14
Installation info
fig. 10
Pursuant to the directives of regulations in
force, discharge of forced draught boilers can
2.2.7 - POSITIONING OF TERMI
NALS FOR TYPE ‘’C’’
BOILERS
either take place through the roof or directly
outwards the room they are installed in. The
following distances shall be considered for
terminals proper positioning:
POSITIONING OF TERMINALS FOR "FORCED DRAUGHT" BOILERS
Min.
POSITIONING OF THE TERMINAL
distances in mm.
Under a window
A
600
Under a ventilation opening
B
600
Under a gutter
C
300
Under a balcony (1)
D
300
From an adjancent window
E
400
From an adjacent ventilation opening
F
600
From vertical or horizontal air pipes or drains (2)
G
300
From an external corner of the building
H
300
From an internal corner of the building
I
300
From the ground or from another floor
L
2500
Between two vertical terminals
M
1500
Between two horizontal terminals
N
1000
From a facing front surface without opening or teminals within a radius
of 3 mt. from smoke outlet point
O
2000
As above, but with openings or terminals within a radius of 3 mt. from
smoke outlet point
P
3000
NOTES
(1)
Terminals below a practicable balcony shall be arranged in such a way as to assure that the total run of smokes, from their outlet from
terminal up to outlet from balcony external perimeter, including the height of protection baluster, if any, is not less than 2 m.
(2)
Distances of not less than 500 mm shall be adopted in placing the terminals, due to the proximity to materials subject to the action of
products of combustion such as plastic gutters or waterspouts, wooden jetties, etc.) unless adequate screeening measures are taken for
the said materials.
FLUE TERMINAL POSITIONING
Summary of Contents for EVE 05 CTFS 24 F
Page 35: ...35 ...