44
EVENT
Faulty burner adjustment
Lack of boiler pressurisation
Overheating
PROBABLE CAUSE
Dirt
Insufficient tightness of the smoke circuit
Irregularity of the flow of fuel
Limescale deposits
Deposits of dirt in the boiler
Incorrect boiler-burner coupling
Incorrect burner adjustment
Insufficient burner performance
Incorrect choice of boiler
Faulty safety level switch
POSSIBLE SOLUTION
Clean according to instructions provided in the burn-
er manual
Check the state of the gaskets, closure of the doors,
burner plate set up and connection to the chimney
fitting
Check the burner and power supply line according to
the instructions given in the specific burner manual.
Check presence of limescale and carry out a chem-
ical wash
Check cleanliness of the water side and smoke side
boiler
Check the correct coupling of boiler-burner
Check burner adjustment
Check burner performance
Check suitability of the boiler to the system
Immediate switch-off of burner, do not introduce wa
-
ter in the generator do not open the door until the
generator has cooled-down