ATTENTION!
Function reserved for Authorised As-
sistance Centres only.
4.2 - PARAMETERS THAT CAN BE EDITED FROM THE CONTROL PANEL
1
ACTIVATION - SELECTION
Press reset buton
(D)
for 10 sec. then release
(service flashing)
Turn knob
(B)
to scroll through the menu’
INFORMATION
Press reset
(D)
to access the Inf parameters unit
PARAMETERS LIST InF
The display alternates the Parameter and Value
CODE DESCRIPTION
FS
Heating temperature, - - if the heat-
ing sensor is faulty
oS
External temperature, - - if there is
no external probe or if it is faulty
dS
Domestic hot water temperature, - - if
there is no sensor or if it is faulty
rS
Return temperature, - - if there is no
auxiliary sensor or if it is faulty
dt
Differential ∆t between flow and
return.
ICH
Heating temperature calculated,
(been ‘‘room zone’’ ON-OFF and
‘‘remote zone’’ OT+.)
FP
Air Fan signal pressure
(Pa)
PH
Water pressure, is there is not pres-
sure sensor, - - is displayed
Sr
Firmware version (Factory)
Sd
Firmware version (Servicing)
Io
Ionization Current (µA)
DISPLAY
Turn knob
(B) to display the parameter list InF
2
Menu access:
InF
InFormation
Hi
Errors Log
SE
SErvice
FA
Factory
tA
tAratura _CALIBRATION
service
service
service
service
service