Maintenance instructions
EVENT
Safety valve intervention
Leakage of the safety valve
Safety pressure switch intervention
Safety level switch intervention
Feed pump block
Insufficient water filling
Burner always on
Burner not ignited
PROBABLE CAUSE
Exceeding of maximum calibration pressure
of the valve
Loss of calibration of the safety valve
Deposits of dirt around the shutter seat
Scratching of the shutter seat
Intervention value of the PRESSURE TRANS-
DUCER too high
Faulty PRESSURE TRANSDUCER
Water level detection interrupted
Pump "circuit breaker" disconnected
Pump shaft blocked
Pump block
Valves closed
Line obstruction
Intake filter clogged
Anomaly level gauges
Level adjustment probes short circuit
Pump cavitation
Incorrect rotation direction of the pump
Incorrect lectrical connection to panel
Safety level regulator faulty
Adjustment pressure switches / pressure
transducer not active
Incorrect connection to control panel
Burner fuses blown / problems concerning the
burner
No consent to the burner by the PRESSURE
TRANSDUCER
No consent to the burner by the safety level
switch
Malfunctions
POSSIBLE SOLUTION
Check the intervention threshold of the pressure
switches
Check the calibration value of the valve
Cleaning of the seat by quick and repeated drives
of the manual opening lever of the valve
Disassembly of the valve and polishing of the seat
by means of a very fine abrasive
Check calibration of the safety pressure switch
Replacing the pressure switch
Rod encrusted / cable interrupted
Check motor absorption
Carry out maintenance
See section "Feed pump block"
Check opening of valves / clogging
Check and clean the suction / delivery pipe
Clean / replace filter
Check fault by alternating replacement (inversion)
of the relay inside the panel and replace the faulty
device
Disassembly of level probes and check the integrity
of the ceramic insulation. Replace if necessary.
Insufficient swing on the intake. Increase swing in
relation to the intake water temperature
Pump filter cleaning / replacement
Decrease resistance of condensate collection tank
duct - pump intake mouthpiece (… increase pas-
sage section/…)
Invert a phase
Check with wiring diagram
See section "Safety status level intervention"
Check calibration of pressure switches / pressure
transducer
Check connections of pressure switches to control
panel
See wiring diagram
Replace fuses / See the burner manual
Replacement of PRESSURE TRANSDUCER
See section "Safety status level intervention"