12.  HUMIDIFIER CONTROL VIA NETWORK

The variables shown in the list are a set of all the internal variables.  

DO NOT CONFIGURE ANY VARIABLES THAT ARE NOT SHOWN IN THE TABLE, 

OTHERWISE HUMIDIFIER OPERATION MAY BE AFFECTED. 

The serial connection (M11) is configured by default with the following parameters:

- Address 1

- Baud rate 19200 bps

- Frame 8,N,2

12.1  Supervisor variable list

“A”

analogue variables*  (Modbus®: REGISTERS)

R/W

ULTRA PURE- 

Modbus®

1

param. d0: Th probe temperature reading

R

2

param. d1: Th probe humidity reading

R

3

param. d2: Probe reading

R

4

param. d5: Instant production

R

“I”

integer variables (Modbus®: REGISTERS)

R/W

ULTRA 

PURE

Modbus®

1

128

Level access password 

R/W

2

129

Firmware release

R

15

142

Alarms, refer to Chap.8 ALARMS:

• 

bit0:  Alarm E0

• 

bit1:  Alarm Et

• 

bit2:  Alarm EF

• 

bit3:  Alarm Ed

• 

bit4:  Alarm EP

• 

bit5:  Alarm PU  

• 

bit6:  Alarm H ¯

• 

bit7:  Alarm H_

• 

bit8:  Alarm EE

• 

bit9:  Alarm CL

R/W

20

147

Parameter A0: Operating mode

R/W

21

148

Parameter A2: Type of external probe

R/W

22

149

Parameter A3: Probe minimum

R/W

23

150

Parameter A4: Probe maximum

R/W

24

151

Parameter A5: Probe offset

R/W

25

152

Parameter A6: Fan off delay time

R/W

26

153

Parameter A7: Fan speed

R/W

27

154

Parameter A8: Maximum evaporation time for no production alarm

R/W

28

155

Parameter A9: Minimum evaporation time for no production alarm

R/W

29

156

Parameter b0: Operating options

R/W

30

157

Parameter b1: Time between two washing cycles

R/W

31

158

Parameter b2: Inactivity time for washing on next start

R/W

32

159

Parameter b3: Washing time (fill + drain)

R/W

33

160

Parameter b4: Start delay time

R/W

34

161

Parameter b5: Operating hours for CL alarm

R/W

35

162

Parameter b6: Time to display new CL alarm in minutes

R/W

36

163

Parameter b7: Transducer On/Off control interval

R/W

37

164

Parameter b8: Probe delay disconnected

R/W

38

165

Parameter b9 TAM OFF delay

R/W

39

166

Parameter bA: Maximum fill time

R/W

40

167

Parameter bb: Refill time in evaporation

R/W

41

168

Parameter bC: Maximum drain time

R/W

42

169

Parameter bd: Drain opening time to completely empty tank

R/W

43

170

Parameter bE: Delay time after measuring low level for refilling

R/W

44

171

Parameter C0: Default display (Terminal)

R/W

45

172

Parameter C1: Parameter A0: Baud rate

R/W

46

173

Parameter C2: tLAN address (If 0 Master controller)

R/W

47

174

Parameter C3: Serial address

R/W

48

175

Parameter P0: Maximum flow-rate

R/W

49

176

Parameter P1: Humidity control hysteresis

R/W

50

177

Parameter P2: Low humidity alarm threshold

R/W

51

178

Parameter P3: High humidity alarm threshold

R/W

52

179

Parameter SP: Humidity set point

R/W

53

180

Parameter d3: Operating hour counter

R

54

181

Parameter d4: Unit hour counter (not resettable)

R/W

60

187

Request via serial (if digital 37 set)

R/W

62

189

Identification of variable on slave unit to read/write from supervisor (see paragraph 14.4)

R/W

63

190

Value of variable on slave unit identified by integer 62 (see paragraph 14.4)

R/W

65

192

Parameter C4: Timeout for master serial offline

R/W

69

196

AA: Waiting time for retry

R/W

70

197

Ab: Percentage of A8 for carrying out level test

R/W

Summary of Contents for pureMist

Page 1: ...NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT Engineering Manual Compact Ultrasonic Humidifier...

Page 2: ...r with the characteristics indicated in this manual must be used for water vapor production Alloperationsontheproductmustbecarriedoutaccordingtotheinstructions provided in this manual and on the label...

Page 3: ...2 Meaning of the symbols 12 6 3 Keypad 12 6 4 Main display 12 6 5 Display software release 12 7 CONFIGURATION PARAMETERS 13 7 1 Basic parameters 13 7 2 Advanced parameters 13 8 ALARMS 14 9 MAINTENANC...

