Important:

 for RS485 connections in household (IEC EN 55014-

1) and residential (IEC EN 61000-6-3) environments, use 

shielded cable (with shield connected to PE both on the terminal and 

controller ends), maximum length specified by the EIA RS485 protocol,, 

using AWG26 twisted pair cable; 

the input impedance of the 485 stage is 1/8 unit-load (96 kOhm). This 

configuration allows a maximum of 256 devices to be connected, with 

cables in separate conduits from the power cable.

ALARM RELAY

This is used to signal one or more alarms via a remote connection.

Alarm relay

NO

COMMON

M 15

Fig. 4.e

ALARM RELAY POWER SUPPLY

The connections shown in Fig.4.g can be used to directly control a  

auxiliary relay coil 

30 Vdc (24 Vac rectified), 3 W max.

+24 V

GND

Alarm signal 

(max 3W)

M 15

Fig. 4.f

Note: 

in industrial environments (IEC EN61000-6-2) the signal 

cables leaving the unit 

must not exceed (33 ft)

(1)

 in length: remote on/

off digital input (terminals M14.1...M14.2) and shielded cable for RS485 

communication

4.4  Auxiliary card connections (optional)

J17

J8

1        2            1        2         3         4         5

M9

M10

+    GND   21Vdc  

The auxiliary card features the following connections

ON/OFF CONTROLLER (humidistat or remote switch)

• 

jumper inputs M14.1 and M14.2 (enable) on the main board;

• 

connect terminals M10.1 and M10.2 to a humidistat or a remote switch 

(voltage-free contact)

• 

set parameter A0=0 to enable On/Off operation (see Chap. 7)

EXTERNAL PROPORTIONAL CONTROLLER (modulating)

• 

jumper inputs M14.1 and M14.2 (enable) on the main board;

• 

connect terminals M10.1 and M10.2 (production request) to an external 

controller; 

• 

set parameter A0=1 to enable modulating control (see Chap. 7) and 

parameter A2 depending on the chosen signal (0 to 10 V, 2 to 10V, 0 to 

20, 4 to 20 mA) (see Chap. 7). 

CONTROL WITH CAREL HUMIDITY PROBE 

(Optional) identified with remote sensor included with cabinet, terminate 3 

conductor wire to terminal strip. Terminations have been completed inside 

by Ultra Pure.  Simply terminate 3 wires (white,black and red) color for 

color to terminal strip and mount T&H in desired location using 5' included 

wire.  

Final checks

The following conditions represent correct electrical connection:

 

main power to the humidifier corresponds to the voltage shown on the 

rating plate.

 

Recepticle has been verified to be 115v, correct polarity and grounded

J8

tLAN terminal connection (optional) with 30 Vdc power supply 

(24 Vac rectified)

M9

tLAN AUX serial connector

M10

M10.1 -  +  Analog proportional controller/probe/humid.

M10.2 -  + GND signal reference

M10.3 - +21Vdc for active probe supply

M10.4 - N.U.

M10.5 - N.U.

J17

AUX input 

Summary of Contents for pureMist

Page 1: ...NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT Engineering Manual Compact Ultrasonic Humidifier...

Page 2: ...r with the characteristics indicated in this manual must be used for water vapor production Alloperationsontheproductmustbecarriedoutaccordingtotheinstructions provided in this manual and on the label...

Page 3: ...2 Meaning of the symbols 12 6 3 Keypad 12 6 4 Main display 12 6 5 Display software release 12 7 CONFIGURATION PARAMETERS 13 7 1 Basic parameters 13 7 2 Advanced parameters 13 8 ALARMS 14 9 MAINTENANC...

Page 4: ...essories Wand Distributor Production Supply Temperature Electrical Rating Amp Max Weight Dimensions 1 1 2 2 Lbs Hr 33 8 104 F 115 V 60Hz 8 MFS 15 28lbs 12 x 9 x 11 Temp Hum Stat Diffuser Remote Displa...

Page 5: ...fier The following are contained inside fig 1 A IOM manual B Optional accessories if purchased ie distributor 50M filter plastic tube seperate box S S distributer seperate box 10 1 4 RED inlet water 3...

