Ultra Aire XT105H / XT155H / XT205H Installation Instructions

Ultra-Aire.com | (800) 533-7533

The Ultra Aire Dehumidifier plugs into a common grounded 115 VAC outlet. Locate the dehumidifier in an 

area where the cord’s length (9') easily reaches a 115 VAC electrical outlet with a minimum of 15 Amp circuit 

capacity. The Ultra Aire XT205H requires a dedicated 20 Amp circuit. If used in an area that may become wet, 

a GFCI protected circuit is recommended. Consult local electrical codes for further information. 
Ultra Aire offers a variety of control devices for use with the Ultra Aire Dehumidifier. The control is to be  

located remotely from the dehumidifier and placed in the space to be conditioned. A low voltage (24 Volt) 

control MUST be used with the Ultra Aire Dehumidifier and MUST be connected with low voltage (18-22 

gauge) thermostat wire.  

ELECTRICAL REQUIREMENTS

 

CAUTION!

DO NOT ALLOW THE WIRE FROM THE 24V TERMINAL TO MAKE CONTACT WITH THE WIRE FROM 

THE COM TERMINAL OR DAMAGE TO THE TRANSFORMER WILL RESULT. 

Electrical Precautions

•  Do not install the control where it may not accurately sense the 

relative humidity such as near HVAC supply registers, near  

exterior doors, on an outside wall, near a window, or near a 

water source. 

•  The screw terminals on the Ultra Aire Dehumidifier and the 

control are labeled to prevent confusion. 

•  Be sure to consult the electrical schematic in the CONTROLS 

Section (page 12) of this manual or inside the access panel  

of the Ultra Aire Dehumidifier before making control  

connections.

 

WARNING!

THE REMOTE CONTROLS OF THE ULTRA AIRE DEHUMIDIFIER ARE POWERED BY A LOW VOLTAGE 

CIRCUIT (24 VAC) AND MUST NEVER CONTACT OR BE CONNECTED TO A HIGH VOLTAGE CIRCUIT.

 

CAUTION!

SOME OF THE TERMINAL CONTROLS ON THE ULTRA AIRE DEHUMIDIFIER MAY BE USED WITH 

CERTAIN CONTROLS. 

Wiring Diagram

Summary of Contents for XT105H

Page 1: ...5H XT155H XT205H Ultra Aire com 800 533 7533 The Ultra Aire XT Dehumidifiers are ventilating dehumidifiers that integrate into the heating and cooling system to provide the ultimate in comfort health...

Page 2: ...Air Ventilation 10 Determine Ventilation Requirements 11 Controls 12 Air Filtration 13 MERV Rating Chart 14 Service 15 Warranty 17 TABLE OF CONTENTS Ultra Aire is committed to manufacturing quality p...

Page 3: ...LING SHEET METAL IMPROPER INSTALLATION MAY CAUSE PROPERTY DAMAGE OR INJURY INSTALLATION SERVICE AND MAINTENANCE MUST BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN DEHUMIDIFIER IS HEAVY HANDLE WITH CA...

Page 4: ...handle the unit s overall dimensions as well as the necessary return and supply ductwork to the unit Allow sufficient clearance for filter removal and to prevent airflow obstruction Electrical servic...

Page 5: ...eter duct to the unit using the screws provided The 6 duct should be capped if fresh air is not desired If setting up the unit to provide fresh air ventilation see page 10 Return Air Inlet Attach 10 d...

Page 6: ...w voltage 18 22 gauge thermostat wire ELECTRICAL REQUIREMENTS CAUTION DO NOT ALLOW THE WIRE FROM THE 24V TERMINAL TO MAKE CONTACT WITH THE WIRE FROM THE COM TERMINAL OR DAMAGE TO THE TRANSFORMER WILL...

Page 7: ...nsate Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to close the float switch The pump also contains a safety float switch The white leads...

Page 8: ...A short piece of flexible ducting on all Ultra Aire Dehumidifier duct connections is recommended to reduce noise and vibration transmitted to rigid ductwork in the structure Use a minimum 10 diameter...

Page 9: ...m Utilize the optional fresh air ventilation duct to provide outside air Install a dedicated air return for the Ultra Aire Dehumidifier from a central area of the structure Install an insulated duct f...

Page 10: ...can be impacted by inside and outside air conditions When a 6 motorized damper is used a digital control is required It may be necessary to use 8 duct work if additional fresh air is required In cold...

Page 11: ...s 2500 X 0 03 5 X 7 5 112 5 CFM Record the required CFM ____________ FRESH AIR VENTILATION Determine Ventilation Requirements The MINIMUM ventilation requirement is calculated using ASHRAE 62 2 2016 U...

Page 12: ...The reset button for the circuit breaker can be found on the back of the unit Control Connections The control and the Ultra Aire Dehumidifier are labeled to prevent confusion Depending on the control...

Page 13: ...RE CHANGING THE FILTER Step 1 The filter door is attached to the cabinet by three hinges Release the latch from the cabinet by pulling it towards the front of the unit The filter door will swing open...

Page 14: ...tial Bag Filter Nonsupported Legionella microfine fiberglass or 11 60 65 95 Humidifier Dust Better Commercial Buildings synthetic media 12 36 in deep 6 12 pockets Lead Dust 10 50 55 95 Milled Flour Bo...

Page 15: ...together the fan only should run Disconnect when complete 8 Jumper a wire from the 24V and DEHU terminal fan and compressor should run Disconnect when complete 9 If this test works then the field cont...

Page 16: ...PERFORMED BY A QUALIFIED SERVICE PERSON Fan is not running Dehumidification or fan is being called for 1 Loose connection in fan circuit 2 Obstruction prevents fan impeller rotation 3 Defective fan 4...

Page 17: ...ver any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Re...

Page 18: ...18 Ultra Aire XT105H XT155H XT205H Installation Instructions Ultra Aire com 800 533 7533...

Page 19: ...19 Ultra Aire com 800 533 7533 Ultra Aire XT105H XT155H XT205H Installation Instructions...

Page 20: ...800 533 7533 www Ultra Aire com...

Reviews: