14
2.5.1 - DATA ACCORDING TO ErP DIRECTIVE
EXT 100
EXT 115
EXT 140
Element
Symbol
Unit
Effective nominal output
Pnominale
kW
99
112
132
Seasonal energy efficiency to heat
the room
ƞ
s
%
93
93
93
Season efficiency class to
discharge
A
A
A
For ch only and combination boilers: useful heat output
Useful Heat Output in high-tempera-
ture regime
(Tr 60 °C / Tm 80 °C)
P
4
kW
55,0
61,4
71,2
Useful efficiency at nom. heat output
in high-temperature regime
(Tr 60 °C / Tm 80 °C
ƞ
4
%
89
87,8
87,8
Useful heat output at 30% of nom.
heat output in low-temperature
regime (Tr 30 °C)
P
1
kW
18
20,5
23,7
Useful efficiency at 30% of nom. heat
output in low-temperature regime
(Tr 30 °C)
ƞ
1
%
97,5
97,6
97,6
Range-rated boiler: YES / NO
YES
YES
YES
Auxiliary electricity consumption
At full load
elmax
kW
0,474
0,474
0,474
At part load
elmin
kW
0,159
0,159
0,159
In stand-by mode
P
SB
kW
0,007
0,007
0,007
Other items
Heat loss in stand-by
P
stb
kW
2,68
2,68
2,68
Emissions of nitrogen oxides ref. PCI (PCS) NOx
Mg/kWh
48 (43)
56 (50)
58 (52)
Annual electricity consumption
Q
HE
GJ
349
424
653
For CH & DHw production boilers
Declarerd load profile
-
-
-
Energy efficiency in DHW production
mode
ƞ
wh
%
-
-
-
Daily electricity consumption
Qelec
kWh
-
-
-
Daily fuel consumptionl
Qfuel
kWh
-
-
-
Inside sound power level
Lwa
dB (A)
-
-
-
Annual electricity consumption
AEC
kWh
-
-
-
Annual fuel consumption
AFC
GJ
-
-
-
Seasonal efficiency class
in DHw production mode
-
-
-
*
Appliances not covered by directive 2009/15 / Ec