OPL 

Low limit of 

retransmission 

current 

When OUTP works as re-transmitter, OPL/OPH define the 
low/high limit of re-transmisson. The unit is 0.1mA. 
For example, to transmit the channel 1 input 0~600

 into 

4~20mA output, the parameters should be set as below:   
dIL1=0, dIH1=600, OPn=1, OPL=40, OPH=200 

0~110 

OPH 

High limit of 

retransmission 

current 

0~220 

Po 

Atmospheric 

pressure 

Defined  atmospheric  pressure,  when  dry  bulb,  wet  bulb 
humidity measurement activated. Unit = KPa 

1~120.0 

SPEd 

Wind speed 

Defined  wind  speed,  when  dry  bulb,  wet  bulb  humidity 
measurement was activated. Unit = m/S 

0.01~10.00 

Addr 

Communication 

address 

Every  instrument  in  the  same  communication  line should 
be  assigned  to  different  communication  address.    The 
communication  applies  AIBUS  protocol.    Every  input 
channel  takes  one  address.    For  example,  if  Cn=3  and 
Addr=10,  then  the  communication  address  10~12  are 
assigned to the instrument.   

0 ~100 

bAud 

Baud rate 

When COMM module interface is used for communication, 
bAud defines the baud rate with range 300~19200bit/s. 
 
When  linear  current  output  module  is  installed  in  COMM 
socket, and bAud is set to 0~220, the COMM output can 
work as retransmission output.    It can retransmit channel 
2 input or cyclically retransmit all input channels into linear 
current.    bAud  defines  the  output  high  limit,  and  Addr 
defines  the  low  limit.    The  unit  is  0.1mA.    For  example, 
to output 4~20mA current, Addr should be set to 40, and 
bAud=200.   

0 ~19.2K 

Loc 

Parameter lock 

Loc=0:  Allow  to  display  and  modify  the  field  parameters 

only, which is defined in EP1~EP12. 

Loc=1: Display the field parameters, without modification. 
Loc=808: Allow to display and set all parameters. 

0 ~9999 

EP1-12 

Field 

parameter 

When  configuration  of  the  instrument  is  completed,  most 
parameters  are able  to hide  from field operators  to  avoid 
improper configuration. 
 
EP1~EP12  define  none  or  up  to  12  field  parameters  for 
operators  from  parameter  table,  except  EP  itself,  like 
H.AL1, L.AL1 and.etc. 
 
If  the  number  of  field  parameters  required  is  less  than 
12(sometimes  even  none),  define  field  parameters  from 
small number, the next unused EP set to NonE. 
E.g. Six parameters of H.AL1 to H.AL6 (all channels’ upper 
alarm)  are  need  to  be  modified  by  field  operators,  EP 
setting are as follows:   
EP1=H.AL1, 

EP2=H.AL2, 

EP3=H.AL3, 

EP4=H.AL4, 

EP5=H.AL5, EP6=H.AL6, EP7=NonE. 
If no field parameter is required, just set EP1=NonE, then 
set Loc to 0 or 1. 

NonE~bAud 

Summary of Contents for AI-702M

Page 1: ...hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 AI 702M 704M 706M HIGH PERFORMANCE INTELLIGENT MULTI CHANNEL INDICATORS Operation Instruction Version 7 7 Ideal for measurement indication alarm calculation and retransmission of temperature pressure flow level humidity etc ...

Page 2: ...ull scale the same as that of single channel Provide high accuracy compensation function such as ice point compensation copper resistance compensation and thermostat compensation to thermocouple inputs Build in accurate internal calculation functions including square root extraction summation subtraction and multiplication Support up to 2 isolated retransmission output Any input channel can be ret...

Page 3: ...6M A J1 J2 J5 L5 L5 S 24VDC Above code symbols a AI 706M instrument with front panel dimension 96 96mm 2 thermocouple inputs 2 two wire RTD inputs 2 current inputs 4 alarm relay outputs RS485 communication interface and the supply power is 24VDC The explanation for each code is below Shows the model of the indicator AI 702M AI 704M AI 706M respectively indicate 2 4 6 channels indicator Shows dimen...

Page 4: ... 1 channel thyristor normal open output Burnt proof technology able to stand 0 3A continuous current or 1A transient current G 1 SSR voltage output 12VDC 30mA G5 2 SSR voltage outputs 12VDC 30mA S Photoelectric isolated RS485 interface S4 Photoelectric isolated RS485 interface with isolated power supply X3 Photoelectric isolated linear current output X5 Photoelectric isolated linear current output...

