background image

  Yudian (H.K.) Automation Technology Co. Ltd. 

                                                                                       

Website: 

http://www.yudian.us

   

http://www.yudian.com.hk

  

                                                                                                                                            Email: 

sales@yudian.com.hk

 

Tel: +852-2770 

8785      Fax: +852-2770 8796 

 

3.  Wait 

until “A” disappears, and 

then removes 

the short wire, and set “Loc” to 0 or 1. 

 

4.  Now,  the  instrument  comes  back  to  normal  measurement  display  mode,  and  the  setting  of 

parameter “Sc” is finished.

 

 
The unit of Sc is 1/20000 of the scale of the corresponding RTD.    At 0

, the total resistance of the two lead 

wire  of  Pt100  or  0~400ohm  should  be  less  than  4ohm,  and  that  of  Cu50  should  be  less  than  2ohm.   
Otherwise, wire resistant compensation will not function.    The smaller the resistance of the lead wire, can 
provide more accurate measurement. 
 

4.  DIN rail mounted type

 

 
DIN mounted type (dimension E5) has no display window. It can input analog signals or input/output on-off 
signals for host computer or PLC, and it can also work as a two-channel programmable re-transmitter.   
E5 dimension instrument has one LED indication light.    When the instrument is communicating with the host 
computer, the light flashes with light on time different to light off time. When the instrument hasn’t received 
signal from the host computer for 6 seconds, the indication light should flash with the same light on time and 
light off time.   
 
 
It means: 

 

That the on-off period is as long as 1.6 second means no communication and no alarm (it can be treated 

as normal); 

 

The light flashing with period 0.6 second means no communication and general error occurs. 

 

The  light  quickly  flashing  with  period  0.3  second  means  no  communication  and  severe  error  such  as 

input over range occurs. 

 

The  light  keeping  off  means  the  instrument  power  off  or  damaged;  the  light  keep  on  (longer  than  8 

seconds) means the instrument power on but damaged. 

 
The parameters of E5 dimension instrument can be set by connecting external display to the 1394 socket.     
Note: The 1394 socket of the instrument only supports Yudian external display. 
 
The instrument can connect PC or PLC to monitoring or capture the data. We can provide the FREE protocol 
for user or order our monitoring software-AIDCS. Please contact Yudian Sales Dept. for more detail.   
 

5.  Dry Bulb, Wet Bulb Humidity Measurement 

 
By connecting 2 units of three-wire PT100 input, is can become the dry bulb, wet bulb humidity measurement.   
1.  Install J0 (RTD input module) in both M1 and M2 slot. Set Sn1=22, Sn2=42. 
2.  Atmospheric pressure and wind speed defined by parameter “Po

 and “SPEd

 

3.  Initialize measurement by wrapping dry bulb with wet muslin, giving same condition with wet bulb 
4.  Once reading is stable, adjust parameter Sc2 to offset reading to 100%,   
5.  Remove wet muslin after the adjustment. 
6.  Recommended  to  set  parameter  (dIP1=1,  dIP2=0)  to  have  more  stable  reading  with  resolution  0.1

 

and 1%RH. 

 

Summary of Contents for AI-702M

Page 1: ...hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 AI 702M 704M 706M HIGH PERFORMANCE INTELLIGENT MULTI CHANNEL INDICATORS Operation Instruction Version 7 7 Ideal for measurement indication alarm calculation and retransmission of temperature pressure flow level humidity etc ...

Page 2: ...ull scale the same as that of single channel Provide high accuracy compensation function such as ice point compensation copper resistance compensation and thermostat compensation to thermocouple inputs Build in accurate internal calculation functions including square root extraction summation subtraction and multiplication Support up to 2 isolated retransmission output Any input channel can be ret...

Page 3: ...6M A J1 J2 J5 L5 L5 S 24VDC Above code symbols a AI 706M instrument with front panel dimension 96 96mm 2 thermocouple inputs 2 two wire RTD inputs 2 current inputs 4 alarm relay outputs RS485 communication interface and the supply power is 24VDC The explanation for each code is below Shows the model of the indicator AI 702M AI 704M AI 706M respectively indicate 2 4 6 channels indicator Shows dimen...

Page 4: ... 1 channel thyristor normal open output Burnt proof technology able to stand 0 3A continuous current or 1A transient current G 1 SSR voltage output 12VDC 30mA G5 2 SSR voltage outputs 12VDC 30mA S Photoelectric isolated RS485 interface S4 Photoelectric isolated RS485 interface with isolated power supply X3 Photoelectric isolated linear current output X5 Photoelectric isolated linear current output...

