Initial Start-up Step-By-Step Instructions
Rev D
C. Allow water to run to drain until the water runs clear from the drain
line. This purges any refuse from the media bed.
D. Turn off the water supply and let the system stand for about five
minutes. This will allow any air trapped to escape from the tank.
5. Add water to the regenerant tank (initial fill) (conditioner and FA filters
only).
A. With a bucket or hose, add approximately 4 gallons (15 liters) of
water to the regenerant tank.
If the tank has a salt platform in the bottom of the tank, add water
until the water level is approximately 1 inch (25 mm) above the
platform.
6. Engage the refill cycle to prime the line between the regenerant tank
and the valve (conditioner only).
A. Slowly open the main water supply valve again, to the fully open
position. Be sure not to open too rapidly as that would push the
media out of the media tank.
B. Advance the controller to the Refill (C8) position. From cycle C1
(Backwash), press and hold the SET button. This will display the
current cycle.
While pressing the SET button, press UP to advance to the next
cycle. Continue to advance through each cycle until you have
reached cycle C8 (Refill).
C. With the water supply completely open, when you arrive at cycle
C8 (Refill), the controller will direct water down through the line to
the regenerant tank. Let the water flow through the line until all air
bubbles have been purged from the line.
NOTE:
We recommend that you do not put regenerant into the tank
until after the control valve has been put into operation. With no
regenerant in the tank, it is much easier to view water flow and motion
in the tank.
NOTE:
As you advance through each cycle there will be a slight delay
before you can advance to the next cycle. The hourglass icon will light
while the camshaft is indexing. There may be a pause at cycle C4
(System Pause). This cycle allows the water/air pressure to equalize on
each side of the valve discs before moving on. The hourglass will not be
visible indicating that the system is paused.
Time & Day
Regen Time & Day
Salt
SU MO TU
WE TH
FR
SA DAYS
C
Capacity
Hardness