If used, the EXT AL input must be connected to one of more normally closed contacts 
(usually relays), put in series with one another, and with a single 10 kOhm resistor po

-

sitioned at the end of the line.
If not used, the input must be terminated with a 10 kOhm resistor (see diagram 6 on 
page 51).
Opening of one or more contact(s) (such as breaking of the cable) has the same effect 
as pushing the emergency button.
The external alarm input can also be connected to the NC contact on the EM SIG output for another C-SV control unit, if you 
want an emergency status of the latter to be propagated to the control panel involved (see diagram 11 on page 53).

8.3.1 Emergency

8.3 Commands for smoke extraction

The control unit can enter in emergency mode following:

• 

Signal from a Smoke sensor

• 

Holding the Emergency Open Button (NC contact) down for at least 0,5 seconds (filtering necessary to reduce the risk of false 
alarms).

• 

Receiving of an alarm from an external source via the EXT AL terminal. The control unit can be connected, for example, to an 
external fire detection system.

When the control unit is in emergency mode, the red LED stays on and the manual, weather, thermostat and CO2 sensor functions 

are disabled. The control unit sends the motors an open command for 3 minutes. If the 

“deadlock”

 

function is enabled (default 

setting), the command is repeated with 2 minute pauses between each repetition, for a total time of 30 minutes.
In solenoid valve piloting mode the times change: the command only lasts 3 seconds and is repeated at 10 second intervals, for a 
total time of two minutes.
Once the conditions that caused the alarm cease, the control unit stays in emergency status until a reset command is given.

8.3.2 EM SIG

8.3.3 EM CL SIG

8.3.4 AUX SIG

This is a clean contact output for signalling an alarm status of the control unit to external de

-

vices. When the control unit goes into alarm mode (due to an emergency signal coming from 
smoke sensors, the emergency button, or an external source), the contact switches as shown 
in diagram 9 on page 52. 
The contact stays in the switched state until the alarm ceases, and the control unit is reset.

It works exactly like EM SIG, but by default it is activated only in the EMERGENCY CLOSING 
status  signalling  the  intervention  of  the  Fire  Brigade  or  authorized  personnel  on  EM  CL 

command.

On the other hand, if the control unit is configured in INTERLOCK SLAVE mode (see dip-switch 
configuration par. 8.2), the output behaves as an exact copy of the EM SIG output, so that the 
control unit has two separate clean contacts which signal the emergency status.

Clean contact switching NC to NO in case of faults.

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Summary of Contents for C-SV 4A

Page 1: ...roup it www ultra exgroup it ucs www ultra excontrolsystems com Doc 85588U Rev 22 10 2020 Drw Dis 32367 h C SV 4A 8A C SV IB 4A 8A SMOKE EXTRACTION WEATHER CONTROL UNIT CENTRALE EVACUAZIONE FUMI METEO...

Page 2: ......

Page 3: ...USE 15 8 1 Commands and signals 15 8 2 Initial configuration 17 8 3 Commands for smoke extraction 18 8 3 1 Emergency 18 8 3 2 EM SIG 18 8 3 3 EM CL SIG 18 8 3 4 AUX SIG 18 8 3 5 Emergency interlock sy...

Page 4: ...n cables and or of the damaged devices or that don t work properly please contact the authorized service centre Incorrect or improper installation may cause the system to malfunction and or result in...

Page 5: ...areas at risk of explosions In case of damage or malfunction the control units must not be used until the Customer Care Technical Service has repaired it The original configuration of the control unit...

Page 6: ...wed by everyone dealing with this product The company is not to be held responsible for damage to property or accidents to people which might occur if the above men tioned warnings are not observed In...

Page 7: ...teries 3 Electronic board 4 Power supply connection terminal 5 Cabinet closing system 6 Earthing connection 7 Integrated emergency push button 8 Manual opening push button panel for natural ventilatio...

Page 8: ...rs Smoke extraction opening occurs after the enabling of smoke detectors emergency push buttons fire control units or BMS building management system systems The emergency push buttons are equipped wit...

Page 9: ...Doc 85588U Rev 22 10 2020 USER MANUAL USER MANUAL EN EN Drw 32367 h 9 54 1 9 9 10 10 10 10 1 5 6 7 8 9 9 4 3 11 FIRE ALARM SYSTEM or BMS 2 2...

Page 10: ...liary output This output is disconnected automatically if a blackout or an emergency occurs In standby mode you must subtract the power consumption of this output from the available power on the two m...

Page 11: ...ll the position of the fixing holes Drill the wall and fix the box Choose adequately the fixing system according to the wall type to which the control unit is fixed Remove plate B from box C to gain a...

Page 12: ...4 Reposition plate B inside box C For C SV IB 4A 8A version reposition connectors D of the push button panel and emergency push button panel Reposition earth cable A on the control unit panel 5 C SV 4...

