANUAL
EN
EN
Drw. 32367/h
10/54
6. TECHNICAL FEATURES
•
Class D control panel (control panel with detectors) according to prEN 12101-9:2008.
•
Designed for use in class 1 environments, according to the classification contained in EN 12101-10 (clean, indoor environ
-
ments, temperature –5°C to +40°C).
•
Mains power supply (for secondary power supply): 100-250 Vac, 50 – 60Hz. Nominal power consumption: 108W (C-SV 4A) -
202W (C-SV 8A). Standby power consumption: less than 2W (C-SV 4A) – less than 9W (C-SV 8A).
•
Secondary power supply from lead batteries: 12V, 4,5 Ah, in series or lead batteries: 12V, 4 Ah, in series. Maximum interrup
-
tion time when switching between the two power supply sources: 0,2 s.
•
Maximum current required of the batteries, when the primary power supply is unavailable: 4,05 A or 8,05 A depending on
the version.
•
Motor outputs: 24 Vdc +/- 25%. 2 lines – max 2A or 4A each for C-SV 4A and C-SV 8A respectively.
•
Visual signals: n° 3 LEDs: GREEN, YELLOW, RED, on board, for diagnostics.
OUTPUTS:
•
N° 2 X 24 Vdc polarity inversion motor outputs, each with a maximum load of 2A or 4A for C-SV 4A and C-SV 8A respectively. 2
natural ventilation zones, 1 smoke extraction zone.
•
N° 1 x 24 Vdc auxiliary output. This output is disconnected automatically if a blackout or an emergency occurs. In standby mode,
you must subtract the power consumption of this output from the available power on the two motor outputs.
•
N° 1 output with clean (NC/NO) switching contact, to display emergencies (EM. SIG.).
•
N° 1 output with clean (NC/NO) switching contact, to display emergency closing (EM. CL. SIG.);
•
N° 1 output with clean (NC/NO) switching contact, to display anomalies/faults (AUX. SIG.).
INPUTS:
•
Input for smoke sensors (up to 10 sensors).
•
Input for emergency push buttons (up to 10 push buttons).
•
Input for emergency signal from any external alarm system.
•
Input for emergency closing command.
•
AUX1 input driven by an external voltage (24 Vdc +/- 25%) for the activation of EMERGENCY INTERLOCK command (by default,
the input is disabled).
•
2 inputs for manual control of the 2 natural ventilation zones.
•
Thermostat input, 1 weather management zone.
•
Inputs for wind, rain and CO2 sensors, 1 weather management zone.
•
Input for disabling weather functions (thermostat, wind, rain, CO2).
ITEMS INCLUDED:
•
2 lead batteries: 12 V, 4,5 Ah (*) or 2 lead batteries: 12 V, 4 Ah (*) (LxHxD: mm. 90 x 100 x 70 – Code 40911V);
•
Extractable input / output connectors for easy wiring.
(* )If the batteries are not supplied by UCS, follow the connection diagram on page 49.
Charging time: for 100% discharged batteries, maximum 10 hours.