Page 5: ...r J4 current input module 1 5V 4 20mA etc Two wire transmitter inputs with J5 module that provides 24VDC power supply Connect to 4 20mA two wires transmitter Maximum lead wire resistance for RTD input 2 wire type RTDs 2 ohm for Pt100 or 0 400 ohm input 1 ohm for Cu50 and 0 200 ohm input 3 wire type RTDs 5 ohm Measurement range K 0 1300 S 0 1700 R 0 1700 T 200 350 E 0 1000 J 0 1200 B 0 1800 N 0 130...

Page 6: ...nd signal terminals 2300VDC Between isolated eletroweak signal terminals 600VDC Response time 1 5 seconds if digital filter parameter is set as 0 or 1 Automatic pilot time interval Approx 1 2s or 2s configurable Alarm function High and low alarm configurable separately for each channel Alarm output Relay contact output NO or NC 250VAC 1A or 30VDC 1A No contact discrete output NO or NC 250VAC 0 3A ...

Page 7: ...he resistance of the wire To apply two wire method J2 module should be installed and resistance of each wire should be less than 2ohm AI 702M 704M 706M can measure the lead wire resistance of two wire method and save it to parameter Sc However the lead wire resistance changes as the temperature changes If the lead wires has the same ambient temperature as that of the instrument and no other resist...

Page 8: ... be displayed one by one When the parameters are set and the parameter lock is locked press can access Field Parameter Table The value of a parameter can be modified by or Press to go to next parameter Press and hold can return to the previous parameter Press can exit parameter setting status 3 Alarm display The lower display window shows channel number If high or low alarm occurs the first digit ...

Page 9: ...ns That the on off period is as long as 1 6 second means no communication and no alarm it can be treated as normal The light flashing with period 0 6 second means no communication and general error occurs The light quickly flashing with period 0 3 second means no communication and severe error such as input over range occurs The light keeping off means the instrument power off or damaged the light...

Page 10: ...ns caused by process input fluctuation 0 999 9 or 0 9999 units Snx Input specification Sn Input spec Sn Input spec 0 K 1 S 2 R 3 T 4 E 5 J 6 B 7 N 8 WRe3 WRe25 9 WRe5 WRe26 10 Extended input spec 11 18 Spare 19 BA2 JPt100 20 Cu50 21 Pt100 22 Pt100 100 00 300 00 23 24 Spare 25 0 75mV 26 0 80ohm 27 0 400ohm 28 0 20mV 29 0 100mV 0 5V J3 0 20mA J4 30 0 60mV 31 0 1V 32 0 2 1V two wire re transmitter J5...

Page 11: ...lay resolution is 0 001MPa Then the parameters should be set as below Sn1 33 dIP1 3 dIL1 0 000 dIH1 1 000 9990 30000 units or 0 1 dIHx Scale high limit Scx Input offset For thermocouple or three wire RTD inputs the units of Sc is 0 1 For example when Sc 100 the actual offset 10 then the measured temperature will be 10 lower than that when Sc 0 For two wire RTD inputs the actual offset Sc x signal ...

Page 12: ...wn as below L AL H AL No alarm 0 0 OP1 1 1 OP2 L5 need 2 2 AL1 3 3 AL2 L5 need 4 4 AU1 5 5 AU2 L5 need 6 6 MIO 7 7 For example ALP1 43 low limit alarm L AL of channel 1 output to AL2 ALP2 53 low limit alarm L AL of channel 2 output to AU1 and both high limit alarms H AL of both channel are sent to AL1 0 77 Cn Number of input channels Define actual number of input channels When Cn 2 the lower displ...

Page 13: ...e to set a AI 702M with 2 inputs fast cyclic display channel 1 input from three wire RTD J0 module on M1 socket channel 2 input from thermocouple J1 module on M2 socket current retransmission of channel 2 outputted to COMM port the AF parameter should be set as below A 1 B 1 C 0 D 0 then AF 19 0 31 nonc NO NC selection Single channel relay module provides both normal open and normal close output w...

Page 14: ... 19200bit s When linear current output module is installed in COMM socket and bAud is set to 0 220 the COMM output can work as retransmission output It can retransmit channel 2 input or cyclically retransmit all input channels into linear current bAud defines the output high limit and Addr defines the low limit The unit is 0 1mA For example to output 4 20mA current Addr should be set to 40 and bAu...