Page 13: ...re suitable for wires with a 0 5 to 1 5 sq mm section 20 to 16 AWG See the ELECTRICAL CONNECTIONS wiring diagrams in this manual The control unit comes with some resistors capacitors fitted on the con...

Page 14: ...ed cable to the battery In this phase the control unit is powered so the most careful attention should be paid The calibration must be carried out only when the control unit is on its final configurat...

Page 15: ...llow LED staying on This means that correct functioning of the control unit and subsequent calibration are required after each restart WARNING WARNING After having carried out the calibration close th...

Page 16: ...and no emergency ON FIXED all other cases OFF All the combinations are indicated below LED STATUS CONTROL UNIT STATUS RED YELLOW GREEN Emergency in progress Primary power supply fault Battery fault Fa...

Page 17: ...s the control unit can be interrogated using a diagnostics cable code 41853M which can be connected to a PC and makes it possible to recover information on the control unit s status in real time To us...

Page 18: ...isabled The control unit sends the motors an open command for 3 minutes If the deadlock function is enabled default setting the command is repeated with 2 minute pauses between each repetition for a t...

Page 19: ...this status until a RESET command is given the control unit goes into standby mode When the control unit is in EMERGENCY INTERLOCK status it gives a closing command to the motors and it ignores any em...

Page 20: ...troke time of 180 seconds is reached impulse operation or when the manual button is released dead man operation b When the reset button is pushed the drive command ends c Impulse operation the drive s...

Page 21: ...scale The selector comes in position 3 Beaufort scale knots km h mph m sec Situation 0 0 0 0 0 calm 1 1 3 1 5 1 3 2 puff of wind 2 4 6 6 11 4 7 2 3 gentle breeze 3 7 10 12 19 8 12 4 5 moderate breeze...

Page 22: ...heck on the control unit at least every 6 months by sending an emergency command from the each push button panel installed We recommend replacing the batteries every 3 years with equivalent batteries...

Page 23: ...sing for 120 seconds for each of the two zones if the battery charge level detected by the control unit is sufficient POSSIBLE FAULTS Interruption or short circuit on one or both the motor lines or pr...

Page 24: ...acement or repair free of charge of the item that within such period is returned delivery paid and found by us to be defective in terms of its materials and or manufacture The guarantee excludes any a...

Page 25: ...Doc 85588U Rev 22 10 2020 USER MANUAL USER MANUAL EN EN Drw 32367 h 25 54 NOTES...

Page 26: ......

Page 27: ...librazione 38 8 USO 39 8 1 Comandi e segnalazioni 39 8 2 Configurazione iniziale 41 8 3 Comandi per evacuazione fumo 42 8 3 1 Emergenza 42 8 3 2 EM SIG 42 8 3 3 EM CL SIG 42 8 3 4 AUX SIG 42 8 3 5 Int...

Page 28: ...tuzione di cavi di connessione e o di dispositivi danneggiati o che non funzionano correttamente Un applicazione scorretta o un improprio montaggio possono causare malfunzionamenti del sistema e o con...

Page 29: ...so di guasti o non corretto funzionamento le centrali non devono essere utilizzate fino a quando il Servizio Assistenza Tecnica non abbia ultimato l intervento di riparazione La configurazione origina...

Page 30: ...e attentamente rispettate da chiunque si appresti ad usare il prodotto Il mancato rispetto di quanto prescritto solleva la Ditta costruttrice da eventuali danni o infortuni a persone o cose che ne pot...

Page 31: ...sso cavi 2 Batterie tampone 3 Scheda elettronica 4 Morsetto collegamento alimentazione 5 Sistema di chiusura quadro 6 Connessione messa a terra 7 Pulsantiera di emergenza integrata 8 Pulsantiera apert...

Page 32: ...atterie tampone e gestiscono attuatori 24 Vcc L apertura per l evacuazione fumo avviene per inter vento di rilevatori di fumo pulsanti di emergenza centrali antincendio o sistemi BMS building manageme...

Page 33: ...Doc 85588U Rev 22 10 2020 MANUALE D USO MANUALE D USO IT IT Dis 32367 h 33 54 1 9 9 10 10 10 10 1 5 6 7 8 9 9 4 3 11 FIRE ALARM SYSTEM or BMS 2 2...

Page 34: ...out o di emergenza Con la centrale in standby la potenza erogata da tale uscita deve essere sottratta alla potenza disponibile sulle uscite motori 1 uscita con contatto pulito in commutazione NC NO pe...

Page 35: ...parete la posizione dei fori di fissaggio Forare la parete e fissare la scatola Scegliere in maniera adeguata il sistema di fissaggio in funzione del tipo di parete su cui viene montata la centrale R...

Page 36: ...a piastra B all interno della scatola C Per la versione C SV IB 4A 8A riposizionare il connettore D della pulsantiera e del pulsante di emergenza Riposizionare il cavo di messa a terra A sull anta del...