Page 6: ...3 8 push connect fitting Black Connect included RJ11 cord to display and plug into cabinet Terminate 3 wire color coded wired if optional temperature and humidity sensor is used to side of cabinet col...

Page 7: ...tially chemically or bacteriologically contaminated water is prohibited 2 2 Drain water Drain water from the humidifer is not toxic and can be drained into the approved drain system Attach 1 2 FPT fem...

Page 8: ...e elbow It s necessary to clean the filter with compressed air or running water periodically frequency depends on the environment in which the system is installed Features filter 50 micron H 5 D 2 3 6...

Page 9: ...ansducer management only for 2 transducer version OFF parallel management modulation of all 2 ON if demand is less than 50 it works only one transducer at a time alternately Tab 4 c 4 2 Power cable co...

Page 10: ...umper inputs M14 1 and M14 2 enable on the main board connect terminals M10 1 and M10 2 to a humidistat or a remote switch voltage free contact set parameter A0 0 to enable On Off operation see Chap 7...

Page 11: ...emptied automatically When in standby the fan stays on for 5 min 5 3 Autotest When humidifier is first started from off if enabled and humidity production is required a test cycle is run A complete f...

Page 12: ...set the values ENTER PRG for 2 seconds access the list of parameters inside the list of parameters select and confirm like Enter on a computer keyboard 6 4 Display software release 1 on power up the d...

Page 13: ...Maximum time to measure high level s 1 60 10 AE Restart fan time in standby for integrated probe reading min 0 120 10 AF Piezoelectric transducer working life h 0 9999 9999 with demineralised water b...

Page 14: ...ity probe signal cable yes humidification interrupted AUTO 3 slow flashes H_ Low humidity The signal from the probe indi cates humidity less than 20 rH Check humidity probe signal cable yes humidifica...

Page 15: ...iew the inside of the tank Scale build up on the surface of the piezoelectric transducers Clean the inside of the tank and replace the transducers Tab 8 b These malfunctions can be avoided by carrying...

Page 16: ...cally to remove it 4 clean or replace the transducers by removing the screws see Fig 9 b after replacement test water tightness by filling the tank manually 5 reconnect the transducer power cables 6 r...

Page 17: ...17 10 GENERAL FEATURES AND MODELS 10 4 Version 115V Fig 10 c...

Page 18: ...ity at 20 C 0 50 S cm total hardness 0 25 mg l CaCO3 temporary hardness 0 15 mg l CaCO3 total quantity of dissolved solids cR depending on specific conductivity 1 dry residue at 180 C depending on spe...

Page 19: ...Inactivity time for washing on next start R W 32 159 Parameter b3 Washing time fill drain R W 33 160 Parameter b4 Start delay time R W 34 161 Parameter b5 Operating hours for CL alarm R W 35 162 Param...

Page 20: ...at 1 the humidifier excludes the external command signals external regulator or probes and uses the value of Integer 60 modbus 188 as like comand signal The humidity production can be managed in two...

Page 21: ...of a signal Y from an external device The type of signal can be selected between the following standards 0 to 10 Vdc 2 to 10 Vdc 0 to 20 mA 4 to 20 mA Maximum humidifier production corresponding to th...

Page 22: ...ituation is repeated alarm EP is activated which shuts down the unit If after a percentage of A8 set by parameter Ab default 70 the water is above the high level threshold atomised water production st...

Page 23: ...llowing fields Percentage request sent to the Master Fig 3 Operating hour counter Fig 4 resettable pressing UP DOWN for 5 seconds see parameter d3 Unit alarms Fig 5 means no alarms are present resetta...

Page 24: ...ctrical wiring from alarm relay output on the master to auxiliary input J17 on the slave and vice versa from alarm relay output on the slave to auxiliary input J17 on the master Main board Slave unit...

Page 25: ...Main Board Connections MASTER UNIT Connections M 11 TX RX GND GND 1 RS485 Supervisore ON OFF 4 Main Board Connections SLAVE UNIT Connections 2 3 6 4 7 5 1 8 ON M9 M 11 M 11 M 11 6 6 6 TLan 2 Supervis...

Page 26: ...Ultra Pure Systems 1855 E Southern Ave Mesa AZ 85204 800 729 5192 www ultrapureus com...

Reviews: