34
PARAMETER BMM MODULE
CODE
SYMBOL
PARAMETER DESCRIPTION
U.M.
RANGE
SETTING
FACTORY
MIN
MAX
803
Srv
Enabled services
0
3
0
31
HL
CH # 1:
Minimum value of the CH setpoint adjust
-
ment
°C
20
45
30
39
HH
Maximum value of the CH setpoint adjustment
°C
50
90
85
322
Po
Pump overrun time
min
0
10
5
341
PL
Pump minimum modulation level
%
0
100
40
313
Pr
Pump maximum modulation level
%
20
100
100
368
VA1
Relay Programmabile #1
0
1
0
773
dr
Enable the DHW request by the temperature
sensor
0
1
0
650
dL
Minimum value of the DHW setpoint adjustment
°C
25
45
40
385
dH
Maximum value of the DHW setpoint adjustment
°C
50
65
60
310
DpT
Pump overrun time after DHW operation
sec
0
600
30
360
dt
Storage tank regulation gain.
0
15
7
320
tH
Storage tank hysteresis
°C
0
30
0
309
St
Application code:
%
0
4
1
619
IG
Relative fan speed at burner pre-purge and ignition
%
0
100
45
314
Sb
Relative fan speed at burner standby
%
0
100
26
319
FH
Maximum relative fan speed
%
0
100
95
346
FL
Minimum relative fan speed
%
0
100
22
2590
Burner maximum capacity
kW
1
1000
70
483
rP
Water Δ-temperature protection:
°C
0
50
30
622
FS
Water minimum flow-rate protection
0
1
0
34
HY
Burner OFF hysteresis
°C
5
20
5
336
HS
Temperature control: slope limit.
°C/MIN
1
30
10
353
HP
Temperature control: proportional gain
0
50
25
354
HI
Temperature control: integrative gain
0
50
12
478
Hd
Temperature control: derivative gain
0
50
0
486
FP
Fan speed control: proportional gain
0
50
2
487
FI
Fan speed control: integrative gain
0
50
2
337
Fr
Fan speed slope (rpm/min)
rpm/min
0
30000
5000
526
FU
Maximum absolute fan speed
Hz
50
120
120
488
Fb
Fan PWM modulation at maximum fan speed
1
20
2
527
PU
Fan tacho: pulse/revolution
2
3
2
777
AFC
Burner air-flow check
0
1
0
793
COC
Chimney obstruction check
0
1
1
783
0
unknown parameter
0
1
0
896
TU
Temperature unit:
0
1
0
768
LG
Low gas pressure protection
0
1
0
771
PS
LowWaterFlow
0
2
1
1056
Fc
Installation loading factor
1
10
3
4.4 - PROGRAMMING THE OPERATING PARAMETERS
ATTENTION!
Function reserved for After Sale
Service Centres only.
ATTENTION!
These functions are explained
in chapter 2.8 (DEVICES menu)
of the Ufly P. TOUch cOnTROl
installation and maintenance
manual.