Page 4: ...essories Wand Distributor Production Supply Temperature Electrical Rating Amp Max Weight Dimensions 1 1 2 2 Lbs Hr 33 8 104 F 115 V 60Hz 8 MFS 15 28lbs 12 x 9 x 11 Temp Hum Stat Diffuser Remote Displa...

Page 5: ...fier The following are contained inside fig 1 A IOM manual B Optional accessories if purchased ie distributor 50M filter plastic tube seperate box S S distributer seperate box 10 1 4 RED inlet water 3...

Page 6: ...3 8 push connect fitting Black Connect included RJ11 cord to display and plug into cabinet Terminate 3 wire color coded wired if optional temperature and humidity sensor is used to side of cabinet col...

Page 7: ...tially chemically or bacteriologically contaminated water is prohibited 2 2 Drain water Drain water from the humidifer is not toxic and can be drained into the approved drain system Attach 1 2 FPT fem...

Page 8: ...e elbow It s necessary to clean the filter with compressed air or running water periodically frequency depends on the environment in which the system is installed Features filter 50 micron H 5 D 2 3 6...

Page 9: ...ansducer management only for 2 transducer version OFF parallel management modulation of all 2 ON if demand is less than 50 it works only one transducer at a time alternately Tab 4 c 4 2 Power cable co...

Page 10: ...umper inputs M14 1 and M14 2 enable on the main board connect terminals M10 1 and M10 2 to a humidistat or a remote switch voltage free contact set parameter A0 0 to enable On Off operation see Chap 7...

Page 11: ...emptied automatically When in standby the fan stays on for 5 min 5 3 Autotest When humidifier is first started from off if enabled and humidity production is required a test cycle is run A complete f...

Page 12: ...set the values ENTER PRG for 2 seconds access the list of parameters inside the list of parameters select and confirm like Enter on a computer keyboard 6 4 Display software release 1 on power up the d...

Page 13: ...Maximum time to measure high level s 1 60 10 AE Restart fan time in standby for integrated probe reading min 0 120 10 AF Piezoelectric transducer working life h 0 9999 9999 with demineralised water b...

Page 14: ...ity probe signal cable yes humidification interrupted AUTO 3 slow flashes H_ Low humidity The signal from the probe indi cates humidity less than 20 rH Check humidity probe signal cable yes humidifica...

Page 15: ...iew the inside of the tank Scale build up on the surface of the piezoelectric transducers Clean the inside of the tank and replace the transducers Tab 8 b These malfunctions can be avoided by carrying...

Page 16: ...cally to remove it 4 clean or replace the transducers by removing the screws see Fig 9 b after replacement test water tightness by filling the tank manually 5 reconnect the transducer power cables 6 r...

Page 17: ...17 10 GENERAL FEATURES AND MODELS 10 4 Version 115V Fig 10 c...

Page 18: ...ity at 20 C 0 50 S cm total hardness 0 25 mg l CaCO3 temporary hardness 0 15 mg l CaCO3 total quantity of dissolved solids cR depending on specific conductivity 1 dry residue at 180 C depending on spe...

Page 19: ...Inactivity time for washing on next start R W 32 159 Parameter b3 Washing time fill drain R W 33 160 Parameter b4 Start delay time R W 34 161 Parameter b5 Operating hours for CL alarm R W 35 162 Param...

Page 20: ...at 1 the humidifier excludes the external command signals external regulator or probes and uses the value of Integer 60 modbus 188 as like comand signal The humidity production can be managed in two...

Page 21: ...of a signal Y from an external device The type of signal can be selected between the following standards 0 to 10 Vdc 2 to 10 Vdc 0 to 20 mA 4 to 20 mA Maximum humidifier production corresponding to th...

Page 22: ...ituation is repeated alarm EP is activated which shuts down the unit If after a percentage of A8 set by parameter Ab default 70 the water is above the high level threshold atomised water production st...

Page 23: ...llowing fields Percentage request sent to the Master Fig 3 Operating hour counter Fig 4 resettable pressing UP DOWN for 5 seconds see parameter d3 Unit alarms Fig 5 means no alarms are present resetta...

Page 24: ...ctrical wiring from alarm relay output on the master to auxiliary input J17 on the slave and vice versa from alarm relay output on the slave to auxiliary input J17 on the master Main board Slave unit...

Page 25: ...Main Board Connections MASTER UNIT Connections M 11 TX RX GND GND 1 RS485 Supervisore ON OFF 4 Main Board Connections SLAVE UNIT Connections 2 3 6 4 7 5 1 8 ON M9 M 11 M 11 M 11 6 6 6 TLan 2 Supervis...

Page 26: ...Ultra Pure Systems 1855 E Southern Ave Mesa AZ 85204 800 729 5192 www ultrapureus com...

Reviews: