Grounding the Switch
It is recommended that equipment changes be done on a grounded rack system. This will reduce or
prevent the risk of shock hazards, equipment damage, and potential of data corruption.
The switch can be grounded from the switch's case and/or the power supply units (PSUs). When
grounding the PSUs, ensure that both PSUs are grounded at the same time in case one of them is
removed.
The following instructions are for grounding the switch.
This equipment must be grounded. Do not defeat the ground conductor or
operate the equipment without correctly grounding the equipment. If there is any
uncertainty about the integrity of the equipment's grounding, please contact the
electrical inspection authority or a certified electrician.
1.
Before grounding the switch, ensure that the rack is properly grounded and in compliance with
local regulatory guidelines. Ensure that there is nothing that can obstruct the connection for
grounding and remove any paint or materials that may prevent good grounding contact.
2.
Remove the grounding screw from the switch.
3.
Attach the power cable
Connect the screw to an 18AWG minimum ring terminal grounding wire (not provided).
4.
Connect the other end of the wire to the rack ground.
Figure 21.