Page 37: ...i fili dell impianto I morsetti sono idonei per fili di sezione da 0 5 a 1 5 mmq da 20 a 16 AWG Consultare gli schemi COLLEGAMENTI ELETTRICI nel presente manuale La centrale viene fornita con alcune r...

Page 38: ...gare il cavo di alimentazione al morsetto G Collegare il cavo rosso alla batteria In questa fase la centrale risulta alimentata quindi occorre prestare la massima attenzione La calibrazione deve esser...

Page 39: ...gnalato col led giallo fisso La verifica del corretto funzionamento della centrale e la successiva calibrazione sono pertanto richieste dopo ogni riavvio ATTENZIONE ATTENZIONE Al termine della calibra...

Page 40: ...LED verde Nessun guasto alimentazione primaria OK e nessuna emergenza ON FISSO tutti gli altri casi OFF Di seguito tutte le combinazioni STATO LED STATO DELLA CENTRALE ROSSO GIALLO VERDE Emergenza in...

Page 41: ...anomalia possibile interrogare la centrale per mezzo di un cavo diagnostico cod 41853M che pu essere collegato ad un pc e permette di recuperare le informazioni sullo stato della centrale in tempo re...

Page 42: ...e ai motori un comando di apertura per 3 minuti Se la funzione ripetizione del comando di allarme abilitata default il comando viene ripetuto con pause di 2 minuti fra ogni ripetizione per un tempo to...

Page 43: ...AUX1 e vi rimane finch non viene impartito un comando di RESET che la riporta in standby Quando si trova nello stato INTERBLOCCO DI EMERGENZA la centrale impartisce un comando di chiusura ai motori e...

Page 44: ...ento a impulso o per rilascio del pulsante manuale funzionamento a uomo presente b per pressione del tasto di reset il comando dell azionamento termina c funzionamento a impulso l azionamento si ferma...

Page 45: ...one 3 scala Beaufort knots nodi km h mph miglia ora m s metri secondo Situazione 0 0 0 0 0 calma 1 1 3 1 5 1 3 2 bava di vento 2 4 6 6 11 4 7 2 3 brezza leg gera 3 7 10 12 19 8 12 4 5 brezza tesa 4 11...

Page 46: ...no ogni 6 mesi impartendo un comando di emergenza da ciascuna pulsantiera installata Si consiglia la sostituzione delle batterie ogni 3 anni con batterie equivalenti 2 batterie al piombo da 12 Volt e...

Page 47: ...elarsi da eventuali danni da vento e pioggia la centrale consente una chiusura manuale di 120 secondi per ciascuna delle due zone se il livello di carica delle batterie rilevato dalla centrale suffici...

Page 48: ...arazione gratuita del pezzo che entro il termine suddetto ci sar restituito in porto franco e che rileveremo essere effettivamente difettoso nei materiali o e nella fabbricazione E escluso dalla garan...

Page 49: ...orrectly by matching the polarities Installare le batterie correttamente rispettando le polarit RED ROSSO BLACK NERO L N BROWN MARRONE BLUE BLU GREEN YELLOW VERDE GIALLO BATTERIES BATTERIA RED ROSSO B...

Page 50: ...ONNECTION CONNESSIONE COMANDI MANUALI WEATHER SENSOR CONNECTION CONNESSIONE SENSORI CLIMA 3 4 5 A B C D 4 7 F 4 7 F For the connector posi tion on the board see page 49 Per la posizione del connettore...

Page 51: ...M SYSTEM CENTRALE COLLEGATA A SISTEMA DI ALLARME ESTERNO CONTROL UNIT CONNECTED TO EMERGENCY CLOSING COMMANDS CENTRALE COL LEGATA A COMANDI DI CHIUSURA DI EMERGENZA EMERGENCY CLOSING COMMAND NOT USED...

Page 52: ...RM N C ALLARME N C 2 RESET N O RESET N A 4 12Vdc red LED LED rosso See Vedere 8 1 6 12Vdc green LED LED verde See Vedere 8 1 7 0Vdc COMMON for LED COMUNE per LED See Vedere 8 1 8 NOT CONNECTED NON COL...

Page 53: ...54 EXAMPLE OF ALARM PROPAGATION FROM C SV 2 TO C SV 1 ESEMPIO DI PROPAGAZIONE ALLARME DA C SV 2 A C SV 1 11 R 10 k INTERLOCK FUNCTION FUNZIONE INTERLOCK 10 INTERLOCK MASTER INTERLOCK SLAVE 1 INTERLOC...

Page 54: ...Doc 85588U Rev 22 10 2020 USER MANUAL MANUALE D USO USER MANUAL MANUALE D USO EN IT EN IT Drw Dis 32367 h 54 54...

Page 55: ......

Page 56: ...Aprile 45 16012 BUSALLA GE ITALY Tel 39 010 9768232 Fax 39 010 9768233 e mail ucs ultra exgroup it www ultra exgroup it ucs www ultra excontrolsystems com e mail ucs ultra exgroup it www ultra exgrou...

Reviews: