ROUTINE YEARLY VERIFICATION OPERATIONS
COMPONENT:
VERIFY:
CONTROL/INTERVENTION
METHOD:
FL
(domestic hot water
priority flow switch
( 2 )
Is the minimum domestic hot water
flow rate 3 l/min.?
The burner must ignite with an
intake above or equal to: 3 l/min.
VG
(Gas valve)
( 3 )
Does the valve modulate properly?
Open a hot water tap at maxi-
mum flow rate and then at min
-
imum. Make sure that the flame
modulates.
SR (heating sensor)
( 11 )
SS (domestic hot water sensor)
( 1 )
SSR (return sensor)
( 22 )
Do the sensors maintain the
original characteristics?
Disconnect the sensor, place it
in the room, measure the resist-
ance value and, through the ta
-
ble Res / Temp (previous page),
check that it corresponds to the
room temperature measured by
a thermometer
E ACC/RIV. (ignition/detection
electrode)
( 4 )
Does the discharge of sparks before
putting the boiler in safe conditions last
less than 10 sec.?
Detach the electrode ionisation
wire and check the securing
time.
TL (anti-overheating
limit thermostat)
( 10 )
Does the TL put the boiler in safety
conditions when overheating?
Heat the TL until it intervenes
and check that it intervenes.
DK (safety pressure switch
against water deficiency)
( 13 )
Does the pressure switch block the
boiler
if the water pressure is below 0.4 bar?
Without request: close the shut-
off valves of the heating circuit,
open the drain valve to make the
water pressure decrease. Before
pressurising again, check the
pressure of the expansion vessel.
Expansion vessel
( 8 )
Does the vessel contain the right
amount
of air?
Check the pressure in expansion
vessel (1 bar when the boiler
is empty). Pressurise the boiler
(open the pump automatic vent
valve). Open the heating circuit
closing valves.
Condensation drain trap
(26)
Has the trap got deposits on the
bottom?
Clean the trap with water.
Domestic hot water flow rate
Filter in cold water inlet
( 2 )
Clean the filter with limescale
remover.
Heat exchanger body
(24 )
Check that the space between the
rungs of the exchanger are not clogged
Eliminate the deposits without
damaging the exchanger, using
a soft bristle brush and specific,
non flammable detergents.
Burner
( 28 )
Check the state of cleanliness of the
burner mesh
Remove any deposits using
compressed air, blowing from
the mesh side.