40
To avoid corrosion by inactivity in the absence of pressure,
the smoke side and water side surfaces of the boiler must be
treated according to the duration of the functioning interruption.
There is a distinction between
wet conservation
(for which the
oxygen must be kept away ) and
dry conservation
(for which
humidity must be kept at minimum level).
Wet conservation
Fill the generator up to the highest level with treated supply wa-
ter. To prevent corrosion from oxygen, add a binder for oxygen
to the boiler water (e.g. sodium sulphite) well mixed to the boiler
water (thermal or mechanical recirculation).
A completely filled generator can be protected from corrosion
even by keeping the pressure with nitrogen (preferably nitrogen
5.0) to a value between 0.1 and 0.2 bar.
The wet conservation with chemical products allows the oxygen
to chemically bind, thus promoting protection from corrosion of
the boiler materials. The wet chemical conservation is designed
for steam generators during brief and prolonged inactivity peri-
ods.
Thanks to a sufficient content of binders for oxygen, to a suitable
alkalinisation, to proper mixing of the conservation solution and
to a complete filling of the boiler and of the system, the corrosion
from inactivity is easily and safely prevented.
This type of conservation MUST NOT, by
contrast, be used if there is a risk of frost.
WARNING
Before starting the generator again, carry out
the following operations:
- Completely discharge the water that was
used for the conservation;
- carefully wash and subsequently fill with
clean water and properly treated.
3.20 - INSTRUCTIONS FOR SHUTDOWN
AND STORAGE
Dry conservation
Warning
This method must be used in the event of pro-
longed inactivity periods and as protection
against frost. In this case, a short-term restart
is not possible.
Complete emptying
After shutdown for inactivity, the boiler can be quickly emptied
only when the pressure is about 3 bar. Adhere to the maximum
temperature allowed for input in the public ducting network. If
necessary, the water must be conveyed into a collection tank
and then drained after it has cooled down.
The steam generators' water side with a high salt content in the
boiler water (> 5000 µS / cm), must be washed again. Subse-
quently, manually open the manholes.
In dry and open boilers, apply drying products (e.g. silica gel,
blue gel) in flat bowls or hang them in a way that they remain
suspended and do not come into contact with the boiler materi-
als. Close the boiler. Check the drying substances at least once
a month and, if necessary, replace them.
Smoke side conservation
After putting the boiler out of service, clean the gas side of the
furnace and of the smoke ducts, by opening the smoke side in-
spections.
It is recommended to protect the combustion chamber and the
smoke passes with an anti-oxidising oil (graphite or paint). It can
be sprayed or applied with a brush. The doors must be opened.
Keep the surfaces dry during the inactivity period (using a dry-
ing agent, e.g. silica gel).
Close all external communications (chimney included).