19
Installation instructions
3.6 - WATER FEATURES
The generator must be fed with water of
quality complying with the requirements set
out in this paragraph.
It must also be ensured that the feed water
and the system water cannot be polluted
by harmful substances (e.g. oil, grease, sea
water).
Standard of reference UNI EN 12953-10 or
UNI 7550.
Most of the waters are not suitable at source for use as feed
water of a steam generator. The type of feed water treatment
depends on the features of the water at source. Its features vary,
so regular checks of the chemical composition are required.
The water supply pipe, downstream of the chemical treatment,
must be fitted with a meter in order to detect the flow rate of the
top-up water added to the return condensate water; this also
allows direct control of the amount of steam intake.
It is appropriate to recover as much condensate water in the
supply tank as possible.
The condensate water must eventually be treated so as to meet the
requirements indicated for the generator feed water (as per table 1).
On the basis of these requirements, including those needed for
feed water (as per table 2), it is necessary that, depending on the
features at source and on the top-up flow rate, a water treatment
system be installed and allow binders to be added for oxygen
(possibly stabilisers for residue hardness, for alkalinisation or
phosphates) in the feed water tank or in its flow pipe.
These requirements should be checked by means of suitable
equipment and, if possible, easy to use every 24 or 72 hours,
depending on the operating mode, or according to local regulations.
Record the measured values, the top-up water flow rate, the
consumption of chemicals and the necessary maintenance
operations in the instruction manual, in order to be able to
always go back to the operating conditions.
WARNING
Do not put water with a temperature below 60°C in the generator.
It is recommended to put feed water with an average temperature of 80°C in the generator.
ATTENTION!
Damages caused by external agents (limescale, oxygen, acid attacks, etc.) are not covered
by the warranty.
Below are the quality requirements for the feed water and for the operating water according
to the European Standard EN 12953-10 (tables 1-2) and indications on the frequency of the
analyses (tables 3-4)
Table 1
FEED WATER FOR STEAM GENERATORS
Parameters
Unit
Feed water
Operating pressure
bar
0.5 - 20
> 20
Appearance
Clear, free from solid suspensions without persistent foam
pH
a,b
8.7 - 9.2
c
8.7 - 9.2
c
Total hardness
ppm CaCO
3
(°F)
< 1 (<1)
< 1 (<1)
Iron
ppm Fe
< 0.1
< 0.05
Copper
ppm CU
< 0.05
< 0.03
Oxygen
ppm O
2
< 0.05
d
< 0.02
d
Oils - greases
ppm
< 1
< 1
Organic substances
Not enough to cause traces, foams or other problems
a. for boilers fed with water with conductivity less than 30 pSicm use
of Na or K hydroxides is allowed only if the recommended pH range
cannot be obtained with the exclusive use of sodium phosphate;
b. for systems where there is no copper or its alloys, the feed water pH
must be higher than 9.2 ;
c. with water softened to pH > 7, it is necessary to respect the pH range
indicated for boiler waters; when operating without a degasser an ex-
cess of deoxygenating agent must be guaranteed;
d. the excess value to be guaranteed must be indicated by the supplier
of the additives used for chemical conditioning.
Summary of Contents for BAHR'UNO
Page 1: ...BAHR UNO INSTRUCTIONS ON INSTALLATION USE AND MAINTENANCE ...
Page 49: ......