TECHNICAL PROGRAMMING MODE (ONLY QUALIFIED PERSONNEL):
Programming procedure:
PHASE 1
To enter programming of functional parameters, keep the key
pressed for about 8
seconds until the writing “PROGRAMMING MODE” appears.
PHASE 2
As soon as you have entered the program, on the subsequent screen it will be possible to see the first parame-
ter
(Parameter 0) with the value programmed in the memory.
PHASE 3
The parameters can be scrolled by using the direction arrows
and
present on the panel.
PHASE 4
After having selected the parameter to be modified, the value can be changed by pressing the
direction key
, the value of the parameter starts to flash. Press
and
to adjust the parameter value.
When you reach the desired value, it is memorised by pressing the key
.
PHASE 5
To modify other parameters, repeat the sequence scrolling with the direction arrows
and .
PHASE 6
After having set or changed the parameters, you must hold the key
pressed for 8 seconds to transfer
the
data to the non-volatile memory.
Correct connection of probes:
N.B. to correctly view the temperature measured by the probe, if the cable passes near electric cables or has an ex-
tension of over 3 metres, a shielded cable must be used for connection.
The following drawing specifies that the positive pole of the shielded cable must be connected to the odd number
terminal while the braid shield of the cable must be connected to the even number terminal.
This shields the probe line and eliminates disturbances.
Dielettrico isolante
“+” Polo cavo coassiale o cavo schermato
al morsetto dispari
Polo calza (schermo)
al morsetto pari
CAVO SCHERMATO
MORSETTIERA
1
2
3
4
SONDA
fig. 31
Shielded pole at even
number terminal
Insulating dielectric
„+“ Coaxial cable or shielded
cable pole at odd number terminal
PROBE
SHIELDED CABLE
TERMINAL BOARD