Installation Instructions
3.12 - MISURA IN OPERA DEL RENDIMENTO DI COMBUSTIONE
3.12.1 - ACTIVATION OF THE CALIBRATION FUNCTION
1
ACTIVATION (from Service Panel)
By pressing the button (
D
) for 3 seconds, the calibration function is activated. Release it when the SER
-
VICE symbol appears,
Do not press it for more than 9’’
(par. 4.2)
This function is not activated if there is
a block or domestic hot water request.
2
MAXIMUM OUTPUT
By turning the knob (B) onto MAX, the boiler will operate at
maximum output:
- 3 illuminated symbols
4
DISABLING
The “calibration” function stays active for 15 minutes.
To disable the
CALIBRATION
function before the time elapses, switch the boiler on and off again by
acting on the main switch
.
3
MINIMUM OUTPUT
By turning the knob (B) in position , the boiler will operate at
minimum output
:
- 2 illuminated symbols
- 1 flashing
ATTENTION!
Function reserved for Authorised
Assistance Centres only.
The user is NOT authorised to activate the func-
tion described below.