Page 5: ...r J4 current input module 1 5V 4 20mA etc Two wire transmitter inputs with J5 module that provides 24VDC power supply Connect to 4 20mA two wires transmitter Maximum lead wire resistance for RTD input 2 wire type RTDs 2 ohm for Pt100 or 0 400 ohm input 1 ohm for Cu50 and 0 200 ohm input 3 wire type RTDs 5 ohm Measurement range K 0 1300 S 0 1700 R 0 1700 T 200 350 E 0 1000 J 0 1200 B 0 1800 N 0 130...

Page 6: ...nd signal terminals 2300VDC Between isolated eletroweak signal terminals 600VDC Response time 1 5 seconds if digital filter parameter is set as 0 or 1 Automatic pilot time interval Approx 1 2s or 2s configurable Alarm function High and low alarm configurable separately for each channel Alarm output Relay contact output NO or NC 250VAC 1A or 30VDC 1A No contact discrete output NO or NC 250VAC 0 3A ...

Page 7: ...he resistance of the wire To apply two wire method J2 module should be installed and resistance of each wire should be less than 2ohm AI 702M 704M 706M can measure the lead wire resistance of two wire method and save it to parameter Sc However the lead wire resistance changes as the temperature changes If the lead wires has the same ambient temperature as that of the instrument and no other resist...

Page 8: ... be displayed one by one When the parameters are set and the parameter lock is locked press can access Field Parameter Table The value of a parameter can be modified by or Press to go to next parameter Press and hold can return to the previous parameter Press can exit parameter setting status 3 Alarm display The lower display window shows channel number If high or low alarm occurs the first digit ...

Page 9: ...ns That the on off period is as long as 1 6 second means no communication and no alarm it can be treated as normal The light flashing with period 0 6 second means no communication and general error occurs The light quickly flashing with period 0 3 second means no communication and severe error such as input over range occurs The light keeping off means the instrument power off or damaged the light...

Page 10: ...ns caused by process input fluctuation 0 999 9 or 0 9999 units Snx Input specification Sn Input spec Sn Input spec 0 K 1 S 2 R 3 T 4 E 5 J 6 B 7 N 8 WRe3 WRe25 9 WRe5 WRe26 10 Extended input spec 11 18 Spare 19 BA2 JPt100 20 Cu50 21 Pt100 22 Pt100 100 00 300 00 23 24 Spare 25 0 75mV 26 0 80ohm 27 0 400ohm 28 0 20mV 29 0 100mV 0 5V J3 0 20mA J4 30 0 60mV 31 0 1V 32 0 2 1V two wire re transmitter J5...

Page 11: ...lay resolution is 0 001MPa Then the parameters should be set as below Sn1 33 dIP1 3 dIL1 0 000 dIH1 1 000 9990 30000 units or 0 1 dIHx Scale high limit Scx Input offset For thermocouple or three wire RTD inputs the units of Sc is 0 1 For example when Sc 100 the actual offset 10 then the measured temperature will be 10 lower than that when Sc 0 For two wire RTD inputs the actual offset Sc x signal ...

Page 12: ...wn as below L AL H AL No alarm 0 0 OP1 1 1 OP2 L5 need 2 2 AL1 3 3 AL2 L5 need 4 4 AU1 5 5 AU2 L5 need 6 6 MIO 7 7 For example ALP1 43 low limit alarm L AL of channel 1 output to AL2 ALP2 53 low limit alarm L AL of channel 2 output to AU1 and both high limit alarms H AL of both channel are sent to AL1 0 77 Cn Number of input channels Define actual number of input channels When Cn 2 the lower displ...

Page 13: ...e to set a AI 702M with 2 inputs fast cyclic display channel 1 input from three wire RTD J0 module on M1 socket channel 2 input from thermocouple J1 module on M2 socket current retransmission of channel 2 outputted to COMM port the AF parameter should be set as below A 1 B 1 C 0 D 0 then AF 19 0 31 nonc NO NC selection Single channel relay module provides both normal open and normal close output w...

Page 14: ... 19200bit s When linear current output module is installed in COMM socket and bAud is set to 0 220 the COMM output can work as retransmission output It can retransmit channel 2 input or cyclically retransmit all input channels into linear current bAud defines the output high limit and Addr defines the low limit The unit is 0 1mA For example to output 4 20mA current Addr should be set to 40 and bAu...

Page 15: ...Yudian H K Automation Technology Co Ltd Website http www yudian us http www yudian com hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 ...

Reviews: