Ultra Aire XT105H / XT155H / XT205H Installation Instructions

Ultra-Aire.com | (800) 533-7533

Troubleshooting (Continued)

SERVICE

  Symptom 

Possible Reason 

Troubleshooting Procedure

 

Troubleshooting Procedure for Performance  

Related Issues

This method of diagnosis is used to function 

check the internal components in the dehumidifier. 

This is to be used when a performance issue is 

suspected.

1.  Set the humidity controller all the way to the 

most humid setting or off position – Did the 

unit shut off?

2.  If yes, turn the fan setting to the ON position – 

does the fan start?

3.  If fan starts, leave in the fan ON position and 

set the humidity all the way to driest setting. 

May have to wait 5 minutes for the compressor 

to start.

4.  Listen for a distinct buzzing/humming sound 

of a compressor starting up – do you hear this 

noise?

5.  If compressor is running and continues to run, 

after about 15 minutes you should feel a slight 

increase in air temperature being discharged 

out of the discharge air side of the unit.

6.  If so, depending on your environmental  

conditions (temp/Rh%), you should see some 

water production out of the hose within  

30 minutes or so. (Note: If the room  

temperature is 55 degrees or below and/or  

in area of low relative humidity, the  

dehumidifier will produce little to no water.)

7.  Collecting the water removed in a 24 hour period 

will give a measurement of performance. 

 

WARNING!

 

ELECTRICAL SHOCK HAZARD:

  

ELECTRICAL POWER MUST BE PRESENT 

TO PERFORM SOME TESTS. THESE TESTS 

SHOULD BE PERFORMED BY A QUALIFIED 

SERVICE PERSON.

Fan is not running. 

Dehumidification  

or fan is being 

called for.

1.  Loose connection in  

fan circuit.

2.  Obstruction prevents 

fan impeller rotation.

3. Defective fan.

4. Defective fan relay.

Low dehumidification 

capacity (evaporator 

is frosted  

continuously).  

Dehumidification is 

being called for.

1.  Defrost thermostat loose 

or defective.

2. Low refrigerant charge.

3.  Dirty air filter(s) or air flow 

restricted.

4.  Excessively restrictive 

ducting connected to unit.

No ventilation. 

Ventilation is being 

called for.

1.  Loose connection in  

ventilation control circuit.

2.  Loose connection in 

damper power circuit.

3.  Defective fresh air 

damper.

Dehumidifier  

removes some  

water, but not as 

much as expected. 

1.  Air temperature and/or 

humidity have dropped. 

2.  Humidity meter and/or 

thermometer used are  

out of calibration.

3.  Unit has entered defrost 

cycle. 

4.  Dirty air filter(s) or air flow 

is restricted. 

5.  Defective defrost  

thermostat. 

6. Low refrigerant charge. 

7.  Air leak such as loose 

cover or ducting leaks. 

8. Defective compressor. 

9. Restrictive ducting. 

 

WARNING!

SERVICING THE ULTRA AIRE DEHUMIDIFIER WITH ITS HIGH PRESSURE REFRIGERANT  

SYSTEM AND HIGH VOLTAGE CIRCUITRY PRESENTS A HEALTH HAZARD WHICH COULD  

RESULT IN DEATH, SERIOUS BODILY INJURY, AND/OR PROPERTY DAMAGE. SERVICE MUST  

BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN.

If the refrigerant charge is lost due to service or a leak, the leak should be repaired and a new charge must 

be accurately weighed in. If any of the old charge is left in the system, it must be recovered before weighing 

in the new charge. Refer to the unit nameplate for the correct charge weight and refrigerant type. 

Refrigerant Charging 

Summary of Contents for XT105H

Page 1: ...5H XT155H XT205H Ultra Aire com 800 533 7533 The Ultra Aire XT Dehumidifiers are ventilating dehumidifiers that integrate into the heating and cooling system to provide the ultimate in comfort health...

Page 2: ...Air Ventilation 10 Determine Ventilation Requirements 11 Controls 12 Air Filtration 13 MERV Rating Chart 14 Service 15 Warranty 17 TABLE OF CONTENTS Ultra Aire is committed to manufacturing quality p...

Page 3: ...LING SHEET METAL IMPROPER INSTALLATION MAY CAUSE PROPERTY DAMAGE OR INJURY INSTALLATION SERVICE AND MAINTENANCE MUST BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN DEHUMIDIFIER IS HEAVY HANDLE WITH CA...

Page 4: ...handle the unit s overall dimensions as well as the necessary return and supply ductwork to the unit Allow sufficient clearance for filter removal and to prevent airflow obstruction Electrical servic...

Page 5: ...eter duct to the unit using the screws provided The 6 duct should be capped if fresh air is not desired If setting up the unit to provide fresh air ventilation see page 10 Return Air Inlet Attach 10 d...

Page 6: ...w voltage 18 22 gauge thermostat wire ELECTRICAL REQUIREMENTS CAUTION DO NOT ALLOW THE WIRE FROM THE 24V TERMINAL TO MAKE CONTACT WITH THE WIRE FROM THE COM TERMINAL OR DAMAGE TO THE TRANSFORMER WILL...

Page 7: ...nsate Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to close the float switch The pump also contains a safety float switch The white leads...

Page 8: ...A short piece of flexible ducting on all Ultra Aire Dehumidifier duct connections is recommended to reduce noise and vibration transmitted to rigid ductwork in the structure Use a minimum 10 diameter...

Page 9: ...m Utilize the optional fresh air ventilation duct to provide outside air Install a dedicated air return for the Ultra Aire Dehumidifier from a central area of the structure Install an insulated duct f...

Page 10: ...can be impacted by inside and outside air conditions When a 6 motorized damper is used a digital control is required It may be necessary to use 8 duct work if additional fresh air is required In cold...

Page 11: ...s 2500 X 0 03 5 X 7 5 112 5 CFM Record the required CFM ____________ FRESH AIR VENTILATION Determine Ventilation Requirements The MINIMUM ventilation requirement is calculated using ASHRAE 62 2 2016 U...

Page 12: ...The reset button for the circuit breaker can be found on the back of the unit Control Connections The control and the Ultra Aire Dehumidifier are labeled to prevent confusion Depending on the control...

Page 13: ...RE CHANGING THE FILTER Step 1 The filter door is attached to the cabinet by three hinges Release the latch from the cabinet by pulling it towards the front of the unit The filter door will swing open...

Page 14: ...tial Bag Filter Nonsupported Legionella microfine fiberglass or 11 60 65 95 Humidifier Dust Better Commercial Buildings synthetic media 12 36 in deep 6 12 pockets Lead Dust 10 50 55 95 Milled Flour Bo...

Page 15: ...together the fan only should run Disconnect when complete 8 Jumper a wire from the 24V and DEHU terminal fan and compressor should run Disconnect when complete 9 If this test works then the field cont...

Page 16: ...PERFORMED BY A QUALIFIED SERVICE PERSON Fan is not running Dehumidification or fan is being called for 1 Loose connection in fan circuit 2 Obstruction prevents fan impeller rotation 3 Defective fan 4...

Page 17: ...ver any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Re...

Page 18: ...18 Ultra Aire XT105H XT155H XT205H Installation Instructions Ultra Aire com 800 533 7533...

Page 19: ...19 Ultra Aire com 800 533 7533 Ultra Aire XT105H XT155H XT205H Installation Instructions...

Page 20: ...800 533 7533 www Ultra Aire com...

Reviews: