background image

of the low-voltage end. If signal is detected for both primary and secondary circuits, the tester 
simultaneously shows the change by converting the secondary current at 5A, and indicates the 
phase type. The symbol “No signal” appears if the tester fails to connect with the high-voltage clamp 
sensor normally. 

 

The LCD flashes continuously 10 minutes after the tester is powered on, to indicate auto power off. 
After the LCD flashes continuously for about 30 seconds, the tester powers off automatically to 
save battery power. If “

” is pressed when the LCD flashes continuously, the tester can continue 

working. 

Under testing mode, press “

” power off the tester. 

Under phase error mode, long press “MEN” to return to testing mode, then press “

” to power off 

the tester. 

Under data viewing mode, move the cursor to “Return”, press “MEN” to return to testing mode, then 
press “

” to power off the tester. 

 

3. Testing of High-Voltage Current and Overhead Current 

 

High voltage! Extremely dangerous! The operation must be performed by 

authorized trained personnel. The operator must stringently follow the safety 

regulations, otherwise it may present a risk of electric shock, which can cause 

personal injury or death. 

The insulation stick must be connected when performing testing by clamping 

high-voltage line, otherwise it may present a risk of electric shock, which can 

cause personal injury or death. 

Danger! It is forbidden to test bare conductor or bus bar with voltage over 

35kV, otherwise it may cause electric shock, thus causing personal injury or 

product damage. 

Danger! Do not measure circuit over 800A, otherwise it may present a risk of 

electric shock, which can cause personal injury or product damage. 

 

 

Please first connect the insulation stick before connecting the clamp sensor, 

to avoid impact on the ground. 

Please use dedicated insulation stick to connect the clamp sensor. 

After testing, incline the insulation stick, disconnect the clamp sensor, and 

then disconnect the insulation stick, to avoid impact on the ground. 

Connect the high-voltage clamp sensor with the 5 pieces of insulation sticks, power on the high-
voltage clamp sensor, then set the conductor at the middle area of the leading sector of the clamp 
jaws, as shown in Figure A. Make the leading sector vertical to the conductor, push the insulation 
stick so as for the jaws to clamp the measured conductor, then the high-voltage clamp sensor starts 

5

Summary of Contents for UT225B

Page 1: ...UT225B UT225B P N 110401111909X UT225B High Voltage Transformer Turns Ratio Tester...

Page 2: ...s 4 1 Power On Off the Primary High Voltage Clamp Sensor 2 2 Power On Off the Tester 2 3 Testing of High Voltage Current and Overhead Current 2 4 Secondary Low Voltage Current Testing 2 5 Testing of T...

Page 3: ...to the instruction It is recommended to perform dielectric test on the product once a year at least AC 60kV rms between both ends 5 pieces of connected insulation sticks II Introduction UT225B High Vo...

Page 4: ...ty Basic conditions Work conditions Remark Ambient temperature 23 C 5 C 15 C 50 C Ambient humidity 40 60 70 Distortion rate of sinusoidal wave 1 3 Signal frequency 50Hz 5Hz 45Hz 65Hz External electric...

Page 5: ...r than 4 8V the symbol appears to indicate replacing battery Transmission distance of primary clamp sensor 100M wireless transmission Data transfer USB Connecting wire of secondary clamp sensor 2M Dis...

Page 6: ...with the indicator light lit up and it starts automatic testing The testing results current pulse and others of the high voltage end are sent to the tester via wireless transmission The indicator lig...

Page 7: ...ise it may present a risk of electric shock which can cause personal injury or death The insulation stick must be connected when performing testing by clamping high voltage line otherwise it may prese...

Page 8: ...or primary current If the tester displays OL for primary current it indicates the measured primary current is over the upper range specified by the high voltage clamp sensor To remove the high voltage...

Page 9: ...e clamp sensor to test circuit over 600V or 5A otherwise it may present a risk of electric shock which can cause personal injury or product damage 1 Connect the low voltage clamp sensor with the teste...

Page 10: ...150 5 150 150 100 0 3...

Page 11: ...by the nameplate at the current transformer If the actual test error is over the set error the symbol OL appears on bottom right of the LCD On site wire connection 6 Data Hold Storage When is pressed...

Page 12: ...or software can indicate maximum minimum and average values and have multiple functions including dynamic display real time monitoring alarming threshold setting alarming indication data viewing savin...

Page 13: ...rying bag 1 pc AAA alkaline dry battery 8 pc User manual 1 pc The content of this user manual cannot be used as a reason for using the product for special purposes The company is not responsible for o...

Reviews: